Inhibited Mineral Insulating Transformer Oil as per IEC: 60296 Type A or latest and Railways required as per RDSO letter NO.TI/PSI/INSOIL/POLICY/07 DT.27.02.2007 & letter NO.TI/PSI/INSOIL/POLICY/08 DT.06.02.2008 and letter NO.TI/PSI/TRNPWR/POLICY/16/01 dated 28.10.2016 and TI/PSI/INSOIL/POLICY/19 dated 26.07.2019. With following characteristic requirements. 1. Lowest Cold Start energizing Temperature: 0 Degree B0C (Zero Degree Celsius) 2. Flash Point: mini. 140 Degree Celsius 3.Presence of Oxidation inhibitor (DBPC-2, di tertiary butyl para cresol) content range: 0.25%-0.30% 4. Oxidation Stability (a) Total acidity (Neutralization Value after oxidation): (max) 0.2mg KOH/g (b) Total sludge after oxidation: (max) 0.05%. Note: RDSOs additional requirements to be tested in anyone NABL accredited Laboratories and copy of report to be furnished to consignee by TPI along with their inspectionreport. [ Warranty Period: 30 Months after the date of delivery ][Quantity Tolerance (+/-): 5 %age , Item Category : Normal , Total PO value variation Permitted: Max 8 lacs ] ]