Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 23-02-2026 | Corrigendum No 02 | Date | 13-03-2026 |
| 2 | 09-02-2026 | Corrigendum No 01 | Date | 04-03-2026 |
| Sl. No. | Item Description |
| 1 | SCHEDULE \"A\" PART-I - SECTION \"A\" BUILDINGS & STRUCTURESNote: This schedule is not pre-priced by MES and the rate indicated as \"Rs 0.00\" under Col 6 signifies this fact only |
| 2 | Design & Construction of Double storeyed Admin Block / Office Complex (G+1)including Scooter/Car Parking as per Architectural Drawing andas per GRIHA norms complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 3 | Design & Construction of Single Storage Accn for 11 Officers, 38 JCOs, 93 Hav & 297 ORs as per Architectural Drawing complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 4 | Design & Construction of Double storeyed Single Living Accn & Baggage Room (G+1) for ORs as per Architectural Drawing andas per GRIHA norms complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 5 | Design & Construction of Single storeyedCook House &Dining Hall for Ors as per Architectural Drawing andas per GRIHA norms complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 6 | Design & Construction ofSingle storeyed Guard House and Armories including Hard standing as per Architectural Drawing complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 7 | Design & Construction of Single storeyedPump House as per Architectural Drawing complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 8 | Design & Construction of Double storeyed Office & Administrative Accn for 185 FD Wksp Coy (G+1) as per Architectural Drawing andas per GRIHA norms complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 9 | Design & Construction of Single storeyed Scooter Shed & Parking Car Parkingfor 185 FD Wksp Coy & Office as per Architectural Drawing complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 10 | Design & Construction of Single storeyed Repair Workshop & Servicing Bayincluding Hard standing for 185 FD Wksp Coy & Office as per Architectural Drawing complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 11 | Design & Construction of Single storeyed Gate Office as per Architectural Drawing complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 12 | Design & Construction of Single storeyed EME Field Repair Workshopfor 185 FD Wksp Coy including Hard standing as per Architectural Drawing complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 13 | Design & Construction of Single storeyed Batteryy Charging Shop, R & I Office, Store Section, Tool & Expense Storeas per Architectural Drawing andas per GRIHA norms complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 14 | Design & Construction ofSingle storeyed \"B\" & \"C\" Vehicle Garrages including Appronas per Architectural Drawing complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 15 | Design & Construction of Single storeyedMT Store, Petrol Store,Lub Oil & Grease Store and MT Driver Room as per Architectural Drawing complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 16 | Design & Construction of Single storeyed Small Arms Repairs Facility (SARF) as per Architectural Drawing andas per GRIHA norms complete as detailed in scope of work and other documents of tender all as specified and directed . |
| 17 | NOTE: Schedule ‘A’ Part I (Section \"B\") & Schedule ‘A’ Part IIto XVI items which are Prepriced by MES, Bidders shall insert their lump sum amount in the Green coloured field under Col-6 only. |
| 18 | Lump Sum price worked out by the contractor for \"BUILDINGS & STRUCTURES\"as listed in Schedule ‘A’ Part-I (Section \"B\") representing percentage (+ or - denomination) derived under last column of this schedule above/belowthe lump sum price prepriced by the MES B/F from Sl page No. 59 |
| 19 | Lump Sum price worked out by the contractor for \"SITE CLEARANCE, EXCAVATION & EARTH WORK \"as listed in Schedule ‘A’ Part-II representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES B/F from Sl page No. |
| 20 | Lump Sum price worked out by the contractor for \"INTERNAL WATER SUPLLY\"as listed in Schedule ‘A’ Part-III representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES B/F from Sl page No. |
| 21 | Lump Sum price worked out by the contractor for \"INTERNAL ELECTRIFICATION\"as listed in Schedule ‘A’ Part-IV representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES B/F from Sl page No. |
| 22 | Lump Sum price worked out by the contractor for \"ROAD , PATH & CULVERT\"as listed in Schedule ‘A’ Part-V representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES B/F from Sl page No. |
| 23 | Lump Sum price worked out by the contractor for \"SEWAGE DISPOSAL\"as listed in Schedule ‘A’ Part-VI representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceof prepriced by the MES B/F from Sl page No. |
| 24 | Lump Sum price worked out by the contractor for \"AREA DRAINAGE\"as listed in Schedule ‘A’ Part-VII representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES B/F from Sl page No. |
| 25 | Lump Sum price worked out by the contractor for \"COMPOUND WALL & FENCING \"as listed in Schedule ‘A’ Part-VIII representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES B/F from Sl page No. |
| 26 | Lump Sum price worked out by the contractor for \"EXTERNAL WATER SUPPLY\"as listed in Schedule ‘A’ Part-IX representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceof prepriced by the MES B/F from Sl page No. |
| 27 | Lump Sum price worked out by the contractor for \"EXTERNAL ELECTRIC SUPPLY\" as listed in Schedule ‘A’ Part-X representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES B/F from Sl page No. |
| 28 | Lump Sum price worked out by the contractor for \"LIGHTNING PROTECTION\" as listed in Schedule ‘A’ Part-XI representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES B/F from Sl page No. |
| 29 | Lump Sum price worked out by the contractor for \"HOT WATER SUPPLY\"as listed in Schedule ‘A’ Part-XII representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES B/F from Sl page No. |
| 30 | Lump Sum price worked out by the contractor for \"SUMMER APPLIANCES& AIR COOLING SYSTEM\"as listed in Schedule ‘A’ Part-XIII representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES B/F from Sl page No. |
| 31 | Lump Sum price worked out by the contractor for \"ELECTRICALLY OPERATED CRANE & STAND BY DG SET\"as listed in Schedule ‘A’ Part-XIV representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES B/F from Sl page No. |
| 32 | Lump Sum price worked out by the contractor for \"DEMOLITION & DISMANTLING OF BUILDING\"as listed in Schedule ‘A’ Part-XV representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES B/F from Sl page No. |
| 33 | Lump Sum price worked out by the contractor for \"DEMOLITION & DISMANTLING B/R & E&M\"as listed in Schedule ‘A’ Part-XVI representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES B/F from Sl page No. |
| 34 | Sch \"A\" PART-XVII (MISCELLANEOUS B&R AND E&M WORKS)Notes: (i) This schedule is not pre-priced by MES and the pre-priced rate indicated as \"Rs 0.00\" under column 5 signifies this fact only. (ii) Excavation and earth work except for the items which categorically includes for same shall be measured and paid separately under respective schedule. |
| 35 | INTERNAL WATER SUPPLYS & F of 15mm bore dia fancy type chromium plated pillar cock with wall flange, screwed for iron pipe or CPVC pipes or for brass ferrule and fixed complete all as specified and directed.Make -Jaquar Cat Part No ORP-10001PM - 7037 or equivalent. |
| 36 | S&F of CP wall mixer 3 in 1 system with provision for hand shower and over head shower and including 1.5 m long tele shower screwed for iron pipes or CPVC pipes or for brass ferrule and fixed complete all as specified and directed.Make - Jaquar Queen Series Cat Part No QQT - 7281 or equivalent. |
| 37 | S& F overhead shower 150 x 150mm of square shape single flow with rubit cleaning systemABS body crome plated with gray face plate with arm having swivel joint chromium plated complete all as specified and directed.Make - Jaquar Queen SeriesCat Part No OHS - 35495 or equivalent. |
| 38 | Supply and fix health faucet with 1200mm long flexible mild steel tube 15mm dia with wall hook and compete all as specified and directed.Make -Jaquar Queen SeriesCat Part No ALD - 573 or equivalent. |
| 39 | S & F of 15mm bore fancy type chromium plated bib taps with wall flange, screwed for iron pipe or CPVC pipes or for brass ferrule and fixed complete all as specified and directed.Make -Jaquar Essco Seriesor equivalent. |
| 40 | S & F of 15mm bore dia fancy type chromium plated angular stop cock with wall flanged screwed for iron pipe or CPVC pipes or for brass ferrule and fixed complete all as specified and directed.Make -Jaquar Essco Series or equivalent. |
| 41 | INTERNAL ELECTRIFICATIONSupply and fixing load line distribution board TPN vertical, 4 way double door type, fixed on wall semi flush with incoming MCCB 4 poles 100 Amps, 16 KA, busbars ,neutral link, blanking plates complete with all accessories all as specified and as directed.Note: Outgoing MCBs shall be measured and paid separately |
| 42 | Supply and fixing TV sockets complete with all accessories all as specified and as directed . |
| 43 | Supply and fixing RJ 11 Gang with shutter (Telephone Jack) complete with all accessories all as specified and directed. |
| 44 | S & F LEDlight fittins table mounting type with hifgh output diffuser 10 Watt, 2\" length , 220 Volt AC decorative type with driver holder and connecting up with twin core twisted flexible copper conductor cable of suitable sizecomplete all as specified and as directed. |
| 45 | S & F LED LED light fittins 36 Watt, 2 x 2 LED panel light, surface / ceiling mounting , slim square , backlist panel luminaires including LED driver holder and connecting up with twin core twisted flexible copper conductor cable of suitable sizecomplete all as specified and as directed. |
| 46 | Supply & fix 12 Watt LED Downlight having luminous efficacy of > 100, input voltage range 140-270 V, input frequency 50-60 Hzcomplete all as specified and as directed. |
| 47 | M & L for drawing 12 pair / multi core coated copper telephone cable including PVC conduit of size 20mm complete all as specified & directed. |
| 48 | EXTERNAL WAER SUPPLYSupply & laying ductile iron, Pressure pipe, Class K-9, 150mm bore dia centrifugally cast (spun) with spigot & socket end ISI marked with IS-8329-2000 with cement mortar lining inside the pipes with outside zinc coating + bitumen coating suitable for push-on-joint (Rubber gasket D joining) in any lenghth complete including all jointing material and rubber gasket laid in trenches / road / pathways/pedal supports etc including making good for disturbed surfaces of road / path ways etc all as specified and directed. |
| 49 | Supply & laying ductile iron, Pressure pipe, Class K-9, 100mm bore dia centrifugally cast (spun) with spigot & socket end ISI marked with IS-8329-2000 with cement mortar lining inside the pipes with outside zinc coating + bitumen coating suitable for push-on-joint (Rubber gasket D joining) in any lenghth complete including all jointing material and rubber gasket laid in trenches / road / pathways/pedal supports etc including making good for disturbed surfaces of road / path ways etc all as specified and directed. |
| 50 | Cutting the existing water supply DI/GI pipe line 200mm bore dia and taking branch connection of 150mm bore dia pipe by inserting Tee complete all as specified and directed. Note:- Rate quoted by the contractor shall be deemed to be including of TEE & other acessories of required size. |
| 51 | M & L Ductile iron specials of any size & any type for spigot socketed pipes such as bends (any type, radius and angle), tapers, any type (straight bend, increasing, decreasing or double socket etc) Tee pieces, single branch, “Y” junction, double branch, cross (all sockets or socket and spigot), collars, caps and plugs adopters etc of any size radius and lengh confirming IS specifications, for pipe upto 150mm bore dia complete all as specified and directed. |
| 52 | Construction of brick masonry valve pit of size 90cm x 90cm X 90cm (internal dimensions) with one brick thick wall in cement mortar 1:4 on 100mm thick PCC 1:4:8 type D-2 (using 40mm graded broken stone aggregate) as in foundation lean concrete, including PCC 1:3:6, type C-1 (using 20mm graded crushed stone aggregate) as in benching and coping and 10mm thick cement plaster in CM (1:4) internally and externally upto 15cm below ground level providing valve pit cover 40x 40 x 6mm angle iron frame all-round fixed by means of 4 Nos holdfast 150mm long made out of flat iron 40 x 6mm embedded in PCC block 1:2:4, type B-1 (using 20mm graded crushed stone aggregate) of size 230 x 200 x 100mm including provn of hinges welded with angle iron frame and MS cover 3mm thick sheet, MS handle of suitable length and size welded with MS cover and suitable locking arrangement and applying two coats of synthetic enamel paint over a coat of red oxide primer including necessary excavation and earth work in soft / loose soil complete all as shown on drawing and as specified. |
| 53 | All as per item No 35above of size 60cm x 60cm x 60cm complete |
| 54 | Supply and fix 150mm (6\"\") bore dia Foot Valve conforming to IS-4038 complete all as specified and as directed. |
| 55 | Supply, install, testing and commissioning for self priming monoblock pumpingset of 12.5 HP having minimum discharge not less than 1000/LPM, head range not less than 36 Mtrs with brass impeller, 3 phase, 50 cycle, 415 volts star delta connected, copper wound induction motor, including base frame, PCC foundation, nut, bolts,3 core copper flat cable of suitable size length from pump set to starter complete all as specified and directed. |
| 56 | EXTERNAL ELECTRIFICATIONSSupply & FixingAutomatic astronomical functional timer switch (Having longitute & altitude of Indian cities on memmory) 250 Volts, Single phase, 20 Amp rating with inbuilt contactor in enclosure, max load of 08 KW including iron clamps , nuts bolts etc complete all as specified and as directed. |
| 57 | M & L for 2.5 Sqmm twin core copper conductor PVC insulated PVC sheathed cable 1100 Volt grade for drawing through poles for making connection to street light fitting provided on poles and upto junction box including thimble etc complete all as specified and as directed. |
| 58 | Supply and fix of path way fitting Bollard light suitable for retrofit LED bulb8 Watt including fixing accessories i.e Nuts, bolt, washer etc duly fixed at site on PCC 1:2:4, type B-1) foundation type 40cm x 40cm x 40cm complete all as specified and directed. |
| 59 | Supply and fix press moulded SMC junction box of inner demensions 250 x 200 x 105mm, suitable for 3 phase, 4 core cable including 8 way connector, MCB SP 230 Volt, AC 50 Hz 10 KA-01 No weather proof cable connecction 2 x 2.5 Smm conductor from MCB to street light fitting and suitable fittings and fixture complete all as specified and directed.Make : Sintex/Hensel or Techno commercial equivalent as given in list of makes. |
| 60 | Supply, install and commissioning of factory made Main LT panel outdoor type , self supported, CPRI Approved make, front and rear openable, double door hinged type with locking arrangement and slopping top canopy, suitable protection with dust and vermin proof etc, fabricated out of 3.00mm thick CRCA sheet duly powder coated with 7 tank chemical process, mounted fixed on and included MS angle section 50 x 50 x 6mm on PCC 1:2:4 type B-1, platform 60cm above the ground level and 45cm below the ground level, factory fabricated with front andback openable double door system with andlock openable by keys, having chromium plated 19mm dia fancy lock, louvers and air vent, gasketconsisting offollowing :- (Near 250 KVA TFR) |
| 61 | (a) Copper bus bar 650 Amps Cap 4 wire fixed on insulator not less than 1.0 Mtr long bus bar - 01 Set INCOMING (a) MCCB 4 POLE, 415 Volts, AC, 630 Amps, 50 KA repturing capacity- 01 No. (For incomming main panel) OUTGOING (a) MCCB 4 POLE, 415 Volts, AC, 400 Amps, 36 KA repturing capacity- 01 No. (For BHQ panel)(b) MCCB 4 POLE, 415 Volts, AC,125 Amps, 16 KA repturing capacity - 01 No (For JCO Mess panel ,Phase-II)(c) MCCB 4 POLE, 415 Volts, AC,100 Amps, 16 KARepturing capacity with thermal magnetic release - 02 Nos (OR LINE Panel & Spare) (d) MCCB 4 pole, 63 Amps, 415 Volt, AC, 16 KArepturing capacity with thermal magnetic release - 01 No. (For Pump House)(e) MCCB 4 pole, 32 Amps, 415 Volt, AC, 16 KArepturing capacity with thermal magnetic release - 02 Nos. (For Spare & Street light) (f) Digital Voltmater 0 - 500 Volt of size 96 x 96mm square with selector switch - 01 No.(g) Indicator lampe (RYB) with holder (Set to three) - 01 Set(h) Ammeter 0 to 630 Amp with selector switch & suitable range of CTs - 01 No |
| 62 | Supply, install and commissioning of factory made Main LT panel outdoor type , self supported, CPRI Approved make, front and rear openable, double door hinged type with locking arrangement and slopping top canopy, suitable protection with dust and vermin proof etc, fabricated out of 3.00mm thick CRCA sheet duly powder coated with 7 tank chemical process, mounted fixed on and included MS angle section 50 x 50 x 6mm on PCC 1:2:4 type B-1, platform 60cm above the ground level and 45cm below the ground level, factory fabricated with front andback openable double door system with andlock openable by keys, having chromium plated 19mm dia fancy lock, louvers and air vent, gasketconsisting offollowing :- (For BHQ) |
| 63 | (a) Copper bus bar 600 Amps Cap 4 wire fixed on insulator not less than 1.0 Mtr long bus bar - 01 Set INCOMING (a) MCCB 4 POLE, 415 Volts, AC, 400 Amps, 36 KA repturing capacity- 01 No. OUTGOING (a) MCCB 4 POLE, 415 Volts, AC, 160 Amps, 25 KA repturing capacity with thermal magnetic release - 02 Nos. (For Adm Block & Spare)(b) MCCB 4 POLE, 415 Volts, AC,100 Amps, 16 KA repturing capacity with thermal magnetic release - 02 Nos (For Cook house & Dining Hall)(c) MCCB 4 POLE, 415 Volts, AC,63 Amps, 16 KARepturing capacity with thermal magnetic release - 01 No (For Quarter Guard) (d) MCCB 4 pole, 32 Amps, 415 Volt, AC, 16 KArepturing capacity with thermal magnetic release - 05 Nos. (For Guard House, Parking Adm, Street light, Storage & Boom barrier) (f) Digital Voltmater 0 - 500 Volt of size 96 x 96mm square with selector switch - 01 No.(g) Indicator lampe (RYB) with holder (Set to three) - 01 Set(h) Ammeter 0 to 400 Amp with selector switch & suitable range of CTs - 01 No(j) Change over switch for DG 160 Amps - 01 No |
| 64 | Supply, install and commissioning of factory made Main LT panel outdoor type , self supported, CPRI Approved make, front and rear openable, double door hinged type with locking arrangement and slopping top canopy, suitable protection with dust and vermin proof etc, fabricated out of 3.00mm thick CRCA sheet duly powder coated with 7 tank chemical process, mounted fixed on and included MS angle section 50 x 50 x 6mm on PCC 1:2:4 type B-1, platform 60cm above the ground level and 45cm below the ground level, factory fabricated with front andback openable double door system with andlock openable by keys, having chromium plated 19mm dia fancy lock, louvers and air vent, gasketconsisting offollowing :- (For OR Line) |
| 65 | (a) Aluminium bus bar 150 Amps Cap 4 wire fixed on insulator not less than 1.0 Mtr long bus bar - 01 Set INCOMING (a) MCCB 4 POLE, 415 Volts, AC, 100 Amps, 16 KA repturing capacity- 01 No. OUTGOING (a) MCCB 4 POLE, 415 Volts, AC, 32 Amps, 16 KA repturing capacity with thermal magnetic release - 06 Nos. (For OR Line & Spare)(b) Digital Voltmater 0 - 500 Volt of size 96 x 96mm square with selector switch - 01 No.(c) Indicator lampe (RYB) with holder (Set to three) - 01 Set(d) Ammeter 0 to 100 Amp with selector switch & suitable range of CTs - 01 No |
| 66 | Supply, install and commissioning of factory made Main LT panel outdoor type , self supported, CPRI Approved make, front and rear openable, double door hinged type with locking arrangement and slopping top canopy, suitable protection with dust and vermin proof etc, fabricated out of 3.00mm thick CRCA sheet duly powder coated with 7 tank chemical process, mounted fixed on and included MS angle section 50 x 50 x 6mm on PCC 1:2:4 type B-1, platform 60cm above the ground level and 45cm below the ground level, factory fabricated with front andback openable double door system with andlock openable by keys, having chromium plated 19mm dia fancy lock, louvers and air vent, gasketconsisting offollowing :- (For Pump House) |
| 67 | (a) Aluminium bus bar 150 Amps Cap 4 wire fixed on insulator not less than 1.0 Mtr long bus bar - 01 Set INCOMING (a) MCCB 4 POLE, 415 Volts, AC, 100 Amps, 16 KA repturing capacity- 01 No. OUTGOING (a) MCCB 4 POLE, 415 Volts, AC, 63 Amps, 16 KA repturing capacity with thermal magnetic release - 03 Nos. (For Pump-02 & Spare-01)(b) Star delta Starter fully automatic suitable for 415 Volt, AC, for 12.5 HP Motor-02 Nos(c) Digital Voltmater 0 - 500 Volt of size 96 x 96mm square with selector switch - 01 No.(d) Indicator lampe (RYB) with holder (Set to three) - 01 Set(e) Ammeter 0 to 150 Amp with selector switch & suitable range of CTs - 01 No |
| 68 | Supply, install and commissioning of factory made Main LT panel outdoor type , self supported, CPRI Approved make, front and rear openable, double door hinged type with locking arrangement and slopping top canopy, suitable protection with dust and vermin proof etc, fabricated out of 3.00mm thick CRCA sheet duly powder coated with 7 tank chemical process, mounted fixed on and included MS angle section 50 x 50 x 6mm on PCC 1:2:4 type B-1, platform 60cm above the ground level and 45cm below the ground level, factory fabricated with front andback openable double door system with andlock openable by keys, having chromium plated 19mm dia fancy lock, louvers and air vent, gasketconsisting offollowing :- (For 185 Work Shop) |
| 69 | (a) Copper bus bar 630 Amps Cap 4 wire fixed on insulator not less than 1.0 Mtr long bus bar - 01 Set INCOMING (a) ACB 4 POLE, 415 Volts, 800 Amps with Thermal Magnetic Release (Manual Fixed type) - 01 No OUTGOING (a) MCCB 4 POLE, 415 Volts, AC, 630 Amps, 50 KA repturing capacity- 02 Nos. (For Sub panel) (b) MCCB 4 pole, 100 Amps, 415 Volt, AC,16 KA rupturing capacity - 02 Nos(For EME Workshop & Spare) (c) MCCB 4 pole, 63 Amps, 415 Volt, AC,16 KArupturing capacity with thermal magnetic release - 01 No(For 185 Office) (d) Digital Voltmater 0 - 500 Volt of size 96 x 96mm square with selector switch - 01 No.(d) Indicator lampe (RYB) with holder (Set to three) - 01 Set(e) Ammeter 0 to 630 Amp with selector switch & suitable range of CTs - 01 No |
| 70 | Supply, install and commissioning of factory made Main LT panel outdoor type , self supported, CPRI Approved make, front and rear openable, double door hinged type with locking arrangement and slopping top canopy, suitable protection with dust and vermin proof etc, fabricated out of 3.00mm thick CRCA sheet duly powder coated with 7 tank chemical process, mounted fixed on and included MS angle section 50 x 50 x 6mm on PCC 1:2:4 type B-1, platform 60cm above the ground level and 45cm below the ground level, factory fabricated with front andback openable double door system with andlock openable by keys, having chromium plated 19mm dia fancy lock, louvers and air vent, gasketconsisting offollowing :- (For 185 Work Shop) |
| 71 | (a) Copper bus bar 630 Amps Cap 4 wire fixed on insulator not less than 1.0 Mtr long bus bar - 01 Set INCOMING (a) MCCB 4 pole, 630 Amps, 415 Volt, AC,50 KA rupturing capacity - 01 No (For Sub Panel)OUTGOING (a) MCCB 4 POLE, 415 Volts, AC, 160 Amps, 25 KA repturing capacity- 02 Nos. (For Equipment user (SARF Phosphanting) & Battery Charging) (b) MCCB 4 pole, 63 Amps, 415 Volt, AC,16 KA rupturing capacity with thermal magnetic release - 01 Nos(For Spare) (c) MCCB 4 pole, 32 Amps, 415 Volt, AC,16 KArupturing capacity with thermal magnetic release - 08 No(For Spare , Street light, Veh garage & Parking, SARF paniting, SARF Drying Oven, SARF Compressor, SARF Degreasing of WPN) (d) Digital Voltmater 0 - 500 Volt of size 96 x 96mm square with selector switch - 01 No.(d) Indicator lampe (RYB) with holder (Set to three) - 01 Set(e) Ammeter 0 to 630 Amp with selector switch & suitable range of CTs - 01 No |
| 72 | Supply and fix Gate light in aluminum die cast with modern artistic design and whitePC diffuser suitable with LEDlampcomplete all as specified and directed. |
| 73 | HOT WATER SUPPLYSupply, Install, Testing and Commissioning of \"Solar Hot Water System\" (Flat Plate Collector) based on indirect transfer of heat of capacity 500 LPD alongwith stand for collector, staging for suitable height for easy flow of water for cold water tank made out of 50 x 50 x 6mm angle iron with PCC 1:2:4 as required complete with temperature guage 0 to 100 degree centigarate , brass gate valve for hot & cold water pipes , horizontal type strainer on incoming water line all as specified and as directed. NOTE: Water storage tanks will be measured and paid separatly under relevent item. |
| 74 | upply and fix electric water heater, storage type steel body with copper inner tank and heating element upto 2 KW capacity 50 Litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc. complete all as specified and directed. |
| 75 | SUMMER APPLIANCES & AIR COOLING SYSTEMS & F Desert cooler electric driven single phase having nominal Air flow capacity 5000 Cum per Hrs including front panel with show grillIron made out of GI sheet 22 SWG complete including front show platewith ON/OFF switch for pump & four speed regulator ISI marked, fan 18\" ISI marked , 4 Mfd capacitor, submersible pump ISI marked , wood wool pad (Set of three) heavy duty includinginterconnecting water and electric witing complete all as specified and directed. |
| 76 | Supply and fix Refrigerator, electric driven (single phase), capacity 310 Litres, BEE, 5 Star rated,all as specified and directed. Make :- Voltas / LG / Samsung / Godrej |
| 77 | Supply and fix Refrigerator, electric driven (single phase), capacity 195 Litres, BEE, 5 Star rated,all as specified and directed. Make :- Voltas / LG / Samsung / Godrej |
| 78 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 Volt to 250 Volt with output voltage stabilized at 230 Volt with accuracy of ± 2.5% and of capacity 4 KVA complete all as specified and directed. Make :- Servo or Equivalant as given in Appdx \"H\" list of makes |
| 79 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 Volt to 250 Volt with output voltage stabilized at 230 Volt with accuracy of ± 2.5% and of capacity 2 KVA complete all as specified and directed. Make :- Servo or Equivalant as given in Appdx \"H\" list of makes |
| 80 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 Volt to 250 Volt with output voltage stabilized at 230 Volt with accuracy of ± 2.5% and of capacity 1 KVA complete all as specified and directed. Make :- Servo or Equivalant as given in Appdx \"H\" list of makes |
| 81 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 Volt to 250 Volt with output voltage stabilized at 230 Volt with accuracy of ± 2.5% and of capacity 0.5 KVA complete all as specified and directed. Make :- Servo or Equivalant as given in Appdx \"H\" list of makes |
| 82 | Supply, installation, testing and commissioning of Central Air Cooling Unit Double Skin 10000 CFM Floor Mounted Double Skin (Inner Panel Shall be made out of 0.6mm GI Plain and Outer Panel shall be 0.6mm Precoated GI with 25mm thick Puff Insulation having density of 40 Cum giving 90% efficiency at 500 FPM air velocity across the pads with Tank Made out of 18 Guage Stainless Steel, Cellulose Pad of 200mm thick, pad area 40 Sqft, having Pre filters of aluminium wire mesh and filter frame made of GI sheet. The filter shall have 90% down to 10 Microns filtration efficiency. Cabinet Make – Evapoler Water Recirculation Pump 0.5 HP Circulation, BLOWER DIDW Forward Curved, 800mm Dia Fan (AMCA Certified) Heavy Duty Centrifugal Blower having Forward Curved Impeller, DIDW (Double Inlet double width) Made out of 16 Guage GI enclosed in suitable housing and mounted on EN 8 Shaft duly dynamically and statically balanced. 11 KW/4 Pole, Class F Motor, IE 1 Motor shall be suitable for 415 Volts, 50 Cycles,3 Phase AC Power Supply with IP-55 protection for enclosure complete all as specified and directed.. |
| 83 | Supply, installation, testing and commissioning of Central Air Cooling Unit Double Skin 5000 CFM shall be Floor Mounted Double Skin(Inner Panel Shall be made out of 0.6mm GI Plain and Outer Panel shall be 0.6mm Precoated GI with 25mm Thick Puff Insulation having density of 40 Cum giving 90% efficiency at 500 FPM air velocity across the pads with Tank Made out of 18 Guage Stainless Steel, Cellulose Pad of 200mm Thick, pad area 40 Sqft, having Prefilters of aluminium wire mesh and filter frame made of GI sheet. The filter shall have 90% down to 10 Microns filtration efficiency. Cabinet Make – Evapoler Water Recirculation Pump 0.5 HP Circulation, BLOWER DIDW Forward Curved, 800 mm Dia Fan (AMCA Certified) Heavy Duty Centrifugal Blower having Forward Curved Impeller, DIDW (Double Inlet double width) Made out of 16 Guage GI enclosed in suitable housing and mounted on EN 8 Shaft duly dynamically and statically balanced. 11 KW/4 Pole, Class F Motor, IE 1 Motor shall be suitable for 415 Volts, 50 Cycles, 3 Phase AC Power Supply with IP-55 protection for enclosure complete all as specified and directed.. |
| 84 | Supply, Installation & testing of Galvanised Sheet of 22 Gauge fabrication of duct with damper and complete nitrile rubber insulation as directed at sitewith Connectors, GI Flanges, turning vanes, with proper duct sealing etc with RTV duct Sealant, Complete with supports omplete all as specified and directed.. |
| 85 | All as per item No 61 but for 20 Gauge FABRICATED Duct |
| 86 | All as per item No 61 but for 18 Gauge FABRICATED Duct |
| 87 | ELECTRICALLYOPERATED CRANEDesign ,Manufacturing, Supply, Erection & Commissioning of indoor type, medium duty class M5, Electrically operated travelling (EOT) overhead crane as per IS : 3177 & 807 (latest version), IS : 2148 of 2004, capable of handling 05 Metric Tonnes (MT) main hoist with centre to centre clear span approximate 15 Metres, double box girder type including floor operated moveablependant control by means of push buttons independent of crab trolley position, protective panel with down shop lead (DSL), trailing cable complete with all accessories / equipments duly painted with two coat of synthetic enameledpaint all as per OEM specifications and as approved by GE. The make of crane shall be as per approved list of make given in P.S or otherwise the manufacturer who installed the crane in MES department with following specification : |
| 88 | EOT cran shall be provided with the following electrically controlled movements type:-(a) Capacity of crane- 05 Ton double box Girder.(b) Clear span - 11 Metres approx each. (c) Bay length - 55 Metres approx. (d) Hook height -5.5 Metres from the floor level. (e) Longitudinal Travel speed - 10 mpm and micro LT speed 1.0 mpm(f) Cross travel speed-7 mpm and micro CT speed 0.7mpm (g) Hoisting speed- 3 mpm (h) Micro hoisting speed-0.3 mpm (j)Control - Pendant control(k) LT wheel track size -As per OEM recommendations(l)CT wheel track size- As per OEM recommendations |
| 89 | NOTE :- (a) Unit rate quoted shall be deemed to include provision of copper wiring of suitable size in rigid metallic conduits with accessories fixed on surfaces from main switch upto electrical control panels and provision of ISMC channel welded alongwith ISMB (gantry girder) and longitudinal travelling rail welded alongwith ISMC.(b) Clear span and bay length specified and shown on building are only indicative. The tenderer shall visit the site and ascertain exact span and bay length before designing/execution.(c) Long travel gantry girder is in the scope of building work & LT wheel andCT wheel track Sqbar has to be provided by the tenderer and cost for the same is to be included in unit rate .(d) Cap channel and rail of both sides included quoted rate it deemed to be included such provision and accessoriesbefore execution of work.(e) Dimensions, capacities/sizes of equipments/accessories mentioned on drawing are minimum to be provided. Prior approval of accepting officer shall be obtained for the detailed construction drg and electrical wiring diagram ofEOT crane and contractor shall incorporate components wherever required and the rates quoted above shall be deemed to be inclusive of such provisions and all accessories.(f) Longitudinal travel shall be limited to 1.5m away from the wall on both ends.(g) The cranes should be manufactured as per latest IS standards and safety factors. |
| 90 | EOT Crane shall comprise of the following :- (1) Major Technical Specification: Type, Capability and general requirements(a) Type : Double box type girderEOT Crane as per IS : 807 & IS : 3177.(latest version)(b) Crane Operation : Pendant control of reputed make with push button for ON, OFF, UP, DOWN, Forward, Reverse, Left, Right, Siren, Bridge Light & Emergency Stop with option for control selection.Operating voltage 110 Volts.(c) Duty Class : M5 for Indoor Operations.(d) Lifting Capacity : 05 Metric TON(e) Span :11 metre(f) Height of Lift :5.5 metre(g) LT Wheel Rail Track Size :Minimum 50x50 Sqmm bar.(h) CT Wheel Rail track size : 50 x 50Sqmmbar. (j) Bay Length :55 Metre approx.(k) Clearance between Rail Top to soffit Roof :As per drawing |
| 91 | (2) Maximum Speed (Metre/Min) :- (a) Hoisting : 3 mpm and 0.3 microspeed.(b) 10 mpm and 1 mpm microspeed LT Speed(c) 7 mpm and 0.7 mpm microspeed CT Speed(3) Hook Approach (Maximum possible):(a) Side Clearance: Side clearance to be fixed to suit the Blanking section clearances minimum 250/300mm.(4) Long Travel Motion : LT Motion shall be twin drive type.(5) STRUCTURAL FABRICATION Constructional Details) :(a) Bridge Girder: Shall be of double Girder Box Type construction having Minimum vibrations.(b) End Carriage Fabricated from rolled steel sections/plates as per IS : 2062 (c) Raw Material : Only tested quality steel Fe 410 WB as per IS-2062, IS : 1964 & IS : 808 and certified for quality by reputed inspection authorities, shall be used. |
| 92 | (d) BRIDGE STRUCTURE / CRANE GRIDER: Shall be made out of double box girder type construction having minimum flange width 500 mm and thickness 6.00mm , minimum Web height 1250mm, thickness 8.00mm. Beam should not have deflection more than 1/900 of span on full load as per BS : 466/1960, all as per OEM specifications.(e) Welded Joints (To be followed for Girder fabrication)(i) NO Number of Joints allowed: Max 2 Nos(ii) Welding Electrodes for all Horizontal Welding E-7018 Electrode only should be used.(iii) Welding Electrodes for all Vertical Welding E 7048 Electrode only should be used(f) Welded Joint Testing : All Butt Welded Joint (both compression/tension and flanges/web joints) shall be subjected to 100% X-Ray Testing and X-Ray Film to be produced for MES evaluation and form part of the documentation.(g) Mechnical Joints: Hexagonal Fit Bolts (as per IS 3640-1982) for all joints coming in Main members (h) Heat Treatment & NDT Examination : The Trolleys shall be stress relived, if necessary, by thermal heat-treatment process after welding & NDT.All welding shall be tested by NDT means [MPI, LPI & RT] after stress relieving operation (Govt. approved Test House & certificated).Contractor to furnish the details of facilities for Heart Treatment furnace & NDT Lab at their works.All the welded joints should be NDT tested by Govt. approved Test House & certificate/X-Ray films to be submitted at time of inspection.. |
| 93 | (6) MECHANICAL ELEMENTS : (a) Wheels :Wheels shall beas per IS of forged and made of C-55 Mn 75 Carbon steel, Hardened to BHN 300-350 as per IS /OEM specifications.(b) Wheels Sizes : Outer diameter shall be as under :-(i) Cross Travel (CT) – Contractor to submit the sizeas per OEM specificaton.(ii) Long Travel (LT) – Contractor to submit the size as per OEM specificaton(c) Number of Wheels : For LT - 04 Nos & CT - 04 Nos.(d) Wheel Assembly : The wheel Assembly of Long Travel (LT) shall be of Live Axle System with L-Type Bearing only.(e) Brake Drum Sizes and minimum braking torques : (i) Main Hoist :As per OEM specifications & design calculation(ii) Cross Travel:As per OEM specifications & design calculation. (iii) Long Travel: AS per OEM specifications & design calculation. |
| 94 | (f) Gear & Gear Boxes Details : Gear Box should be of fabricated type duly stress relived.Pinions made of En-24 and gears of En-18.Gears in all the Stages shall be helical in design and to be of machined, lapped and hardened.Straight and helical spur gearing shall normally be used for all motions.Worm and bevel gears shall not be used.First and high speed reductions shall be through helical gears.All first reduction pinions and also the other pinions if feasible shall be integral with the shafts.All gears shall be of hardened and tempered alloy or carbon steel with machine cut teeth.Gear tooth shall be cut in metric module system.Surface hardering of teeth is not allowed.The Gear /pinion should be hardened to HRC 50-55 and ground.Reduction Gear box ratios in all motions shall be maintained as under : - (i) Main Hoist: As per OEM specifications.(ii) Cross Travel (CT) : As per OEM SPECIFICATIONS .(iii) Long Travel (LT) : As per OEM specifications. |
| 95 | (g) Lubrication : Suitable totally enclosed continuous oil/grease lubrication system shall be provided for gear box for its all rotating parts wherever applicable. (h) Rope Drum : Shall be fabricated type stress relived or seamless pipe.The circumferential weld joints shall be tested by 100% A-Ray quality size i.e. diameter and length shall be as under. :-(j) Main HoistRope Drum : As per OEM specificationsNS .(k) Type of Coupling : Coupling should beflexible geared Barrel type. No pin /bush / rubber type coupling to be used. (l) Machining Operation : All mechanical mating surfaces and wheel seating areas are to be machine to the required finish and protected. (m) Hoist Wire Rope Details : Fiber core confirming to IS : 2266. Maintion wire rope dia 16mm, 4 No. of fall & construction.Minimum factors of safety & tensile strength (1960N/Sqmm for wire rope) as per ISO : 4309 :1990 or as per OEM Specification & design. (n) Main Hoist : As per OEM specifications. (o) Buffers (End Stoppers) : Buffers of adequate size be provided. (p) Maintenance Platform : Maintenance / service platform made of 6.0mm thick chequered plate of 750mm width shall be provided & fixed through bolted joints only.A hand railing 1000mm height are to gaurd(Minimum 50mm) shall also be provided.Platform shall have anti-skid grating. (q) Guards : All the moving parts should be duly covered with guards as per safety norm.Proper guard cover / tray to prevent falling of bolts from coupling etc should also be provided, wherever required. |
| 96 | (7) Electricals : (a) Input Power Supply : Shall be 415 ± 10% Volts, 50 ± 3% Hz, 3 Phase, AC.(b) Control Voltage : Shall be 110 Volt AC. (c) Protection : All Panels, Limit-Switches and Motor shall be IP-54 protection.(d)Motor Details :Squirrel Cage Induction Crane duty motors, Totally enclosed, fan cooled, Insulation Class-F & confirming to relevant latest IS:325, and IS-123, S4 duty, 150 starts per hour and 40% CDF.All electric motors shall be provided VVVF drives in all motions, Noted No. of motors, capacity of motor as under. (i) Main Hoist : Min of10 HP speed less than 1000 rpm or as per OEM specifications.(ii) Cross Travel (CT) : Min of 0.5 HP speed less than 1000 rpm or As per OEM specifications.(iii) Long Travel (LT) : 2 Nos of Min of 0.5 HP speed less than 1000 rpm or as per OEM specifications.(e) Type & Details of Brakes for all Motions : EHT type shall be provided to hold the mechanism in position instantaneously as soon as the power supply is ‘OFF’ either accidentally for all motions. (f) Electric Contactors : All Contactors shall have SIEMENS / L&T/ BCH contactors suitable for Crane operations.Crane duty AC-4 ratings. |
| 97 | (g) Contactor Rating : The rating of all contactor shall be at least 50% higher than the respective electric motor full load current, at the specified duty cycle. (h) Wiring: All the panel wiring should be done by using standard multi core Copper conductor highly flexible, FRLS cables.(j) Down Shop Lead (DSL) : XLPE/PVC insulated copper conductor festoon trailing cables fire resistant and retardant cables as per IS : 694. (k) Trailing Cables Erection : Trailing cables (Extra flexible having copper conductors only)for CT shall be supplied with ready chain type (E-chain) with tongue and groove type (Make - Igus / Gortrac) and erected by contractor. LT shall be tailing cables, Fastoon type, copper conductor. (l) IIlumination : 03 Nos totally enclosed 100 w LED Lamps and fitting shall be provided under the bridge. (m)Limits Switches : Hoist shall be provided with gravity type (Over Hoisting and Over lowering).Shunt adjustable type limit switches.Limit switches shall be provided for both CT and LT motions.Two way lever type for CT and LT for both directions. (n) Pendent control : Pendent should be MS Sheet fabricated having push buttons for each motion e.g. Bridge light, Siren/bell On and Off switches and stay put type emergency stop switch push button.Pendent shall be independent moveable type.(o) ANTI-COLLISION DEVICE: As per OEM specifications |
| 98 | (8) Painting Instructions:. (a) Surface Cleaning : Girder to be shot blasted or chemically treated for surface cleaning, after completion of all operations but prior to painting.(b) Painting :One coat of Red Oxide Primer and 48 hours of compulsory curing after painting..(c) The crane should be thoroughly cleaned and final painting with two coat of synthetic enameled paints(Colour- Golden Yellow)and intermitted curing of 16 hours.Final touching will be done after erection and testing. |
| 99 | (9)MAKES OF BOUGHT OUT ITEMS (BOI) : Makes shall be as per the list given below.(a) Hoist Hooks : Herman Mohtta / Hercules / Silpa Udyog / Smriti Forgings / Karachiwala (b) Wire Ropes: Usha Martin / Fort William / GARWARE.(c) Electric Motors : GE/ Bharat Bijlee / Siemens / KEC / ABB / Crompton / Alstom /marathan.(d) Thruster Brake Unit : ElectroMag / Speed-O-Control / Omega. (e) Limit Switches (Gravity type) : Siemens / EMM/BCH / SOC / SKF. (f) Contactors : Siemens / L&T / GE / BCH (g) Over Load /Time Relay : Siemens / L&T/GE / BCH. (h) HRC Fuses : Siemens / L&T / GE |
| 100 | (j) Switch fuse unit : Siemens / L&T / GE / BCH .(k) MCB / MCCB : Siemens / L&T / GE. (l) PUSH Buttons : Siemens / L&T /BCH. (m) Couplings : As per OEM.(n)Bearings : SKF /FAG / NTN / Ina only. (o) Cables : LAPP / Schiess Kabel / CCl / Fort Gloster / Grandely / Finolex / KEI ISI marked/polycab / IGUS . (p) Bridge light fittings : Bajaj / Philips / Wipro / Sudhir / Balaji / Flexpro .(q) Transformer : Logistat / Pactil / Any reputed make. (r) Control Panel : As per OEM specification.(s) Documents / Details for submission : The following documents/ details shall be submitted to MES reference for approval of accepting officer / checking within 30 days from the date PO placement, prior to taking up the manufacturing of the crane. |
| 101 | (10) Drawing / Documents : For approval from accepting officer.(a) GA Drawing of the Crane (for approval) - Contractor to submit.(b) GA Drawing of Hoist/Trolley(for approval) - Contractor to submit .(c) Calculation of Bridge Girder- ISMB / ISMC - Contractor to submit. (d) Calculation for Selection of Electric Motors, Gears, Brakes, Couplings, Wheels, Wire Rope etc.: Contractor to submit.(e) Design calculation for Bridge Girder, Crab etc.: Contractor to submit. (f) Calculation of Bridge Girder- ISMB / ISMC - Contractor to submit. (g) Wiring Diagram with Logic Circuits and Bill of Material (for Approval) -Contractor to submit. and diagonal -10 kg pull should be applied while checking - Contractor to comply |
| 102 | (11) INSPECTION : (a) Verification of Test certificate for Raw materials used for Girders, end carriages, Hoist, Gear box casings etc - Contractor to comply. (b) Verification of X-Ray report of butt joints coming in the girders and Random testing on the welds by Physical examination - Contractor to comply. (c) Inspection of Bridges and End carriages with Wheel assembly and Alignment checking - Contractor to comply.(d) Verification of Span and diagonal dimensions, Checking of Wheel Alignment, Mechanical Assemblies and Total Alignment - Contractor to comply.(e) Free running of the CT and Hoist mechanisms - Contractor to comply. (f) Check of Crane span(g) Measurement of CAMBER in the bridges - Contractor to comply.(h) Full/ Rated Load Test and deflection test - Contractor to comply. (j) 125% Rated-LOAD Lifting ability check - Contractor to comply . (12) CRANE ERECTION & COMMISSIONING (a) Unloading & Erection : Unloading the consignment at site will be carried out by the Contractor. Contractor shall shift the all crane material to site and erect the crane at MES site. Necessary tools and equipments required for erection shall be brought by the Contractor. (b) Crane Commissioning : Prove out for the Crane’s Capacity and Smooth Functioning of the Crane (at site) shall be the responsibility of the Contractor.Final Load testing as per ISS at 125% of rated load shall be conducted at site by the representative of Accepting Officer in the presence of Engineer-in-Charge.Load shall be arranged by contractor from location at site shown by Engineer-in-charge. (c) All safety equipments like safety boot,saftey belt, helmet, gloves, loader, googles etc required for erection personnel shall be brought bt contractor-contractor to comply . |
| 103 | (13) TOOLS & SPARES :(i) Tool box with standard tools shall be supplied with the crane.(ii) Recommended spares for two years normal working of equipment shall be furnished. Details of bearings, oil seals used should be supplied with the crane. (14)O & M Manuals :(a) Five (05) sets, of Erection, Operation and Maintenance Manual along with two sets of CDs, containing the following technical drawings and details shall be submitted.All copies shall be hard bound in high quality leather folders, encased in decent individual boxes. (b) Contractor is required to measure all necessary dimensions i.e. Span, Head room, Clearances between rail centre to existing coloumn and rail size etc, at site before starting of the crane design/ manufacturing. |
| 104 | (15) ADDITIONAL NOTES : (a) The details refered to above will be considered as our offer.(b) Any ‘T’ bid details even after all confirmation are found missing or left out, the details and specifications given in the tender documents shall be followed. |
| 105 | STAND BY DG SETSupply, installation, testing and commissioning of silent DG Set, conforming to IS: 10002-1981 complete with Diesel Engine of suitable BHP & AC Brushless SPDP alternator, conforming to IS : 13364-1992, mounted on a common base frame & coupled through a flexible coupling or close coupled complete with suitablePCC foundation platform,control panel having meters, Remote monitoring unit, sound-proof canopy etc. of not less than 100 KVA(80KW) capacity conforming to the following specifications complete all as specified and directed. Make :Kirloskar , Crompton Greves, Cummins |
| 106 | [a] Engine : 4 cylinder, in-line, 4 stroke, radiator cooled engine, well designed air handling system with dry type, heavy duty, replaceable paper element air cleaner with restriction indicator, air to air aftercooling, optimised turbocharger for increased altitude,Inline fuel pump with class H electronic governing, spin on fuel filter, standard integral set-mounted radiator system, designed and tested for 50°C ambient temperature, full flow spin on lube oil filter, electrical starter motor with soft start engagement feature, battery charging alternator with 1 x 24 or 2 X 12 V DC dry type battery. |
| 107 | [b] Alternator: Brushless type, screen protected, revolving field, self-excited alternator, conforming to IS/IEC 60034-1 3-phase reconnectable winding with 12 terminals brought out for connection, dedicated winding specially designed for single operation, impregnation on all wound components for better mechanical strength |
| 108 | [c] Control Panel : Manufactured with 14/16 gauge CRCA sheet and powder coated for weather-proof and long lasting finish. |
| 109 | The control panel consists of the following parts :[i] Controller: Aluminum bus bars with suitable capacity with incoming/outgoing terminals. [ii] Indicating lamps for ‘Load ON’ and ‘Set Running’. [iii] Instrument fuses duly wired and ferruled. [iv] MCCB of suitable rating with overload and short circuit protections |
| 110 | [d] Microprocessor based generator set monitoring and control system including an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration and diagnostics, LED backlit LCD display with tactile feel soft-switches & generator set status LED lamps, remote START-STOP. |
| 111 | [e] Engine Metering: Oil pressure, engine temperature, starting battery voltage, engine running hours. [f] AC Alternator Metering: L-L voltage and L-N voltage, current (phase and total), KVA (phase and total) and frequency .[g] Engine Protection: Low lube oil pressure, high/low coolant temperature, battery over/under/weak volts, fail to crank/start, sensor failure, cranking lockout, low fuel level. |
| 112 | [h] AC Alternator Protection: Over/under voltage, over/under frequency, loss of AC sensing. [j] Data Logging : Engine hours, control hours and upto 5 recent fault codes. [k] Configurable glow plug control. [l] 24 V DC operation.[n] Mounting Arrangement : Engine and alternator are mounted on a common MS fabricated base frame with AVM pads. [o] Base frame with integral fuel tank is provided with drain plug, air vent, inlet and outlet connection, level indicator and provision for cleaning. |
| 113 | ARBORICULTURESupply and plantation of PALM TREE PLANT with saplings 120cm to 150cm height including excavation of suitable size of pit shall not less than 75 cm dia & 80 cm deep) to accommodate the roots of plants including provn of good earth and treating with farm yard manure in the ration (4:1) fertilizers and pesticides (i.e. Bevation and neem cake BHC 10% linson dust. Thimment or phorate, manures super and vermicompost) and make up the trench area to proper levels for its growth and maintaining for one year from the certified date of completion of work complete all as specified and direcetd |
| 114 | All asper item No 66 above but Ashoka Tree plant saplings 120cm to 150cm height |
| 115 | All asper item No 66 above but Guava Tree plant saplings 120cm to 150cmheight |
| 116 | All asper item No 66 above but Lamon Tree plant saplings 120cm to 150cmheight |
| 117 | All asper item No 66 above but Pomogranate Tree plant saplings 120cm to 150cm height |
| 118 | All asper item No 66 above but Haze Tree plant saplings 90cmheight |
| 119 | All asper item No 66 above but Bogavila Tree plant saplings 90cmheight |
| 120 | All asper item No 66 above but Neem Tree plant saplings 90cmheight |
| 121 | All asper item No 66 above but American Dune Grass |
| 122 | Supply only of Compost manure incl loading unlaoding & transportation & stacking at site complete. The compost shall be of uniform texture relatively dry of dark broen of black color & should have an non offensive earth like odour. It shall be nutrient rich soil like material created by the biolobical decomposition of organic material such as vegetative debris & live stock manure. (Note :-The net measurement of the compost manure shall be arrived at by reducing the actual stack measurement by 8%) |
| 123 | Supply Only following chemical fertilizer |
| 124 | Urea / Ammonium Sulphate |
| 125 | Bone Meal |
| 126 | Potassium Sulphate or Murate of Potash |
| 127 | Supply only insecticide/herbicide of approved make Choropyriphos 35 % EC or Monocrotophos 30 % EC |
| 128 | Supply only of good earth (sand) from outside MD Land free from kankar, stones, cobbles, Moorum, shingle, Rocks building rubbish etc of all kinds & suitable for agriculture/arboriculture purpose. The PH of the soil brought shall be of the range 6 to 8.50 (Note:-The net measurement of the compost mansure shall be arrived at by reducing the actual stack measurements by 20%) |
| 129 | Supply & fixing tree guards 45 cm dia and 1.50 m high fabricated with 3 No. FI (of size 35x3mm at bottom & 25x3 in the middle & top) welded with MS welded mesh of weight not less than 4 Kg/Sqm & 3 legs of 12 mm dia MS bars 400 mm long all as per attached sketch with 02 coats of synthetic enamel paint over a coat of red oxide primer. |
| 130 | NOTE for Sl Item No 66 to 79 :-(i) Height of plant shall be measured from top of follage (not from the isolated branch/ leaf, main stem) to 150mm from top of root.(ii) Water will not be supplied by MES for arboriculture. Contractor has to make his own arrangement for watering to plants and grass. (iii) The rates quoted by the contractor deemed to include watering, maintenance of plants / grass till Two years after certified date of completion of work.(iv). During Two years after completion if any plant / grass is found dead or not of satisfactory growth, plants / grass of approved size and shape shall be provided without any extra cost to the Govt.(v). Supply and application of manure, sweet earth and pesticides, fertilizers etc up to two years after completion are deemed to be included in the quoted unit rate.(vi)In case offailure by the contractor to maintain the plants / grass as above, the same shall be carried out by the department at his Risk and Cost..(vii) The plants shall be brought at site Six months before the date of completion of the work as per Work order. |
| 131 | “Prime Cost Sums (PC)\"Provide Prime Cost sum for Automatic hydraulic type Boom Barrier for Front gate and rear gate including fixed support, pair of photocells with anodised aluminium mounting, LED lighting system with variable flashing, push button Complete all as specified and directed. |
| 132 | NOTE FOR ITEM NO 81.00 :- (1) Prime Cost sum shall be expended wholly or in parts as directed by GE. (2) The full amount of the prime cost sums inserted in the tender documents and the value of the percentage addition thereto quoted by the Contractor to cover all overheads and profit will be deducted from the Contract Sum. (3) The worksunder Prime Cost sum shall be paid at actual prime cost (as defined), plus the percentage addition quoted by contractor to cover all overheads and profit. Contractor shall produce such quotations, invoices and receipted bills as may be necessary to show the actual details of the sums paid by him. (4) The Rate quoted under Prime Cost sum include all proper charges for packing, carriage and delivery to the Site, fixing after deduction of all trade discounts, rebates and allowances. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |