| 1 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth for laying pipes in trenches/rectification of leakages and getting out in soft/loose soil complete all as specified and as directed. |
| 2 | Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exe 25 cm complete all as specified and as directed. |
| 3 | Removing excavated soil n exc 50 M and depositing where directed at level n.exc 1.5 M above the starting point complete all as specified and as directed. |
| 4 | Taking out the sluice valve steel spindle and refacing, re-grinding and refixing of the following size after cleaning dust, greasing etc |
| 5 | 80mm dia |
| 6 | 100mm dia |
| 7 | 150mm dia |
| 8 | 200mm dia |
| 9 | Supply and fix in replacementof centric butterfly valves wafer Type PN 1.6 as per BS-5155 &IS-13095 lever operated body grey castiron disc -SGI Epoxy coated Disc seal-Nitrile/Epdm in gear operated of following sizes confirming to IS specification all as specified including taking down unserviœable accessories all as specified and as directed. |
| 10 | 150 mm dia |
| 11 | 100 mm dia |
| 12 | Supply and replace worn out / rusted nut, bolts andwasher in repairs of any size wherever necessary all as specified and as directed. |
| 13 | Supply and fix in replacement of old unserviceable MS pipeIS-1239marked(heavyduty)exposedin multistoried building including all fittings like coupling, bends, elbows, tees etc. and suitable fixing arrangementfor pipe support such as MS round, angles, channels, plate including cutting to size welding completeincluding painting the whole surfaœs of MS pipe with synthetic enamel paint as per colour code over two coats of zinc chrome primer all as specified and as directed. |
| 14 | 80 mm dia |
| 15 | 100 mm dia |
| 16 | 150 mm dia |
| 17 | Material and labour for cutting existing CI pipe/MS pipes in position for rectification of leakages/replacment of unserivceable pipes of the following sizesNote : The new pipes/Joints will be measured and paid seperately. |
| 18 | 80 mm dia |
| 19 | 100 mm dia |
| 20 | 150 mm dia |
| 21 | Material and labour for replacement of 150mm MJ Collar with nut and bolt including taking out old unserviceable collarNote : Earthwork & cutting of pipes measured seperately. |
| 22 | Supply and fixin replacement of oldunserviceable Cl specialssuchasbends (anytype,radius,and angle)tapers any type (straight, bend, or double sockets etc) Teepieces,singIebranch\"Y\"junction, double branch(allsockets or socket and spigot) cross,coIIars caps and plugs etc upto 150mm bore, complete all as specified and as directed. |
| 23 | Supply and fixinreplacementof63mmdiagunmetalbranchpipewithnozzleconformingtoIS903includingtakingdown unserviceable, complete all as specified and as directed. |
| 24 | Supply and fixinreplacementofgunmetalfireHydrant valvewith5 mmflangedinletand63mmfemalesingleheaded instantaneousoutlet complete with Lug & Chain as per IS-5290 hydrostatically tested to 21 Kgf/cm2 of pressure having a flow rate of 900 LPM at 7Kgf/m2 including taking down unserviceable complete all as specified and as directed. |
| 25 | Supplyand fix in replacement of 20mm Gun metal gate valveswith iron wheel headscrewed both ends for iron pipe, confirmingtoISspecificationallasspecified includingtakingouttheunserviceablecompleteallasspecifiedand as directed. |
| 26 | Supply and fix in replacement of Fire brigade inlet connection4 way completewith Lug & Chain as per IS 5290 Hydrostatically tested to 21 Kgf/cm2 of pressure having a flow rate of 900 LPM at 7Kgf/m2 all as specified and as directed. |
| 27 | Supply and fix in replacementof fire hose 63 mm dia confirming to IS:636, 15 meter length including gunmetal heavy duty pair of male and female couplings all as specified and as directed. |
| 28 | Supply and fix in replacementof sluicevalve, non rising spindle flanged end of class PN 1.6 with stainlesssteel spindle with all accessories suitableforsize80mmdiaconfirmingtoISspecficationallasspecified includingtakingoutthe unserviceable. |
| 29 | All as per item No.16 here-in above but of size 100 mm dia |
| 30 | All as per item No.16 here-in above but of size 150 mm dia |
| 31 | Supply and fix in replacment of Automatic air release valve 25mm dia threaded type including taking down old u/s complete all as specified and as directed. |
| 32 | Hackingout old broken glass (any thickness, size, quality or description)from metal frame including punchingor drilling out old glazing pins / spring clips /removing beads etc, including making good breakages in taking out and providing for fixing of new one all as specified and as directed. |
| 33 | Material and labourforSheetglassofsize5.5mmthick,ordinaryqualityand glazingcompletewith rubbergasketincludingcuttingofPer SM glass in oval shape of size not exceeding 0.5SQM each all as specified and as directed. |
| 34 | Painting fire hydrant pipe line up to 150/100/80mm dia by scrapping old rusted paint and applying one coat of red oxide primer and two coats of synthetic enamel paint of fire red colour including markingfire hydrantflow, all as specified and as directed. |
| 35 | Material and labour cleaning of fire static tanks capacity 100kL & 50 kL at Navjivani Hospitalby draining out the brackish / muddy water and applying bleaching powder in the bottom, side wall byand scrubbing and removing scale dirt and fungus with steel wire brush and one coat of white wash complete including writing date of cleaning with white paint all as directed. |
| 36 | Supply and fix in repair GI fire buckets 04 Nos of thickness 1mm & 9 Ltrs capacity duly filled with cleaned sand and water (02 Nos bucket filled with water & 02 Nos bucket filled with sand) along with suitable fire stand with angle Iron of size 40x40x5 mm and roof should be GI sheet of 1 mm thick& also suitable space for 03 Nos Fire extingushers including complete painting with super enamled paintred coulor and write FIRE on Roof top of stand, all as specified and as directed.Note : Rate of Fire extingushers not included |
| 37 | Material and labour for servicing of diesel engine driven high pressure fire pump of following capacity at fire pump houses at INA Ezhimala by servicing all accessories PT pump injectors, wood ward governor, Self Starter, Radiator, dynamo, engine wiring, terminal contacts and safety controle etc. including replacement of complete OiI, OiI FiIter, Fuel Filter, bypass filter, Air filter,Coolant, Suitable fan belts etc and reassembling the sub assemblies after carrying out neœssary repairs and paint with one coat of enamel paint commissioning and testing as directed. Make : Kirloskar |
| 38 | 108BHP capacity Diesel engine |
| 39 | 38 BHP capacity Diesel engine |
| 40 | 77 BHP capacity Diesel engine |
| 41 | Supply and fix in replacement battery charger type CVCC output 24V, 10A DC suitable for diesel engine pump all as specified and as directed. |
| 42 | Material and labour for hydraulic pressure testing and refilling fire extinguisher including repair/ replacementof worn out parts such as line valve, check nuts, and hose with nozzle wherever required for proper functioning of extinguisher for following type and capacity all as specified and as directed. |
| 43 | DCP stored pressure - 9 kg capacity |
| 44 | CO2 - 4.5Kg capacity |
| 45 | AFFF foam - 9 liters capacity |
| 46 | Material and labour for rewinding of electric motor of following capacity and including following services complete all as specified and directed by the Engr-in-charge.(a) Disconnecting the electrical cable from the terminal box of motor and decoupling the motor from the pump, remove the motor from foundation bed and lifting the motor using chain pulley block and transporting to authorised work shop.(b) Dismantling the motor stator and taking out the burnt copper winding wire /fibre strip/insulating materials.(c) Clean the stator slots by CTC solution and rewind on stator slots with duel coat super enamelled copper wire of existing gauge with insulating materials/fibre strip/varnishing and made terminal connection using 90 mm fibre glass coated wire.(d) Assembling the motor after rewinding.(e) Transporting to the motor to the site re-fixing on foundation channel, coupling the pump and motor with correct alignmentapply grease and connecting electrical connections and testing. |
| 47 | 100HP/74KW |
| 48 | 40HP/30KW |
| 49 | Material and labour for rewinding of 3 Phase, monoblock pumpset of 15 HP capacity including following services(a) Disconnection of electric cable from the terminal box of pump set. remove the pump set from the foundation bed and transport to authorised work shop.(b) Decoupling the motor stator from pump set and taking out the burnt copper winding /fibre strip/insulating materials(c) Clean the stator slots by CTC solution and rewind on stator slots with super enamelled copper wire of existing gauge with insulating materials/fibre strip/varnishing and made terminal connection of fibre glass coated wire.(d) Re-assembling the pump set after stator rewinding and replacement of gland rope (e) Transporting the pump set to the site re-fixing on foundation channel, apply grease and connecting electrical connections and testing |
| 50 | Supply and fix in repair dialtype pressure gauge (4\"Dia)(Firebug)0-16 bar includingtaking down old unserviceable item all as specified and as directed. |
| 51 | Supply and fix in repair Single pressure switch, universal type to suit the system including taking down old unserviceable item all as specified and as directed. |
| 52 | Material and labour for painting of fire yard control cabinet out door type size 0.5 x 0.5 x 0.3 meter with two coats of paintover a coatredoxideprimerbyspraypaintincluding scrapping out old rusted paint and necessary snickering and making all as directed all as specified and as directed. |
| 53 | Supply and replace rubber bush for pump coupling suitable for the following capacity of pumps |
| 54 | 75KW/100HP motor |
| 55 | 15HP/11KW motor |
| 56 | Material and labour for repairs to valve chamber of size upto 1.2x1.2x1.2m by dismantling the broken angle iron & MS plate coverand complete by welding with new hinges, locking arrangements etc. refixing the MS plate on PCC and including necessary brick work , replacement of angle iron of 50x50mm for support and cement plastering, painting steel surfaces with twocoats of synthetic enamel paint of tint and one coat of white wash on cement surfaces, all as specified and as directed. |
| 57 | Supply and fix in replacement of old u/s 3 pole power contactor AC 1 rating 160 Ampsand AC3 rating 140 AmpsAux contacts 2 NO+2NC range from 9A-650 A, 220V coil voltage ,including taking down the existing unserviceable material all as specified and as directed. |
| 58 | Supply and fix in replacementof old u/s 3 pole power contactor, AC 1 rating 100 Ampsand AC3 rating 70 AmpsAux contacts 2 NO+2NCrange from 9A-650 A, 220V coil voltage ,including taking down the existing unserviceable material complete all as specified and as directed. |
| 59 | Supply and fix in replacementof old u/s 3 pole powercontactor,AC 1 rating 45 Ampsand AC3 rating 25 Amps Aux contacts1 NO+2NC range from 9A-25 A, 220V coil voltage ,including taking down the existing unserviceable material complete all as specified and as directed. |
| 60 | Supply and fix in replacement of old u/s electronic star Delta timer, wide operating voltage 160-500V, 50 Hzavailable in time delay range3-30secand 12-120 secs including taking down old material complete all as specified and as directed. |
| 61 | Supply and fix in repair MCCB 4pole36KA of capacity 160A with thermal Adjustable type all as specified and as directed. |
| 62 | Supply and fix in repair MCB 3pole 10KA of capacity 25 to 63A all as specified and as directed. |
| 63 | Supply and fix in repair MCB 2 pole 10KA of capacity 6 to 32A all as specified and as directed. |
| 64 | Material and labour cleaning of fire static tank of capacity 225KL (at Kautilya Fire Pump House) by draining out the brackish / muddy water and applying bleaching powder in the bottom, side wall byand scrubbing and removing scale dirt and fungus with steel wire brush, cleaning two times with fresh water and one coat of white wash complete including writing date of cleaning with white paintall as specified and as directed. |
| 65 | Supply and fix in replacementof Non Return Valve of size 100 mm dia includingtaking down unserivceablecompleteall as specified and as directed. |
| 66 | Supply and fix in repairs Non Return Valve of size 150 mm dia including taking down unserivceablecomplete all as specified and as directed. |
| 67 | Supplyandfix inreplacementofFootValve150mmdiaincludingtakingdownunserivceablecomplete all as specified and as directed. |
| 68 | Supplyandfix inreplaœmentofFootValve100mmdiaincludingtakingdownunseñvceablecompleteall as specified and as directed. |
| 69 | Supply and fixin replacementof old unservisableHose box made of 18 gauge MS Sheet 800mm X 600mm X 250mm with doubledoorwith 4 mm thickglassesand door frame made of 16 gauge MS sheet painted fire red outsideand brilliant white inside yard complete all as specified and as directed. |
| 70 | Painting of Valve chamber by two coats of synthetic enamel paint of existing colour on MS cover, hinges, angles and one coat of white wash on outside and inside chamber including scrapping out old rusted paint complete all as specified and as directed. |
| 71 | Material and labour for rewinding of 3 Phase, Air blower motor 3 HP capacity including following services(a) Disconnection of electric cable from the terminal box of pump set. remove the pump set from the foundation bed and transport to authorised work shop.(b) Decoupling the motor stator from pump set and taking out the burnt copper winding /fibre strip/insulating materials(c) Clean the stator slots by CTC solution and rewind on stator slots with super enamelled copper wire of existing gauge with insulating materials/fibre strip/varnishing and made terminal connection of fibre glass coated wire.(d) Re-assembling the pump set after stator rewinding and replacement of gland rope (e)Transporting the pump set to the site re-fixing on foundation channel, apply grease and connecting electrical connections and testing |
| 72 | Material and labour in repairs of Chimney (up to 30mtr height self supported) and cat ladder,primary chamber,secondry chamber,wet scruber, other pipeline complete cleaning inside surface & out side surface and paiting complete outer surface with Heat resistant Aluminium paint (600* C) including repairing of lightening arrester,Air blower cleaning and painting etc with all connecting materials complete all as specified and as directed.Note : Necessary scaffolding and arrangements shall be included in the quoted rate. |
| 73 | Supply and fix in replacement of LED stack light (Aviation light) incuding all fitting arrangements on top of chimney connected with 3 core control wiring 1.5 Sqmm through panel to top of chimany with connector complete all as specified and as directed. |
| 74 | Material and labour for Demolition of cement concrete (unreinforced) to carryout necessary pipe leakages/valves servicing of any description and in any position not otherwise specifically provided. |
| 75 | Material and labour for Cement concrete in sub floors, sub-bases, floors and pavings of cement concrete of following types:- |
| 76 | Material and labour plain cement concrete Type D2, 1:4:8 (40mm graded agreggate) of 150 mm thickness(For Sub base) |
| 77 | Material and labour plain cement concrete Type B1 1:2:4 (20mm graded agreggate) of50 mm thickness (For Top layer flooring) |
| 78 | Supply and fix in replacement of Sprinkler glass bulb type (Standard response) as per IS:15106/TAC guidelines 68 degree temperature rating pendent type complete all as specified and as directed. |
| 79 | Supply and fix in replacement of Detectors Complying with and type certified to EN - 45Addressable type multisensor detector with heat and smoke combination as per IS: 11360 complete all as specified and as directed. |
| 80 | Supply and fix in replacement of Beam Master detector with Transmitter and receiver complete all as specified and as directed. |
| 81 | Supply and fix in replacement of Addressable control module complete all as specified and as directed. |
| 82 | Supply and fix in replacement of Addressable monitor module including taking down unserviceable complete all as specified and as directed. |
| 83 | Supply and fix in replaœmentAddressablemanual call point resettabletypeincludingtaking down unserviceablecompleteall as specified and as directed. |
| 84 | Supply and fix in replacement Addressable electronic sounder cum strobe including taking down unserviceable complete all as specified and as directed. |
| 85 | Supply and fix in replacementof 12Volt7AHcapacitymaintenance free BatterysuitableforAutomaticFireDelection&Alarm System complete all as specified and directed by Engr-in-Charge. |
| 86 | Supply and fix in repairs 2 core 1.5 sqmm PVC insulated unsheathed armoured FRLS multi stranded copper conductor cable with ISIMarked suitable for communication between fire alarm panel and detectors/call points,etc complete all as specified and as directed. |
| 87 | Material and labour for general servicing of100 HP centrifugal pump set and electric motor (only general servicing) by checking insulation health, removing scales on shaft, replacement of gland bush, unserviceable nut bolts and washers, re-allign with motorand testing all as specified and as directed. |
| 88 | All as per item No. 61 here-in-above but of 40 HP capacity. |
| 89 | All as per item No. 61 here-in-above but of 15 HP capacity. |
| 90 | Supply and fix in replacement of old u/s Rigid non-metallic PVC conduit of dia 25mm exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc.complete all as specified and as directed. |
| 91 | Supply and fix in replacement of FPJ fire fighter telephone jack complete all as specified and as directed. |
| 92 | Supply and fix in replacement of fire fighter emergency telephone portable headset with jack pin and connected 1.5 mtr wire compatible with telephone jack complete all as specified and as directed. |
| 93 | Supply and fix in replacement of display card (Model : DP-DLSP) suitable to fire alarm panel of Notifier make (Model: NFS2-3030)complete all as specified and as directed. |
| 94 | Supply and fix in replacement of processor unit CPU (Model : CPU2-3030D) suitable to fire alarm panel of Notifier make (Model: NFS2-3030) complete all as specified and as directed. |
| 95 | Supply and fix in replacement of loop card module (Model : LCM 320) suitable to fire alarm panel of Notifier make (Model: NFS2-3030) complete all as specified and as directed. |
| 96 | Supply and fix in replacement of loop card extension module (Model : LEM 320) suitable to fire alarm panel of Notifier make (Model: NFS2-3030) all as specified and as directed. |
| 97 | Supply and fix in replacement of power supply unit (Model : AMPS 24E) suitable to fire alarm panel of Notifier make (Model: NFS2-3030) all as specified and as directed. |
| 98 | Supply and fix in replacement of network card (Model : NCM W) suitable to fire alarm panel of Notifier make (Model: NFS2-3030)complete all as specified and as directed. |
| 99 | Material and labour for servicing/cleaning of detectors, MCP, and checking base connections and functionality checking of each module complete all as specified and as directed..Note: a) The unserviceable detectors will be replaced and measured seperately.b) The quoted rate is deemed to be inclusive of arrangement of necessary scaffolding, removal and refixing of ceiling etc. |
| 100 | Material and labour for identify,checking of loop circuit one by one and identify defective loop, modules and devices all as specified and as directed. |
| 101 | Material and labour for function testing of detectors, modules and devices after making sytem serviceability all as specified and as directed. |
| 102 | Material and labour for reprogramming the system after clearance of defedes in loops, modules, detctors and functionality checking all as specified and as directed.Note: The contractor has to submit ladder logic of programming, loop circuit along with final bill |
| 103 | Supply and fix in replacementof PVC insulated PVC round sheathed, flexible copper cable 1100V of size 3 core 16 sqmm including taking down of unserviceableall as specified and as directed. (For terraoe/Jockey pumps) |
| 104 | Supply and lay DI pipes spigot and socket ends centrifugally cast class K9 in any length laid in trenches including taking out the unserviceable CI pipes of 150mm dia. |
| 105 | Note1. The contractor has to rectify all minor repairs on same day/major repairs within 2 days. Otherwise a penalty of Rs. 1500/day delayed will be recovered incase of Engr-In-Charge is not satisafied with delay reasons.2. The contractor has to kept all spares ready for early rectification of complaints.3. The contractor has to submit soft copy of any programmning in CD alongwith final bill. |