| 1 | SCHEDULE \"A\" Part-I (Building/Structures) (To be quoted by the tenderer) |
| 2 | Item No 01 : Design Structurally and constructionofPhysical training (PT) sheds(Trg Shed (S/S) size - 20.00 mtr x 12.00 mtr x 7.50 mtr), Gp VII(i), RRC Framed structure, add 85% Plinth area,complete all specified in, Soil Bearing Capacity report, design basis report, drawings and tender documents.Note : (a) Necessary arrangement for horizontal and vertical training at 01 locations to be done in all PT shed as per direction of GE.(b) SBC of Soil of Each location of Training Sheds/Blocks Can be different. Bidders are requested to Consider SBC report attached with tender before quoting. |
| 3 | Sch \"A\" Part-II (External Electric Supply)Lump sum price worked out by the contractor for (External Electric Supply) as listed in Schedule \"A\" Part-I against the lump sum price inserted by the MES. |
| 4 | Sch \"A\" Part-III(Area Drainage)Lump sum price worked out by the contractor for (Area Drainage) as listed in Schedule \"A\" Part-III against the lump sum price inserted by the MES. |
| 5 | Sch \"A\" Part-IV(Site Clearance) Lump sum price worked out by the contractor for (Site Clearance)as listed in Schedule \"A\" Part-IV against the lump sum priceinserted by the MES. |
| 6 | Note for Srl No 2 to 6The percentage above / below the SSR -2020 (part-II) rates shall be derived from the amount quoted by the contractor against Srl No. 2 to 6by comparing it with the amount inserted / pre- priced by the department and the same shall be applicable for the items of respective schedule |
| 7 | Schedule \"A\" Part-V (Miscellaneous items of works) |
| 8 | External Electric Supply |
| 9 | Item No 02 : Supply, installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, shutter in front and in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and paintedto both internal and external surfaces with powder coating paint in heatprocess of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and includingfollowing accessories and mounted on PCC Plat form made out of PCC 1:3:6, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed : |
| 10 | BUSBAR :-(i)200 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulatorbus bar support (Square/round) insulators of suitable size and good insulation resistance |
| 11 | INCOMING :- |
| 12 | (i)MCCB 4 Pole63 Amps, 25 KA with Rotary Handle, microprocessor release adjustable amp Ics = 100% Icu as per IEC 60947-2 , Adjustable Over load from 0.5 to 1* In , Adjustable Short Circuit from 2 to 10*Ir , Adjustable Neutral Protection - N, N/2,OFF for 4 Pole MCCB , Inbuilt Thermal Memory- 01 No (in coming) |
| 13 | (ii)Digital Voltmeter 0 - 500 Volt with in built selector switch- 01 No. |
| 14 | (iii)Digital Ammeter0 - 250 Amp with in built selector switch - 01 No. |
| 15 | (iv) Indicator Lamps (LED type) & bakelite fuseshowing R,Y, B phase - 01 set |
| 16 | (v) Digital frequency meter 40-60 Hz - 01 No. |
| 17 | (vi) Copper wound CT with CTR 250/5 - 03 Nos |
| 18 | OUT GOING |
| 19 | (i)MCB 4 Pole 32 Amps with breaking capacity 10 KA at 415 volts- 05 Nos |
| 20 | (ii) Indicator Lamps (LED type) & bakelite fuse showing R,Y, B phase - 04 set |
| 21 | Item No 03 : M&L for earthing complete with galvanised steel plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mts deep below ground level with top edge of the plate not less than 1.50 Mtrs below ground level connected to glavanised ironstrip 25 x 4 mm by means of bolts, nuts check nuts and washers of galvanised iron or steelconnected to earthing test point all as specified incl 40 mm GI tubing medium grade and necessary fitting for protection of GIstrip incl laying of charcoal dust and common salt in alternate layer, PCC Pit (1:3:6) type C-1 using 20 mm graded stone aggregate, RCC cover 40mm thick (1:2:4) type B-0 using 12.5mm graded stone aggregate reinforced with 6 mm dia round bar @ 75mm C/C both ways with MS handle 8mm dia, |
| 22 | plastering 15mm thick CM (1:6) externally upto 150mm below ground level , GI funnel with 20mm dia medium grade GI pipe for watering and wire mesh incl excavation and earth work and disposal of surplus soil complete all as specified and shown on electrical plate No 3 of SSR Part (2009) all as specified an directed. |