| 1 | BUILDING |
| 2 | EARTHWORK: |
| 3 | Earth work in excavation in foundation trenches or drains including dressing of sides and ramming of bottoms lift upto 1.5M including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50M(a) All kinds of soil. |
| 4 | Filling available excavated earth ( excluding rock) in trenches, plinth sides of foundation etc. in layers not exceeding 20 cm in depth consolidating each deposited layer by ramming & watering lead upto 50 m and lift upto 1.5 m |
| 5 | Supplying and filling in plinth with sandy soil under floors including watering, ramming, consolidating and dressing complete. |
| 6 | CEMENT CONCRETE WORKS: |
| 7 | Providing and laying in position cement concrete of specified grade excluding the cost of centering, shuttering,- All work upto plinth level:(a) 1:4:8(1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size ) |
| 8 | RE-INFORCED CEMENT CONCRETE WORKS: |
| 9 | Providing and laying inpositionready mixed plain cement concreteor site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana/ Ordinary Portland/ Portland Slag cement, admixture in recommended proportions as per IS:9103 to accelerate / retard setting of concrete,to improve ductility and workability without impairing strength;including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of Engineer-in-charge; for the follwing grades of concrete. All work upto plinth level: |
| 10 | (a) Concrete of M-25 grade with minimum cement content of330 kg/cum. |
| 11 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15 degree landings, balconies, shelves, chajas, lintels, bands, plain window sills, staircases and spiral staircases upto floor five level excluding the cost of centering, shuttering, finishing and reinforcement with |
| 12 | (a) 1:1.5:3 (1 cement: 1.5 coarse sand : 3 graded stone aggregate 20mm nominal size) |
| 13 | Reinforced cement concrete work in walls (any thickness) i/c attached pillasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. upto floor five level but excluding the cost of centering and shuttering and reinforcement: |
| 14 | (a) 1:1.5:3 (1 cement: 1.5 coarse sand : 3 graded stone aggregate 20mm nominal size) |
| 15 | STEEL REINFORCEMENT: |
| 16 | Reinforcement for RCC work i/c straightening, cutting, bending, placing in position and binding all complete. |
| 17 | (a) Thermo-Mechanically Treated bars |
| 18 | FORM WORKS: |
| 19 | Providing form work i/c centering & shuttering so as to give a rough finish, strutting and propping etc. height of propping and centering below supporting floor to ceiling not exceeding 4m and removal of the same for in-situ reinforced concrete and plain concrete work in: |
| 20 | a). Foundation, footing, bases of column etc and mass concrete. |
| 21 | b). Column, pillar, posts and struts (square rectangle or polygon in plain). |
| 22 | c). Lintels, beams , plinth beams, girders, bresummer and cantilever withwater proof ply12 mm thick |
| 23 | d). suspended floor,roofslandingbalconies ans access platform withwater proof ply12 mm thick |
| 24 | e).Stairs (excluding Landings) except spiral-staircase. |
| 25 | f). Weather shade, Chhajjas corbels etc. including edges |
| 26 | g) Vertical and Horizontal Fins individually or forming box louvers band, facias and eaves. |
| 27 | BRICKWORKS: |
| 28 | Brick work with 1st class burnt clay F.P.S(non modular) bricks in foundation & plinth in cement mortar 1 : 4 (1cement :4 coarse sand). |
| 29 | HalfbrickmasonrywithIstclasscommonburntclayF.P.S.(non modular) bricksin superstructure above plinth level upto floor V level in cement mortar 1 : 3 (1cement :3coarse sand). |
| 30 | WOOD WORKS: |
| 31 | Providing wood work in frames of doors, windows, clerestorywindows andotherframes wrought framed and fixed in position with hold fast lugs or with dash fastener of required dia. And length (hold fast or dash fastener shall be paid for seperately(a) Local best quality Teak wood |
| 32 | Providing and fixing panelled or paneled and glazed shutters for doors,windowsand clerestory Windows i/c ISI marked M.S.butt hinges bright finished of required size with necessary screws, excluding panelling which will be paid for seperately, all complete as per direction of Engineer-in-charge.(a)Local best quality Teak wood. -35 mm thick shutters |
| 33 | Providing 40X3mm flat iron hold fast 40cm long i/c fixing to frameswith 10mm dia. Bolts, nuts and wooden plugs and embedding in cement concrete block 30X10X15 cm 1:3:6 mix (1 cement : 3coarse sand: 6 stone aggregate 20mmnominal size). |
| 34 | Providing and fixing bright finished brass 100 mm door mortice latch with one dead bolt and a pair of lever handles with necessary screws etc. complete (best make of approved quality). |
| 35 | Providing and fixing ISI marked oxidised M.S. Tower bolts black finished(barrel type ) with screws etc. complete. |
| 36 | (a) 250x10mm |
| 37 | (b) 100x10 |
| 38 | Providing & fixing ISI marked oxidisedM.S. Sliding bolts with screws etc. Complete.(a) 250X16mm. |
| 39 | FLOORING: |
| 40 | Providing and laying vitrified floor tiles in different sizes(thickness to be specified by the manufacturer) with waterabsorption’s less than 0.08% and conforming to IS : 15622 ofapproved make in all colours and shades, laid on 20mm thickcement mortar 1:4 (1 cement: 4 coarse sand) including groutingthe joints with white cement and matching pigments etc.,complete. |
| 41 | Size of Tile 600 x 600 mm |
| 42 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer),with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (Icement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm. including grouting the joint with white cement & matching pigments etc.complete. |
| 43 | Size of Tile 600x600 mm |
| 44 | STEEL WORKS: |
| 45 | Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffering, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-Charge, (for payment purpose only weight of the stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 46 | Providing and fixing in position collapsible steel shutters with vertical channels 20xl0x2mm and braced with flat iron diagonals 20x5mm size with top and bottom rail of T-iron 40x40x6mm with 40mm dia, steel pulleys complete with bolts, nuts, locking arrangement, stoppers, handles, including applying a priming coat of approved steel primer. |
| 47 | Steel work in built up tubular ( round, square or rectangular tubes etc.) including cutting, hoisting fixing in position and applying a priming coat of approved steel primer, including welding and bolted including special shaped washers etc. complete. |
| 48 | Electric resistant welded tube (Conforming to IS:1611-1979) |
| 49 | Providing & fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-Charge) with zinc caoting 120 grams per sqm as per IS:277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metres or as desired by Engineers-in-charge. The sheet shall befixed using self drilling /self tapping screws of size (5.5x 55 mm)with EPDM seal,complete upto any pitch in horizontal/ vertical orcurved surfaces, excluding the cost of purlins, rafters and trussesand including cutting to size and shape wherever required with |
| 50 | Precoated galvanished iron profile sheets 0.50 mm thick . |
| 51 | Providing & fixing precoated galvanised steel roofing accessories, Zinc caoting 120 grams per sqm as per IS:277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/self tapping screws or with polymer coated J or L hooks, bolts and nuts and or GI seam bolts and nuts, G.I plain and bitumen washers complete : |
| 52 | Ridges plain (500 -600mm) |
| 53 | Precoated galvanished iron profile sheets 0.50 mm thick . |
| 54 | Providing and fixing false ceiling with 12 mm thick plain/semi perforated or with design ceiling tiles of BWP type phenol formaldehyde synthetic resin bonded pressed particle board conforming to IS:3087 finished with a coat of aluminium primer on both sides & edges and two coats of synthetic enamel paint of approved quality on exposed face fixed to a grid made out of anodised aluminium ( with 15 micron anodic coating) T-sections 35X15X1.5 mm size main runners and cross runners 23.5X19X1.5 mm fixed to main runners placed 600 mm centre to centre both ways so as to form a grid of 600 mm square. the frame work shall be suspended from ceiling by level adjusting hangers of 6mm dia M.S rod fixed to roof slab by means of ceiling cleats. The suspenders shall be placed 600X1200 mm centre to centre including fixing to the frame with C.P brace screws and applying a priming coat of zinc chromate yellow primer (aluminium frame work shall be paid separately.) |
| 55 | Providing and fixing 20 mm Plank as eave board with Tolhao / Uchanwood |
| 56 | FINISHING: |
| 57 | 15mm cement plaster on rough side of single or half wall of mix: 1: 4 (1 cement : 4 coarse sand) |
| 58 | 12mm cement plaster 1:3 (1 cement: 3 coarse sand ) finished with a floating coat of neat cement . |
| 59 | Providing and applying white cement based putty of average thickness1mm of approved brand and manufacturer over plastered surface to prepare the surface even and smooth complete. |
| 60 | Distemperingwith oil bound washable distemper of approved brand and manufacturer to give an even shade. New work (two or more coats) over and including priming coat with cement primer :- |
| 61 | Finishing walls with Arcylic Smooth exterior paint of requierdshade :New work (two or more coat applied @ 1.67 ltr/10 sqm. Over and including base coat of water proofing cement applied @ 2.20 kg/10 sqm) |
| 62 | Making plinth protection 50 mm cement concrete 1:3:6 (1 cement:3 coarse sand:6 graded stone aggrt. of 20 mm nominal size)over75 mm bed of dry brick ballast 40 mm niminal size well rammed ans consolidated and grouted with fine sand including finishingthe top smooth. |
| 63 | Supplying and installation of 8 passenger (load 630 kg) machine roomless (MRL) lift, speed not less than 1m/s as per direction of engineer in charge including all accessories complete. |
| 64 | WATER SUPPLY AND SANITARY INSTALLATION |
| 65 | EARTH WORK : |
| 66 | Earth work in excavation by mechanical means ( Hydraulic Excavator ) / manual means in foundation trenches or drains ( not exceeding 1.5 m in width or 10 sqm on planincluding dressing of sides and ramming of bottoms lift upto 1.5 metres including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 metres |
| 67 | All kinds of soil |
| 68 | Filling available excavated earth (excluding Rock) in trenches, plinth, sided of foundation etc. In layers not exceeding 20 cm in depth consolidating each deposited layer by ramming and watering, lead up to 50mm and lift up to 1.5m. A) All kinds of soil. |
| 69 | P.C.C WORK : |
| 70 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering. |
| 71 | 1:3:6( 1cement:3 coarse sand:6 gradedstone aggregate 40mm nominal size) |
| 72 | 1:4:8( 1cement:4 coarse sand:8 gradedstone aggregate 40mm nominal size) |
| 73 | FORM WORK: |
| 74 | Centering and shuttering including strutting, propping etc and removal of form for. |
| 75 | (a)Foundation, footing, bases of column etc and mass concrete. |
| 76 | Suspended floors, roofs, landing, balconies and access platform. |
| 77 | RCC WORK: |
| 78 | Reinforced cement concrete work in beams,suspended floors, roofs having slope upto 15 degree landing, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level upto floor five level excludingcost of centering, shuttering, finishing and reinforcement in (a) 1:1.5:3 ( 1cement : 1.5 coarse sand : 3 graded stone aggregate 20mm nominal size). |
| 79 | Reinforcement for RCC worksincluding straightening, cutting, bending placing and binding all complete upto plinth level. |
| 80 | Thermo-Mechanically Treated bars |
| 81 | Brickworks: |
| 82 | Brick work with 1st class common burnt clay F.P.S ( non modular ) bricks in foundation and plinth ina) Cement mortar 1:4 ( 1 cement : 4 coarse sand ) |
| 83 | Half brick masonry with 1st class common burnt clay F.P.S( non modular )brick in superstructure above plinth level and upto floor five level. a) Cement mortar 1:3 ( 1 cement : 3 coarse sand ) |
| 84 | Honeycomb brick work 10/11.4 cm thick with 1st class common burnt clay F.P.S (non modular ) brick in superstructure above plinth level and upto floor V level in cement mortar 1:4 (1 cement: 4 coarse sand) |
| 85 | Flooring: |
| 86 | Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only. Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. |
| 87 | Double charge vitrified tile polished finish of size Size of Tile 600 x 600 mm |
| 88 | Cement concrete flooring 1:2:4 (1 cement: 2 coarse sand: 4 stone aggregate )finished with a floating coat of neat cement including cement slurry, but excluding the cost of nosing of steps etc complete. A) 40 mm thick with 20 mm nominal size stone aggregate. |
| 89 | 15mm cement plaster 1:3 (1 cement: 3 coarse sand ) finished with a floating coat of neat cement on theroughside of single or half brick wall. |
| 90 | SANITARY INSTALLATION |
| 91 | Providing and fixing white vitreous china pedestal type water closet (European type W.C.pan )with seat and lid, 10 litre low level white P.V.C flushing cistern, including flush pipe, with manually controlled device ( handle lever ) conforming to IS : 7231, with all fittings and fixtures complete, including and making good the walls and floors wherever required : a) W.C pan with ISI marked white solid seat plastic seat and lid. |
| 92 | Providing and fixing wash basin with C.I brackets, 15 mm CP brass pillar taps, 32 mm C.P brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever required : |
| 93 | White Vitreous China Flat back wash basin size 450x300 mm with single C.P brass pillar tap. |
| 94 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 95 | Providing and fixing Chlorinated Polyvinyl chloride ( CPVC ) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings this includes jointing of pipes && fittings with one steps CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in charge. |
| 96 | 80 mm dia outer dia pipes |
| 97 | 100 mm dia outer dia pipes |
| 98 | Water Supply |
| 99 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps i/c cutting and making good the walls etc. (Internal work - Exposed on wall). |
| 100 | 15 mm nominal outer diameter pipes |
| 101 | 20 mm nominal outer diameter pipes |
| 102 | 25 mm nominal outer diameter pipes |
| 103 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps i/c cutting and making good the walls etc. (External work ). |
| 104 | 25 mm nominal outer diameter pipes |
| 105 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings. This including joining of pipes and fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. |
| 106 | 150 mm nominal outer dia Pipes |
| 107 | Providing and fixing bib cock of superior quality |
| 108 | 15 mm nominal bore |
| 109 | Providing and fixing C.P brass stop cock of superior quality. |
| 110 | 15 mm diameter |
| 111 | Providing and fixing gun metal non - return valve of approved quality ( screwed end ). |
| 112 | 25 mm nominal bore |
| 113 | Providing and fixing C.P.brass shower rose with15mm or 20mm inlet |
| 114 | 100 mm diameter |
| 115 | Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement: 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement: 2 coarse sand: 4 graded stone aggregate 20mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 (1 cement: 5 fine sand: 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement: 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design: |
| 116 | With Ist class common burnt clay F.P.S. (non modular) bricks |
| 117 | Texmo ACS 1575E 2HP single phase monoblock pump |
| 118 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS: 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 119 | 10,000 litres net capacity storage tanks |
| 120 | PROVIDING ELECTRIFICATION AND INSTALLATION |
| 121 | Wiring for light point / fan point/Exhaush Fan point /call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface /recessed steel conduit with modular type switch,phemolic laminated sheet suitable size M.S. box and earthing the point with 1.5 sq.mm FR PVC insulated copper conductor single core cable etc as required. |
| 122 | Group C |
| 123 | Wiring for light point /power point plug with 2x4 sq.mm FR PVC insulated copper conductor single core cable in surface /recessed steel conduit alongwith 1 no.4.sq.mm FR PVC insulated copper conductor single core cable for loop earting etc as required. |
| 124 | Wiring for circuit / sub main wiring alongwith earth wire with following size of FR PVC insulated copper conductor, single core cable in surface /recessed steel conduit as required. |
| 125 | a) 2X1.5.mm² +1x1.5mm² earth wire |
| 126 | b) 2X2.5.mm² +1x2.5mm² earth wire |
| 127 | c) 2X4.mm² +1x4mm² earth wire |
| 128 | d) 2X6.mm² +1x6mm² earth wire |
| 129 | Sub- Head-II |
| 130 | ( Fittings & Accessories) |
| 131 | S/F Recess Mounting LED down Lighter BGSL 0101WH,220223,cast aluminium housing fixed with collimated lens,1x1W white LED mounted on MCPCB ,extruded Al heat sink spring loaded mounting clips, complete with connections etc as reqd. |
| 132 | Supplying, installation testing and commissiong of ceiling fan, capacitor type suitable for low voltage operation including wiring the down rods of standard length (upto 30 cm ) with 1.5 sq.mm FR PVC insulated, copper conductor, single core cable including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. (ISI marked approved) |
| 133 | a) 1200 mm sweep |
| 134 | S/F stepped type electronic fan regulator on the modular plate switch box i/c connection but excluding modular plate as reqd. |
| 135 | 305mm sweep exhaust fan complete with all accessories connection etc as required |
| 136 | S/F Light Plug Point Modular Type Accessories |
| 137 | (a) S/F suitable size G.I. box with modular plate and cover in front on surface or in recess i/c P/F 3 pin 5/6 amp modular socket outlet 5/6 amp modular switch, connection painting etc. (Light plugs to use in non-residentail building). |
| 138 | S/F Power Plug Point Modular Type Accessories |
| 139 | (a) S/F suitable size G.I. box with modular plate and cover in front on surface or in recess i/c P/F 6 pin 15/16 amp modular socket outlet 15/16 amp modular switch, connection painting etc. |
| 140 | Supply and fixxing of following size of PVC casing and capping along with accessories etc. |
| 141 | (a) 20mm |
| 142 | S/F 2 ton capacity split type Air conditioner (Diamond, 3 star , 5G 29, G-SC 24 FD 3 WJH) complete with indo voltage stabilizer Automatic 5 KVA ( 140-280 for 2 ton). |
| 143 | S/F 35ltr water heater (Geyser) A.C. 2kw vertical type with all acessories, (150581 SKT-Plus 35L) i/c connection etc as reqd. |
| 144 | Sub-Head - III |
| 145 | ( Earthing ) |
| 146 | P/F lighting conductor finial made of 25mm dia 300mm long copper tube having single prong at top with 85mm dia 3mm thick copper plate i/c holes etc. Complete as reqd |
| 147 | p/f copper tape in horizontal run p/f copper tape 2ommx3mm thick on parapet or surface of wall for lightning conductor as reqd(for horizontal run) |
| 148 | p/f copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as reqd(for vertical run) |
| 149 | Earthing with copper earth plate 600 mmx 600mmx6mm thick i/c accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) as reqd. |
| 150 | Extra for using Salt & Charcoal for copper plate with electrode as reqd. |
| 151 | Earth connection from earth electrod with 4mm dia in 15mm GI pipe as required |
| 152 | Sub- Head- IV |
| 153 | (DB,s & MCB,s) |
| 154 | S/F (Following way) Single/Double pole and neutral, sheet steel MCB distribution board, 240V on surfuce/ recessed complete with tinned copper bus bar, neutral bus bar, din bar, detachable gland plate, interconnection, phosphatized powder painted i/c earthing etc as reqd. (but without MCB/RCCB/Isolator). |
| 155 | S/F \"B\" series,SP MCB. Supplying and fixing following 5 amps to 32 amps rating 240 Volts, B series, miniture circuit breaker suitable for lighting and other load of following poles in the existing MCB DB complete with connection, testing and commissioning etc as required. |
| 156 | a) Single Pole |
| 157 | S/FDP MCBisolator: Supplying and fixing following rating, four pole,240 volts, isolator in the existing MCB DB complete with connection, testing and commissioning etc. as required. |
| 158 | a)100 amps. |
| 159 | Sub- Head- V |
| 160 | ( Rising Main & Meter Board ) |
| 161 | P/F 400Amp TPN stand ground on load on load change own switch (compact design) 415/500v including connection to as required. |
| 162 | S/F Busbar chamber with 4 strips copper busbar of length 600mm suitable for 200 amps capacity complete with all accessories i/c connection earthing the body as required. |
| 163 | FIRE FIGHTING WITH WET AND SPRINKLER SYSTEM |
| 164 | Providing & Fixing of M.S. pipeincluding of primer & red paint , fashner, MS bend , tei rod, universal clamp, MS socket,MS flange nut bolt , Gasket etc. Make : Nizone |
| 165 | 150 mm dia |
| 166 | 100 mm dia |
| 167 | 80 mm dia |
| 168 | 50 mm dia |
| 169 | 25 mm dia |
| 170 | Supply and fixingHydrant valve |
| 171 | Supply and fixing RRL hose pipe 15 mtr. Long including male female coupling |
| 172 | Supply and fixing Branch pipe |
| 173 | Supply and fixing Hose box |
| 174 | Supply and fixing Hose reel hose with drum 30 mtr long |
| 175 | Supply and fixing Two way Valve |
| 176 | Supply and fixing ABC type fire extinguisher 4 kg |
| 177 | Supply and fixing CO2 type fire extinguisher 4.5 kg |
| 178 | Supply and fixing Pendent type Sprinkler |
| 179 | Supply and fixing 25 mm ball valve including of fittings |
| 180 | Supply and fixing Butterfly Valve 100 mm dia |
| 181 | Supply and fixing Butterfly Valve 50 mm dia |
| 182 | Supply and fixing Non Return Valve 100 mm dia |
| 183 | Supply and fixing Foot Valve 100 mm dia |
| 184 | Supply and fixing Foot Valve 80 mm dia |
| 185 | Supply and fixing of Pressure Switch |
| 186 | Supply and fixing Pressure Gauge |
| 187 | FIRE FIGHTING ALARM |
| 188 | FIRE ALARM SYSTEM |
| 189 | Supply, Installation & Commissioning of heat detector operating at 54/57 Degree Centigrade wit rate of rise cum fixed temperature( dual thermistor) type with mounted based complete with all connection etc. as required. |
| 190 | Supplying, installing, testing and commissioning of intelligent Addressible Manual pull station with necessary accessories.etc. |
| 191 | Supplying, installing, testing and commissioning of intelligent Addressible Hooter with necessary accessories etc. |
| 192 | Supplying, installing, testing and commissioning of 2 core x 1.5 sq. mm, Armoured cables FRLS type confirming to IS standards and specifications. |
| 193 | Supply and drawing of cable fire retardant PVC insulated copper conductor cable in the existing surface/ recessed steel conduit of following pairs, cores and size including connections and interconnections etc. |
| 194 | Speaker Cable Single Pair 2Cx 1.5 Sq.mm |
| 195 | Speaker Cable Two Pair 2Cx 1.5 Sq.mm |
| 196 | Fire Alarm Control panel with Lead acid battery back up for 8 hours normal operation and 15 minutes alarm operation. The control panel, battery charger etc, shall be as per requirement. 4 Loop Panel |
| 197 | Supply, Installation & Commissioning of heat detector operating at 54/57 Degree Centigrade wit rate of rise cum fixed temperature( dual thermistor) type with mounted based complete with all connection etc. as required. |
| 198 | HAND APPLIANCES |
| 199 | Supply of 4.5 KG. Capacity CO2 Type Fire Extinguishers. |
| 200 | Supply of 6 KG. Capacity ABC Type Fire Extinguishers |
| 201 | Supply of 09 Ltr. Capacity AFFF Type Fire Extinguishers |
| 202 | LAND DEVELOPMENT |
| 203 | EARTH WORKS: |
| 204 | Banking excavated earth in layers not exceeding 20 cm in depth, breaking clods, watering, rolling each layer with 1/2 tonne roller or wooden or steel rammer and rolling every third and topmost layer with power roller of minimum 8 tonne and dressing up in embankment for roads marginal banks flood banks and guide bank lead upto 50 metres and lift upto 1.5 metre |
| 205 | Hard/Dense Soil |
| 206 | EXTERNAL SERVICES |
| 207 | Kirloskar 25kVA Three Phase DG - Indobazzar |
| 208 | 50 sq.mm Aerial Bunched Cable (ABC) is a type of low-tension (LT) power distribution cable designed for overhead installations,typically rated up to 1.1 kV. |
| 209 | Cost of 65mm dai G.I. Pipe,light duty. |
| 210 | Gi Octagonal Street Light Pole - 5-12 Mtr, Rust Proof For Outdoor And Highway Use, Sleek Silver Finish, Aesthetic And Easy To Maintain |
| 211 | Erection of stell tuber pole of length not less than 8 mtrs but not exceeding 10 mtrs in cement concrete 1:3:6 ( 1cement:3 coarse sand 6 graded stone agtt.40mm nominal size ) foundation i/c.excavation & re filling etc.as reqd. |
| 212 | MS Cross Arm. More Similar MS Cross Arm. MS High Mast Pole |
| 213 | MS V Cross Arms With Back Clamp |
| 214 | Providing of Main Pannel (External) connection |
| 215 | TELEPHONIC CONDUITS |
| 216 | Telephone Wiringin existing conduit |
| 217 | Supplying and drawing (following pair) 0.5 FR PVC insulated copper conductor unarmoured telephone cable in the existing surface/recessed steel/PVC conduit as reqd |
| 218 | TV Cable in existing conduit |
| 219 | Supply and drawing Co-Axial TV cable RG-6 grade 0.7mm solid copper conductor PE insulated shielded with file tinned copper braid and protected in PVC sheath in existing surface/recessed steel/PVC conduit as reqd |
| 220 | SOIL TESTING |
| 221 | Mobilisation of necessary equipment and man-power at the project site and demobilisation of the same on completion of field work.Shifting and erecting from one bore hole to another.Boring 150mm dia. Dia holes in all kinds of soil upto a maximum depth of 40.00m (N=100) whichever is met earlier including collection of undistrubed samples from cohesive soil only at 3.0m interval (upto N=30) and conducting Standard Penetration Test at 1.5m IntervalsConducting necessary Laboratory Test.Submission of the final report in triplicate including recommendation for the type of foundation and bearing capacity. |