| 1 | Taking down cement plaster on brick or stone walls etc including racking out joints, hacking for key, scrubbing down with water etc. completeall as specified and directed. |
| 2 | Demolition of brick work or stone/boulders masonary, built in cement mortor including all quoins, arches pillars, etc but excluding ashlar facing dressed stone work and precast concrete articles complete all as specified and directed. |
| 3 | Dismantling AC sheet (Corrugated, Semi corrugated etc) as in roofs etc including ridges complete all as specified and directed by Engineer-in-charge. |
| 4 | Dismantling timber scantlings 40 sq. cm and over in section in framed work, in any position complete all as specified and directed. |
| 5 | Demolition of cement concrete (unreinforced) in ground floors and pavings not exceeding 15 cm thick above or below ground level complete all as specified and directed. |
| 6 | Dismaintling of wall and ceiling boards (fibre, pulp, insulation, etc.) or insulation boards / slabs/ blankets, any thickness, including cover fillets including cover fillets complete all as directed by Engineer-in-Charge. |
| 7 | M&L for Brick work with sub class ‘B’ old size burnt bricks, straight or curved on plan exc 6m mean radius built in cement mortar (1:6) complete all as specified and directed by Engineer-in-charge. |
| 8 | All as per Srl item No 7.00 here-in-before but except brick.Note : Old serviceable brick retrieved from serial item No 2.00 of BOQ here-in-before shall be used under this item. |
| 9 | M&L for rendering 15 mm thick in CM 1:4 including water proofing compound on fair face of brick or concrete surface, finished even and fair without using extra cement complete all as specified and directed.Note:- WPC shall be measured and paid saperately. |
| 10 | M&L for rendering 10mm thick onfair faces of brick work or concrete surfaces in cement mortar (1:6) finished even and smooth without using extra cement complete all as specified and directed. |
| 11 | Supply only liquid water proofing compound ISI marked complete all as specified and directed by Engineer-in-charge |
| 12 | M&L for preparing newly plastered surfaces and applying applying two coats of distemper with distemper oil emulsion white or tinted over one coat of primer complete all as specified and directed. |
| 13 | M&L for preparartion of new plastered surfaces of walls and applying two coats cement base paint on walls completeall as specified and directed. |
| 14 | M&L for preparation of old distempered surfaces of walls by washing, rubbing down and stopping of distempered and painted surfaces and treating oil and greasy spots and applying one coat of oil bound distemper oil emulsion white or tinted completeall as specified and directed. |
| 15 | M&L for preparation of old decorated, plastered or pointed surfaces of wall by brooming down or steel wire brushing, scrapping down smoke soot moulds, moss and efflorescent, salts and treating oil & greasy spots etc and applying one coat of white wash complete all as specified & directed by Engineer-in-Charge. |
| 16 | M&L for preparation of old plaster surfaces of walls and applying one coat of cement based paint on walls complete all as specified and directed. |
| 17 | M&L for complete removal and preparation of old painted surfaces of wall and applying two coat of exterior emulsion paint dark shed complete all as specified and directed. |
| 18 | M & L for Pre-painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering /cladding to wall, fixed with self tapping screws complete all as specified and directed by Engineer-in-charge. |
| 19 | S&F Pre-painted galvalume aluminium zinc coating GI based plain steel ridges suitable for corrugated steel sheet 0.5mm thick of red colour having tensile strength of 550 Mpa as in roof covering / cladding to wall, fixed with self tapping screwscomplete all as specified and directed. |
| 20 | S&F 2nd class hard wood plain solid in truss, purlin, straight chowkhat and frames wrought, frame rebated on the solid, rounded or chamferred put together with glue pinned at joints etc complete all as specified and directed. |
| 21 | Fixing only2nd class hard wood plain solid in truss, purlin, straight chowkhat and frames wrought, frame rebated on the solid, rounded or chamferred put together with glue pinned at joints etc complete all as specified and directed.Note : Old serviceable 2nd class hardwood retrieved from serial item No 4.00 of BOQ here-in-before shall be used under this item. |
| 22 | M&L for GI frame work for seamless ceiling comprising of GI perimeter channel 0.55 mm thick with two unequal flanges of 20 and 30 mm and web of 27 mm fixed to surrounding wall using nylone sleeves and screws at 450mm centre to centre / intermediate channel 0.9 mm thick having two equal flanges of 15mm each and web of 45 mm suspended from soffit at approx 900mm centre to centre with GI cleat and steel expansion fasterners with and including ceiling section ( not exc 1.2m length) of 0.55 mm thickness having kurled web of 50mm and flange of 26mm each with lips of 10.5mm fixed to the intermediate channel with connecting clips across the intermediate channel at 457mm centre to centre, size of grid 605mm x 605mm and fixing 4mm thick decorative gypsum ceiling board complete all as specified and directed. |
| 23 | All as per Srl item No 22.00 here-in-before but except board.Note : Old serviceable board retrieved from serial item No 6.00 of BOQ here-in-before shall be used under this item. |
| 24 | M&L for cement concrete 1:2:4, type B-1 (using 20mm graded stone aggregate) as in lintels upto 1.5 metre clear span, cills, steps, siesmic and other similar bands, plinth courses, string courses, lacing courses, coping, parapets and railing upto 60cm height, copings bed block,roof kerbs or mud stops, kerb stone, kneelers, apex stones, bed plates, surface channels and drains, benching, water troughs and the like including weathering, slightly rounded or chamfered angles and throatings etc. including necessary form work complete all as specified and directed by Engineer-in-Charge. |
| 25 | Taking down surface / concealed copper / aluminium point wiring (light, bell, fan, socket or power) complete, including fixtures and fittings such as switches, ceiling roses, lamp holders, pendants, sockets, regulators, tubelight fittings etc and making good disturbed surfaces with plaster on walls, floors etc complete all as specified and directed. |
| 26 | M&L for Point wiring complete with 1.5 sqmm single core FRLSH PVC insulatedcable with multi stranded copper condutor in and including PVC conduit 20mm dia and thickness not less than 1.5mm, ISI marked with all accessories for surface or concealed conduit as directed at site incl chase cutting for one light/fan point controlled by one one way switch including MS sheet sunken box concealed on wall duly painted inside and outside with one coat of red oxide primer and two coats of black bituminous paint with modular sheet cover for fixing switches, sockets, regulators etc. alongwith 1.5 sqmm multi stranded FRLSH, PVC insulaedcopper cable as continuous earth connected to common earth and earth dolly including making good the disturbed surfaces complete all as specified and as directed. |
| 27 | All as per Sl item No 26.00 above herein before but for one bell point controlled by one bell push. |
| 28 | All as per item No 26.00 (here-in-before) but for one socket outlet 5 pin, 5amps on the independent board complete all as specified and directed. |
| 29 | All as per serial item No. 26.00 here-in-before but for One 5 pin 5 Amp socket outlet on the same board with other switches. |
| 30 | M&L for point wiring with 2.5 sqmm PVC insulated, unsheathed FRLSH multistrand copper conductor cable 1100 volts grade drawn into and including rigid non metallic PVC conduit medium grade not less than 20 mm dia ISI marked ivory colour with all and including conduit fittings and fixing accessories 1.2mm thick sunken anodised pressed steel terminal boxes with 3.0 mm thick hylam sheet cover for mounting switches, socket etc including 2.5 Sqmm FRLSH multistrand copper conductor cable as continuous earth wire complete for one socket 16 Amp socket outlet controlled by one switch on independent board.complete all as specified and directed. |
| 31 | S & F modular type6A one way SP switch 1 moduleconfirming to IS: 3854-1997 with finger proof terminal complete all as specified and directed. |
| 32 | S & F modular bell push, 6 Amp 240 volt one module complete all as specified and directed. |
| 33 | S & F Bell ding dong type, AC 230 volts all as specified and directed. |
| 34 | S & F modular type 2/3 pin 6 Amps socket 2 module conforming to IS: 1293-2005 complete all as specified and directed. |
| 35 | S & F modular type16 A one way SP switch 1 module confirming to IS: 3854-1997 with fingure proof terminal complete all as specified and directed. |
| 36 | S & F modular type 2/3 pin 16 Amps socket 2 module conforming toIS: 1293-2005 complete all as specified and directed. |
| 37 | S & F modular type 3/5 pin socket with one single pole MCB 20 Amps 230 volts complete all as specified including concealing in wall suitable for AC and domestic appliances complete all as specified and directed. |
| 38 | S & F modular type 120W step fan regulator of 2 module size conformng to IS: 11037-1984 complete all as specified and directed. |
| 39 | S&F Angle / batten holder polycorbonate type body suitable for batten fitting complete all as specified and directed. |
| 40 | S&F LED bulb base B22 of capacity 10 watts not less than 700 lumens output at 6500K colour temp, complete all as specified and directed. |
| 41 | S&F ceiling rose 63x30 mm three terminal, polycorbonate body complete all as specified and directed. |
| 42 | Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete. |
| 43 | S&F in replacement LED (1.2m) smartbrite extra batten made of CRCA sheet housing provided for efficient heat dissipation with a PC glossy diffuser duly prewired connection having a normal system lumenoutput of 2000 lumen/20 watt at a minimum system efficacy of 2000 lumen per 20 watt and total power consumption not more than 20 watt including driver of capacity 10 KA. It has a rated system life time of 25000 burning hours at L70 and should have acolour temperature of 6500 K, CRI>80, THD<10\"%\" AND PF>0.95 complete all as specified and directed. |
| 44 | S&F in replacement LED (0.6m) smartbrite extra batten made of CRCA sheet housing provided for efficient heat dissipation with a PC glossy diffuser duly prewired connection having a normal system lumenoutput of 1150 lumen/10 watt at a minimum system efficacy of 1150 lumen per 10 watt and total power consumption not more than 10 watt including driver of capacity 5 KA. It has a rated system life time of 25000 burning hours at L70 and should have acolour temperature of 6500 K, CRI>80, THD<10\"%\" AND PF>0.95 complete all as specified and directed. |
| 45 | S&F Security Light of 35 watts of new generation energy saving & environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having IP65 protection and impact resistance of IK07 with 10KV Built -in-Surge Protection Devision,should have a colour temperature of 6500 K, CRI>80, THD<10% AND PF>0.95 including suitable pipe, clamps, nut and bolts for mounting the light all as specified and directed. |
| 46 | S&F in repair 10W integrated LED bulk head luminaire environment friendly, ultra modern, energy saving, surface mounted decorative oval bulk head with LED light, complete all as specified and directed. |
| 47 | M & L concealed sub main wiring with 2 runs of 4 sqmm main wire along with 1 run of 4 sqmm earth wire (green in colour) single core FRLSH PVC insulated, unsheathed, multi-stranded, 1100 volts grade ISI marked copper conductor cable, drawn through and including adequate size rigid non-metallic PVC conduit (medium grade) with all fittings & accessories including cutting chases for conduits as required, sinking for terminal boxes, making good the same including taking down old unserviceable cable complete all as specified by Engr- in- Charge.NOTE:- Two runs of main copper conductor, one run of earth wire and one run of PVC conduit shall be measured as one unit length. |
| 48 | M & L concealed sub main wiring with 2 runs of 6 sqmm main wire along with 1 run of 6 sqmm earth wire (green in colour) single core FRLSH PVC insulated, unsheathed, multi-stranded, 1100 volts grade ISI marked copper conductor cable, drawn through and including adequate size rigid non-metallic PVC conduit (medium grade) with all fittings & accessories including cutting chases for conduits as required, sinking for terminal boxes, making good the same including taking down old unserviceable cable complete all as specified by Engr- in- Charge.NOTE:- Two runs of main copper conductor, one run of earth wire and one run of PVC conduit shall be measured as one unit length. |
| 49 | M & L concealed sub main wiring with 2 runs of 10 sqmm main wire along with 1 run of 10 sqmm earth wire (green in colour) single core FRLSH PVC insulated, unsheathed, multi-stranded, 1100 volts grade ISI marked copper conductor cable, drawn through and including adequate size rigid non-metallic PVC conduit (medium grade) with all fittings & accessories including cutting chases for conduits as required, sinking for terminal boxes, making good the same including taking down old unserviceable cable complete all as specified by Engr- in- Charge.NOTE:- Two runs of main copper conductor, one run of earth wire and one run of PVC conduit shall be measured as one unit length. |
| 50 | Supply & fixing in replacement sheet metal enclosure MCB distribution board Single Pole & Neutral 240 volts 4 way with 200 Amp rated bus bar double door with isolated Neutral bar & shrounded bus bar IP-42having door earthing complete all as specified and directed. |
| 51 | Supply & fixing in replacement sheet metal enclosure MCB distribution board Single Pole & Neutral 240 volts 8 way with 200 Amp rated bus bar double door with isolated Neutral bar & shrounded bus bar IP-42having door earthing complete all as specified and directed. |
| 52 | Supply & fixing in replacement of MCB Single Pole Neutral 240 volt any rating from 32 to 63 amps, C series with rupturing capacity 10 KA complete all as specified and directed. |
| 53 | Supply & fixing in replacement of MCB single pole 240 volt any rating from 6 to 32 amps, C series with rupturing capacity 10 KA complete all as specified and directed. |
| 54 | M&L for earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick burried directly in ground not less than 2.25 mtrs deep below normal ground level with top edge of the plate not less than 1.5 mtrs below normal ground level, surrounded from all sides with mixture of charcoal and common salt, connected to galvanized earth lead wire 4.00 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel protected by galvanised iron light grade 15 mm dia pipe and GI pipe 20mm light grade for water filling including 15x20mm reducer socket funnel wire mesh, RCC cover with concrete 1:2:4 using 8 mm# bar@100 mm c/c both ways ,PCC chamber pit with PCC (1:3:6) type C-2 and excavation and earth work,disposal of suplus spoil to a dstance not exceeding 50mtrs all as specified and shown on electrical plate No. 3 of 2009 (Part-I) complete including taking down old unserviceable earthing all as specified and directed. Note :- The unit rate includes for protection pipe and GI wire 4mm dia from top of earth plate up to 7.5 meter above ground level. |
| 55 | M&L for taking down AC indoor & outdoor unit complete disconnecting electric and gas connection without damaging and keeping in safe custody and refixing the same complete all as specified and directed. |
| 56 | M&L for taking down ceiling fan complete with down rod and taking to workshop for rewinding with copper super enamelled wire and painting as original and refixing the same complete all as specified and directed. |
| 57 | Excavation in trenches in soft/loose soil not exc. 1.5 M wide and not exc. 1.5 M deep and getting out including forming bottom to required level or slope for laying of cable, pipe and concrete bed or for manhole etc not exc.10 Sqm on plan all as specified and directed by Engineer-in-Charge. |
| 58 | Returning, filling in soft/loose soil including spreading, leveling and watering well ramming in layers n.exc. 25cm all specified and directed. |
| 59 | Removing excavated materials not exc 50 mtr and deposited where directed at a level not exc. 1.5 mtr above the starting point complete all as specified and as directed. |
| 60 | M&L for sand cushioning and covering clean and dry sand to underground electric cable in trenches / floor complete all as specified and directed.Note :- Punned thickness shall be measured and paid for. |
| 61 | M&L for sub class \"B\" brick laid dry, flat with width equal to length of brick as cover laid over the cabel to give mechanical protection to underground cabels complete all as specified and directed. |
| 62 | Supply, laying, testing and commissioning cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, elecric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 sqmm 2 core including taking out old unserviceable cable complete all as specified and directed. |
| 63 | Supplying, laying, jointing, commissioning and testing XLPEinsulated screened PVC bedded, armoured,heavy duty underground electric cable with stranded aluminium conductor 1100 volts grade of cross sectional area 25 sq mm 3.5 core confirming to IS-7098 (Part-I-1988) laid in trenches, along poles through pipes etc including taking down old unserviceable cable complete all as specified and directed by Engineer-in-charge.Notes :- (i)Excavation, earth work, sand cushioning, cable protection and GI pipe shall be measured & paid for separately under respective items of BOQ(ii) Road cutting / floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall deemed to be inclusive of the above provisions. |
| 64 | S&F Galvanized iron tubing, 50mm bore light grade, ISImarked, including all fittings and laid in trenches / under road / drains, fixed to poles / walls with required numbers of clamps made out of 25x3mm flat iron, bolts, nuts and washers for protection of LT electric cable complete including taking down old unserviceable tubing all as specified and as directed by Engineer-in-charge.Notes :- (i) Excavation & earthwork shall be measured & paid for separately under respective items of BOQ(ii) Cost of flat iron clamp if required is included in the unit rate of this item. Nothing extra shall be paid on this account. |
| 65 | M&L for drilling hole under road for laying of underground cable through pipe of suitable size complete all as specified and directed. |