| 1 | Schedule \"A\" Section-I (Building Works) is not prepriced by MES and prepriced rates indicates 0.00 under column 6 signified this fact only |
| 2 | Construction of MI Room, single storey with RCC framed structure with permanent specifications complete all as specified & shown on drawings. |
| 3 | Construction of Garage for ambulance, single storey with RCC framed structure and with permanent specifications complete all as specified & shown on drawings. |
| 4 | Construction of scooter cum car parking shed, single storey with RCC framed structure and with permanent specifications complete all as specified & shown on drawings. |
| 5 | Schedule \"A\" Section-II to Section-XI (BOQ Item No 2.01 to 2.11 here-in-after). These schedules are Prepriced by MES and Prepriced rates indicated under column-6. Bidders to quote their rates under column-7 only . |
| 6 | Schedule \"A\" Section-II (Excavation & EarthWorks) |
| 7 | Schedule \"A\" Section-III (Internal Water Supply Works) |
| 8 | Schedule \"A\" Section-IV (Internal Electric Supply Works) |
| 9 | Schedule \"A\"Section-V (Road, Path & Hardstanding Works) |
| 10 | Schedule \"A\"Section-VI (Area Drainage Works) |
| 11 | Schedule \"A\" Section-VII (Sewage Disposal Works) |
| 12 | Schedule \"A\" Section-VIII (Hot Water Supply Works) |
| 13 | Schedule \"A\" Section-IX (External Water Supply Works) |
| 14 | Schedule \"A\" Section-X (External Electric Supply Works) |
| 15 | Schedule \"A\" Section-XI (Refregeration and AIR Conditioning Works) |
| 16 | Schedule \"A\" Section-XII (Miscellenous Item of Works) (Item No 3.01 to 3.09 here-in-after) (to be quoted by bidders). Bidders to quote their rates under Column-7 only . |
| 17 | S&F security light bracket with32/40 mm bore GI tubing, light grade, cut and bent to shape required 1.5 metre long fixed with including bends, flat iron clamp made of FI 40x6mm, nuts, bolts, washers etc duly painted with two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified & directed. |
| 18 | Supply instalation and testing, single phase motor, AC,32 A, 240 Volts, 50 Hz complete all as specified and directed |
| 19 | Supplying and laying 75mm thick, precast SFRC drain cover without frame but including sides iron sheets (medium) complying to the standard specifications as per IS : 12592 BIS standard minimum load bearing capacity 5 ton per sqm in square or in rectangular in shape complete all as specified and directed. |
| 20 | M&L boring of holes under road, pavement, taxi track, hardstanding for passing/crossing pipes/cables upto 100mm dia/bore at suitable depth (not below than 600mm) bytrenchless technology using ultra sounding technique and using necessary machinery / equipments complete without damaging the surface and removing excavated soil /material to a distance not exceeding 50mtr complete all as specified & directed. |
| 21 | M&L construction of masonry pits of size 45cm x 45cm x 45cm (internal size) for valves with sub Class \"B\" bricks straight or curved or plan exceeding 6 mtr mean radius built in cement mortor 1:6, PCC 1:3:6 in foundaiton, 15mm thick plaster in cement mortor 1:4 on internal faces of walls, 40mm thick PCC 1:2:4 in floors including valve pit cover made out of MS sheet 2mm thick with angle iron 40mm x 40mm x 6mm frame with fixing hinges, locking arrangement hold fas and handle etc. duly painted with two coats of synthetic enamel paint over & including one coat of red oxide primer including necessary excavation & earth work in soft/ loose soil etc. including breaking of existing broken/damaged valve pit complete all as specified & directed. |
| 22 | Supply, installation, testing and commissioning of LT Panel board out door type made out of 3.15 mm CRCA Sheet CPRI tested cubical type totally enclosed wheather dust and vermin proof with front and rear opening of 400 Volts 3 phase 4 wire 50 Hz having 4 pole aluminium bus bar capacity 100 Amps insulated with heat shrinkable sleeves RYB and supported on SMC/DMC insulator including internal wiring with FRLS copper wire powder coated including connecting all in coming and out going cable feeders with necessary lugs ferrules etc. The panel should have angle iron support of size 50x50x6 mm with 4 legs of 750 mm long (300 mm grouted in PCC and 450 mm above GL) on the base all around including PCC foundation support, well finishing with cement mortar. Comprising of the following switchgear and accessories are as under :-(a) Mains Incoming :(i) MCCB 63 Amps 4 Pole 16 KA - 01 No(b) Outgoing :(i) MCCB 25 Amps 4 pole 16 KA-04 Nos (ii) Digital type Multifunctional meter to measure Amp, Voltage-01 No(iii) LED Indicating lamp wikth in built selector switch-01 set of three(iv) CT 100/5A with MCB SP 10 KA-03 Nos(v) MCB SPN 6 Amp 10 KA - 2 Nos |
| 23 | Note for item No 3.06:All MCCB shall be with adjustable Thermal magnetic setting (TMD) (ii) The board shall be epoxy polyster powder coated with structure siemens gray shade RAL-7035 (iii) Sheet metal works shall be processed with nine tank process i.e. degreasing, water rinsing, activation, derusting, water rinsing, phosphating, water rinsing, passivation and water drying. (iv) Busbar shall be of electrolytic grade aluminium and shall be insulated with Red, Yellow, Blue and black colour heat shrinkable PVC sleeves (v) Earth bus shall run throughout the length of the panel at the bottom of the panel. (vi) Each feeder shall be provided with individual inscription plate made out of black anodized AI/polycarbonate sheet with engraved/painted letters. (vii) Power switches/MCCB\"s will be provided iwth door operating mechanism, door interlock and padlocking feature. (viii) Danger notice board with conventional skull & bone sign in postman red to be provided on front & rare side (ix) All incoming & outgoing feeder shall be provided with cable glands at entry & exit of cable (x) all MCCB\"s to be provided with rotary operating handle. |
| 24 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of + 2.5% and of capcity 4 KVA complete all as specified and directed. |
| 25 | Supply and fix steel body desert coller electric driven single phase having 18\" exhaust fan motor with nominal air flow capacity of 4000 CuM per hour including submersible water pump heavy duty with wate storage capacity upto 140 ltrs with wood wool pads 03 sides over flow pipe drain pipe water filling point with automatic float valve cooler body made of powder coated metal sheet suitable thickness approved by Engr-in-Charge complete all as specified and directed. |
| 26 | Supply and fix refrigerator, electric driven (single phase), suitable to working on AC 220 Volts, 50 Hz, CFC free refrigerant gas, double door type with minimum 2 star rating with ISEER as perlatest ministery of power notification of capacity more than or equal to 240 litre complete all as specified and as directed |