| 1 | Sch \"A\" Part-I (BUILDING WORK), To be quoted by contractor |
| 2 | Design & survey, fabricate, supply, errect, construction and execution of 04 Md Officers Accn (Maj to Brig) with servent quarter,based on given tentative line plan (G+1) complete all as specified and as directed. |
| 3 | Design & survey, fabricate, supply, errect, construction and execution of 02 Md Officers Accn (Maj to Brig) with servent quarter,based on given tentative line plan (G+1) complete all as specified and as directed. |
| 4 | Design, fabricate, supply, errect, construction and execution of Garrage for 4 car parking, based on given tentative line plan complete all as specified and as directed. |
| 5 | Note for Srl 1.01 to 1.03 :-Design and drawings of foundation, sub-structure and super structure to be submitted by the contractor duly vetted by IITs & approved authorised Govt. agencies and also shall be got approved by department before commencement of work. |
| 6 | Total amount of sch \"A\" Part - II (SITE CLEARANCE AND DEVELOPMENT WORK) |
| 7 | Total amount of sch \"A\" Part - III (PROTECTIVE WORK) |
| 8 | Total amount of sch \"A\" Part - IV (PATH WAYS) |
| 9 | Total amount of sch \"A\" Part - VA (SEWAGE DISPOSAL) |
| 10 | Sch \"A\" Part-VB (SEWAGE DISPOSAL) |
| 11 | M&L DWCPE pipe (SN8) (ID) pipe 163 mm internal dia and 180 mm outer diawith coupler, ring and bends as required , laid in trenches and jointed complete as per IS 16098-2 (2013) including testing complete all as specified and directed. |
| 12 | M&L CI Sluice Valve 75mm dia PN16 with flanged endincluding testing complete all as specified and directed. |
| 13 | M&L CI Sluice Valve 100mm dia PN16 with flanged endincluding testing complete all as specified and directed. |
| 14 | Total amount of sch \"A\" Part - VI (AREA DRAINAGE) |
| 15 | Total amount of sch \"A\" Part - VII A (DEMOLISHION OF BUILDING) |
| 16 | Sch \"A\" Part-VII B (DEMOLISHION OF BUILDING) |
| 17 | Dismantling of Old Unserviceable DBs any make and capacity complete all as specified and as directed. |
| 18 | Dismantling of Old Unserviceable MCBs any make and capacity complete all as specified and as directed. |
| 19 | Taking down old Unserviceable sub main wiring of any size/type including all accessories any type and size complete all as specified and as directed. |
| 20 | Dismantling of existing UG cable of any size/type all as specified and directed complete all as specified and as directed. |
| 21 | Dismantaling of old unserviceable existing steel water tubing of any grade of size 100mm dia including all fittings complete all as specified and as directed. |
| 22 | Total amount of sch \"A\" Part - VIII A (EXTERNAL ELECTRIC SUPPLY) |
| 23 | Sch \"A\" Part-VIII B (EXTERNAL ELECTRIC SUPPLY) |
| 24 | Design, Supply installation, testing and commissioning of Outdoor type Feeder Piller Box (CPRI approved), totally enclosed fabricated out of 50 x 50 x 6 mm angle iron and 3.15 mm thick CRCA sheet with hinged door, dust & vermin proof of size not less than 1.5 x 1.0 x 0.6 mm with 3 phase 4 wire copper bus bar 300 amps for phases and half for neutral rating with the following accessories: - (a) Incoming MCCB 4 pole 200 amp 415 volts grade repturing capacity (25 KA)- 01 Nos (b)Outgoing MCCB 4 pole 100 Amp 415 volts grade repturing capacity (25 KA) - 02Nos (b)Outgoing MCCB 4 pole 63 amp 415 volts grade repturing capacity (25 KA) - 02 Nos (d) Digital ammeter 3.5 digit with 3 Nos CTs of ratio 200/5 amps - 01 Nos (e) Digital voltmeter 31/2 digit - 01 Nos (f) Indicator lamps RYB (Set of 3) - 01 Set |
| 25 | M & L for supply, transporting, erecting truly in vertical position and fixing of steel tubular pole swaged, over all length 9 metres, type 410 – SP – 31 complete with mild steel base plate, pole cap, finial taper plug, MS bolts, nuts & washers, necessary excavation & earthworkin hard / dense soil, PCC sub base block as mass concrete of size 600 X 600 X 150 mm in cement concrete 1:4:8 Type D-2 in base of foundation, PCC foundation block of size 600 X 600 X 1500 mm in cement concrete 1:3:6 Type C-2, pole plinth of size 600 X 600 X 300 mm in cement concrete 1:2:4 Type B-1 including necessary form work as required at site and painting of pole with two coats of anti corrosive black bituminous paint through out internally and externally upto planting depth (embedded in concrete) and remaining portion of the pole painted two coats of aluminium paint over a coat of red oxide primer on complete exposed surface including painting of 05 Nos. bands / strips of 30 cm wide each with two coats of synthetic enamel paint (black & yellow) at a distance of 30 cm from plinth block upto 1500 mm height and marking / sign writing of pole number and feeders locations of pole with thick synthetic enamel paint (white) complete all as specified and directed. |
| 26 | Total amount of sch \"A\" Part - IX (EXTERNAL WATER SUPPLY) |
| 27 | Total amount of sch \"A\" Part - X (INTERNAL WATER SUPPLY) |
| 28 | Total amount of sch \"A\" Part - XI A (INTERNAL ELECTRIC SUPPLY) |
| 29 | Sch \"A\" Part - XI B (INTERNAL ELECTRIC SUPPLY) |
| 30 | Supply and fixing Geyser 25 Ltr Capacity, BEE five star rating with Digital Temperature Display & heating element upto 2 KW, ISI mark, with all accessories such as safety valve, thermostate, NRV, connection piece etc, and making good as per existing surface Complete all as specified and directed. |
| 31 | Supply and fix High quality LED T8 indoor batten tube light 20 Watt with aluminium extrusion in D shaped have large diameter for increased convection heat transferincluding one LED PC tube rod and driver,internaly pre wired of 1.5 sqmm twin twisted flexible cableall as specified & directed.NOTE: The contractor must submit 5 years warranty for LED light fitiings. |
| 32 | S&F LED luminaire wall bracket type, made in fully cast aluminium body finished with polyurethane paint with nipple having B22 holder including 05/6 watt LED bulb complete all as specified and directed. NOTE: The contractor must submit 5 years warranty for LED fitiings. |
| 33 | S&F bed side LED light fitting , 6 watt, with independent switch and G-22 holder and LED lamp complete all as specified and directed. |
| 34 | S& F socket outlet for TV/Video/audio device modular type with inner and outer modular plate type, specially built for wall/high mounted TV and inc pressed steel/metal flush box concealed complete all as specified and directed. |
| 35 | S&F sheet metal enclusure for DBs (double door type) VTPN (Triplepole and neutral) 12way including blacking platge as required with 200 Amps rated bus bar, 415 volts fixed complete all as specified and directed . |
| 36 | S& F LED Bulb of 9 watt completeas specified .NOTE: The contractor must submit 5 years warranty for LED bulb. |
| 37 | S& F socket outlet for Telephone (RJ11) modular type with inner and outer modular plate type for communication (telephone)including pressed steel/metal flush box concealed complete all as directed. |
| 38 | Supply,fix, testing and commissioning of commercial type auto clean filterless electric chimney with inverter technology, BLDC motor 90cm 1400cm^3/h made out of stainless steel including exhaust duct of required size and length, suitable for all kind of cooking stove/furnace or any other cooking appliances used in daily cooking. The chimney should be efficient and silent working and must be mounted as per site requirement i.e. ceiling (centre) mount orwall mount and must be capable of removing and absorbing all kind of smoke,fumes,steam,odor and oil from the cook house. Make :- Glen (CH 6074 AC)/ equivalent in Elite/ Faber/ Hindware/ BoshNote:- The quoted shall include all kind of addition/alteration civil work including plastering, PCC and brick work required to install the chimney at the site. |
| 39 | Total amount of sch \"A\" Part - XII (RAIN WATER HARVESTING) |
| 40 | Total amount of sch \"A\" Part - XIII (FENCING AND GATE) |