| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C(ANCHOR,HAVELLS, ABB) |
| 2 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modularswitch, connections etc. as required.(ANCHOR,HAVELLS, ABB) |
| 3 | 5/6 A switch.(ANCHOR,HAVELLS, ABB) |
| 4 | 3 pin 5/6 A socket outlet.(ANCHOR,HAVELLS, ABB) |
| 5 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.(ANCHOR,HAVELLS, ABB) |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).(ANCHOR,HAVELLS, ABB) |
| 7 | CREB S/F ceilling rose: eachSupplying and fixing 3 pin, 5 amp. ceilling rose on the existing junction box/wooden block including connection etc. as required |
| 8 | BRHOLD S/F brass holder: Supplying and flxing brass batten/angle holder including connection etc. as required. |
| 9 | Supply & fixing C series SP MCB S/F 5 amo 32 amp rating,240/415 Volt C curve,miniature circuit brecker suiteble for inductive load of existing DB complete with connections.Single pole.(HAVELLS, L&T,LEGRAND,ABB,SEIMENS) |
| 10 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, 2 way piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.(ANCHOR,HAVELLS, ABB) |
| 11 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 12 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor complete as required.(For horizontal run) |
| 13 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor complete as required. (For vertical run) |
| 14 | WGPVCSB Circuit/sub-man wiring in PVC conduit:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes ofPVC insulated copper conductor, single core cable in surface/ recessed PVC conduitas required. (2 x 1.5 sq. mm + 1 x |
| 15 | WGPVCSB Circuit/sub-man wiring in PVC conduit:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes ofPVC insulated copper conductor, single core cable in surface/ recessed PVC conduitas required. (2 x 2.5 sq. mm + 1 x |
| 16 | WGPVCSB Circuit/sub-man wiring in PVC conduit:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes ofPVC insulated copper conductor, single core cable in surface/ recessed PVC conduitas required. (2 x 4 sq. mm + 1 x 4 |
| 17 | WGPVCSB Circuit/sub-man wiring in PVC conduit:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes ofPVC insulated copper conductor, single core cable in surface/ recessed PVC conduitas required. (4 x 10 sq. mm + 2 x 6 |
| 18 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (1 x 1.5 sq. mm) (HAVELLS,POLYCAB,FINOLEX,KEI) |
| 19 | Supplying and fixing stepped type electronic fan regulatoron the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 20 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)(8 way (4 + 18), Double door).(HAVELLS, L&T,LEGRAND,ABB,SEIMENS) |
| 21 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)(6 way (4 + 18), Double door).(HAVELLS, L&T,LEGRAND,ABB,SEIMENS) |
| 22 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)4 way (4 + 12), Double door.(HAVELLS, L&T,LEGRAND,ABB,SEIMENS) |
| 23 | Supply & fixing TP MCB isolator : S/F 63 amp rating ,415 V isolator on existing DB complete with connection..(HAVELLS, L&T,LEGRAND,ABB,SEIMENS) |
| 24 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 25 | Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required. |
| 26 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 32 MM |
| 27 | Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 75 to 90 Watt. Confirming to IP 66 and above Protection complete in all respect. CAT- AAA(HAVELLS, ,PHILIPS,OSRAM) |
| 28 | Supply and fixing of LED Tube Light with batten suitable for up to 1 X 22 watt LED tube light fitting including tube on Surface complete in all respect. CAT- AAA(HAVELLS, ,PHILIPS,OSRAM) |
| 29 | Supply & Erracetion of factory fabricated & wired metal clad dust and vermin proof floor mounting, M.S. Channel Base with bottom and top cable entreis Electrical control panel with TPN MCCB\"s (Four Pole 36 KA with thermal magnatic release)Switches Complete and instrument chamber etc.complete in all respects. The instrument chamber shall be separate and shall comprise of flush type digital metering system for phase to phase voltage and single phase voltage, current and otherparameters(KVA,P.F,KW etc) in each phase with ouch type selector switches for different readings, instrument fuses, current transformer etc. The panel board shall have suitable capacity electrolytic alumininum busbars as per IS8623 or above istulated with heat shrink sleeving and mounted on non hygroscopic supports such as CMC/BMC support with deteachable side covers and shall be suitable for extension on the sides. The MCCB\"s shall be complete with suitable cable end boxes, compression glands and indicating lamp on incoming etc. The Job includes the grounting of the board as per directions of Engineer-in charge. All out goings of 100 Amp and above shall have an Ammeter. The panel board shall be fabricated with CRCA sheet with a minimum thickness of 1.6mm/2mm. Cubicle type switch board shall be of cat A & B Only. Incoming:400 Amp. MCCB-1 Nos. Outgoing: 100 Amp. MCCB-3 No, & 63 Amp. MCCB-2 No Cat. B. Pannel Cubicle Type ( HAVELLS, L&T,LEGRAND,ABB,SEIMENS) |
| 30 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cable 1100 volt grade at a depth of 750 mm below ground lavel over a cushion of 75 mm thick sand alround and protected with brunt bricks on sides and on top .Complete in all respect (70 sq. mm 3-1/2 core) .(HAVELLS,POLYCAB,FINOLEX,KEI) |
| 31 | Supply and fixing of 36 Watt to 46 Watt indoor Recess mounting LED Square Fitting for Armstrong Ceiling having Powder coated die cast aluminium housing body with extended heat sink and diffuser of Special Polycarbonate meterial and driver set complete in all respect.CAT-AAA(HAVELLS, ,PHILIPS,OSRAM) |
| 32 | Supply and burring of Safe Earthing Electrode T-39 (Hot-Dip Galvanized), Length up to 3000mm, outer pipe 76mm inner Dia 38mm terminal Dia 12 mm ,outer GI pipe of 16 SWG and inner GI pipe of 12 SWG with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonary housing. (From electrode terminal to switch board, cost of 25 X 3 GI. Strip will be extra) Make: As approved in U.P. P.W.D., & C.P.R.I. Certified. |
| 33 | Supply and laying of 25mm x 3mm G.I. strip from earth electrode directly in the ground as required complete in all respect. |
| 34 | S&F of 400 Amp. four pole change over switch on 50mm x 50mm x 6mm angle iron frame, including the cost of labour, T&P, painting and other material required for proper completion of the work as per direction and satisfaction of Engineer in charge.(HAVELLS, L&T,LEGRAND,ABB,SEIMENS) |
| 35 | Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thik) having 3mm thikness with single arm bracket (1 Mtr length) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and Required T&P completee in all respect. |
| 36 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.(16 sq. mm 4 core) (HAVELLS,POLYCAB,FINOLEX,KEI) |
| 37 | Supply and fixing of C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 38 | S/F Exhaust Fan 300 mm (HAVELLS, USHA,POLYCAB,ORIENT) MAKE . |
| 39 | S/F GEYSER 50 Liter , (HAVELLS, USHA,POLYCAB,ORIENT) MAKE. |
| 40 | S/F Ceiling Fan 1200mm , (HAVELLS, USHA,POLYCAB,ORIENT) MAKE. |
| 41 | S/F WALL Fan 400mm Sweep , (HAVELLS, USHA,POLYCAB,ORIENT) MAKE. Please Enable Macros to View BoQ information |