| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bellpoint with 1.5 sq.mm FRLS PVC insulated copper conductorsingle core cable in surface / recessed medium class PVCconduit, with piano type switch, phenolic laminated sheet,suitable size M.S. box and earthing the point with 1.5 sq.mm.FRLS PVC insulated copper conductor single core cable etc. asrequired.a)Group C |
| 2 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 3 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.a)2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 4 | b)4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 5 | Supplying and fixing metal box of 150mm X 75mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 A socket outlet and 5/6 A piano type switch, connections, painting etc. as required |
| 6 | Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 A socket outlet and 15/16 A piano type switch, connections, painting etc. as required. |
| 7 | Supplying, Installation, Testing and Commissioning of 5 Star Rating AC Ceiling Fan, 1200 mm Sweep ISI Marked without regulator with all accessories as equivalent to Crompton, Model No. HS DURA or its equivalent etc., as required. |
| 8 | Supplying and fixingtwo module stepped type electronic fanregulator on the existing modular plate switch box includingconnections but excluding modular plate etc. as required. |
| 9 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 10 | Supplying and fixing call bell/ buzzer suitable for single phase,230 V, complete as required. |
| 11 | Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 12 | Installation of exhaust fan in the existing opening, includingmaking good the damage, connection, testing, commissioningetc. as required. a)Upto 450 mm sweep |
| 13 | Supplying of Metallic Exhaust Fan300 mm sweepwith accessories etc as equivalent to Havells Model No. Venti Air DS Green Code - FHVVEMTDSSB09 or its equivalent as required |
| 14 | Supplying of LED 9W Bulb in the existing Batten Holder similar to Phillips, Cat No. ACE Saver 2 Star or equivalent etc as required |
| 15 | Supplying, Installation, Testing and Commissioning of 1 x 4\" CRCA Housing Box Type luminaries suitable for T8 LED Tube (1 x 18 / 20W) Similar to Bajaj Model No. BLRB-DB 118 or equivalent etc as required |
| 16 | Supplying of 20W LED Tube Light with Polycarbonate housing designed for high performance similar to Bajaj Model No. BLRB 20W LEDor equivalent etc as required |
| 17 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.a)Single Pole |
| 18 | Supplying and fixing following rating, four pole, 415 V, isolatorin the existing MCB DB complete with connections, testing andcommissioning etc. as required. a)40 A |
| 19 | a)63 A |
| 20 | Supplying and fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earthbar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator) a)6 Way , Double Door |
| 21 | Supplying and fixing of following ways surface/ recessmounting, vertical type, 415 V, TPN MCB distribution board ofsheet steel, dust protected, duly powder painted, inclusive of200 A tinned copper bus bar, common neutral link, earth bar,din bar for mounting MCBs (but without MCBs and incomer ) asrequired . (Note : Vertical type MCB TPDB is normally usedwhere 3 phase outlets are required.) a) 4 Way (4 + 12), Double Door |
| 22 | Supplying and fixing of45W LED Street Light LuminariesSimilar to Bajaj EDGE NXT LED Model No.ENXT P54L WH PO PC SDwith all accessories or its equivalent with suitable G.I bend standard pipe i/c connections etc. complete as required. |
| 23 | Providing earthing with safe earthing electrode of galvanization 80 to 100 microns, length 2 mtr, outer dia 50 mm, inner dia 19 mm and inner space be filled with crystalline conductive mixture including filling -up with electrolite (Back fill compound) as required for safe earth electrode and providing masonary enclosure with cover plate having locking arrangement etc. as required. (Ashlok)(Proof/ Test Certificate should be enclosed) |
| 24 | Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15 mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. |
| 25 | Providing and fixing 4.00 mm dia copper wire on surface or inrecess for loop earthing along with existing surface/ recessedconduit/ submain wiring/ cable as required. |
| 26 | Fabricationand supplying of street light pole made up of 65mm dia \"B\" class ISI mark G.I. Pipe 6 mtr long with earth stud and necessary G.I reducer/coupling fixed withstreet light bracket made up of 40 mm dia 1.0 mtr long \"B\" class G.I. pipe ISI marked including bending thepipe to the required shape including SMC box of size 250 x 200 x105 mm(outside)thick hinged door and locking arrangement properlymounted on MSflat welded on the pole with DIN channel, 6 A MCB DP and 63 A rating modular 4 way connector and 300 x 300 x 6 mm thick M.S. Base platewelded at the bottom i/c painting with one coat of metallic primer and two coats of synthetic enamel paint,as required as per the direction of the Engineer Incharge . |
| 27 | Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 1.1 KV grade of following size direct in groundincluding excavation and refilling the trench etc as required, butexcluding sand cushioning and protective covering. a)Upto 35 sq. mm |
| 28 | Laying and fixing of one number PVC insulated and PVCsheathed / XLPE power cable of 1.1 KV grade of following sizeon wall surface as required. a)Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 29 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5mm thick G.I. plate with inscription there on, bolted /welded to35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing thesame in ground as required. |
| 30 | Erection of metallic pole of following length in cement concrete1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) foundation including excavation and refilling etc. as required. a) Above 4.5 metre and upto 6.5 metre |
| 31 | Supplying of following XLPE insulated heavy duty armoured aluminium conductor UG cable of 1.1 KV grade conforming to IS 7098 (Part-I) and IS No:1554 (Part-I 1988 as applicable Make: Clooster/ Havells/ Polycab/RR Cable etc as reqd. a) 16 Sqmm x 3 Core |
| 32 | Supplying and layingof one number double walled corrugated high density Polythylene pipe having corrugation on the outer wall and plain surface inner wall confirming to IS 14930 Part -I complete with necessary HDPE fitting for protection of 1.1 KV grade underground cable directly in ground at the depth of 50 cm in the existing cabletrench etc as reqd.a) 50/38mm |
| 33 | Supplying and layingof one number double walled corrugated high density Polythylene pipe having corrugation on the outer wall and plain surface inner wall confirming to IS 14930 Part -I complete with necessary HDPE fitting for protection of 1.1 KV grade underground cable directly on the Surface or Wall etc as reqd.a) 50/38mm |
| 34 | Supplying of Analog Time Switch 240VAC Base/DIN Mounting, 15 x 15 x 15, White in colour as Equivalent to GIC, Model No-J648B1 or its equivalent make. |
| 35 | Supplying of Modular Contractor 40A-3NO Equivalent to L&T Cat No.AUM-3004003 or its equivalent etc., as required. |
| 36 | Supplying, Installation, testing and commissioning of 25W LED POST TOP LANTERN Luminaries withIP66protection, Energy Saving and spun aluminium Landscapewith high power LEDs, Clear Cover bright illumination etc deflector as equivalent to Havells Part No. RUBYPT25WLED830SSYMTOPCor its equivalent. |
| 37 | Supplying and FixingSMC Junctionbox of having inside area 140 x 140 x95mmas equivalent to SINTEXSMC Junction Box Model No-GSJB -1414 mmthick hinged door and locking arrangement properlywith DIN channel, 6 A MCBand 63 A rating modular 4 way Connector. |
| 38 | Supplying and FixingSMC Junctionbox of having inside area 250 x 200 x100mmas equivalent to SINTEXSMC Junction Box Model No-GSJB -2520 mmthick hinged door and locking arrangement properlywith DIN channel(RAILS)etc or its equivalent make. |
| 39 | Supplying, Installation, Testing and commissioning of 45W LED Street Light LuminariesSimilar to Bajaj EDGE NXT LED Model No.ENXT P54L WH PO PC SDwith all accessories or its equivalent. |