Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | CIVIL WORK(A) : |
| 2 | Clearing Grass and removal of Rubbish |
| 3 | Clearing grass and removal of the rubbish up to a distance of 50 m outside the periphery of the area cleared. |
| 4 | Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead up to 50 m and lift up to 1.5m, as directed by Engineer-in-charge. All kinds of soil. |
| 5 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 6 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 7 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:3:6 (1 Cement : 3 coarse sand (zone-III): 6 graded stone aggregate 40 mm nominal size). |
| 8 | Providing and laying RCC (up to Plinth Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :1:1.5:3 (1 cement : 1.5 coarse sand (zone-III): 3 graded stone aggregate 20 mm nominal size) |
| 9 | Providing and laying RCC (Above Plinth).Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing andreinforcement :1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size) |
| 10 | Steel reinforcement for R.C.C. work up to plinth level |
| 11 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete up to plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 12 | Steel reinforcement for R.C.C. work above plinth level |
| 13 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 14 | Centering and Shuttering |
| 15 | Centering and shuttering including strutting, propping etc. and removal of form for: Foundations, footings, bases of columns, etc. for mass concrete. |
| 16 | Centering and Shuttering |
| 17 | Centering and shuttering including strutting, propping etc. and removal of form for: Lintels, beams, plinth beams, girders, bressummers and cantilevers. |
| 18 | Centering and Shuttering |
| 19 | Centering and shuttering including strutting, propping etc. and removal of form for: Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 20 | EPS cement sandwich wall 50mm thick |
| 21 | Providing and fixing in position factory made EPS cement sandwich wall/roof/floor light weight solid core panels made of core material of EPS granule balls/beads (conforming to IS 4671:1984 and shall have density not less than 15kg per cum) adhesive, cement, sand, flyash and other bonding material in mortar state processed to form in a preset mould. The outer face on both sides of the panels will be non asbestos fiber cement board confirming to IS 14862:2000 or Calcium silicate board confirming to EN 14306:2009 of 5mm thick each. Panel shall be laid on 6mm thick cement mortar (1 cement: 2 fine sand) mixed with chemical adhesive of 0.5kg per 50kg of cement or shall be preferably fixed into \"C\" channel made of 1.2mm thick MS plate screwed/fastenened to the slab/column/beam etc. The panel shall fixed vertically with tongue and groove joint and horizontally locked with steel bar between each other and floors and filled with cement mortar and adhesive. Panels should be used as floor & roofing with additional structural support, steel or RCC depending upon the design. All the operation shall be completed in all respect as per drawings, Manufacturers specifications and under the overall direction of Engineer-in-Charge (Cost of all the material is included except \"C channel\" which will be paid separately). Non load bearing panels 50mm thick of required size. |
| 22 | Providing and laying autoclaved aerated |
| 23 | Providing and laying autoclaved aerated cement blocks masonry with 100 mm thick AAC blocks in super structure above plinth level up to floor V level in cement mortar 1:4 (1 cement : 4 coarse sand). The rate includes providing & placing in position 2 Nos. 6mm dia M.S bars at every third course of masonry works. |
| 24 | Brickwork in foundation & plinth |
| 25 | Brickwork with common burnt clay F.P.S (non modular) bricks of class designation 7.5 in foundation & plinth in cement mortar 1:4 (1 cement : 4 coarse sand) |
| 26 | Half brick masonry in superstructure |
| 27 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. Cement mortar 1:4 (1 cement :4 coarse sand) |
| 28 | 12 mm cement plaster |
| 29 | 12 mm cement plaster of mix : 1:4 (1 cement: 4 coarse sand) |
| 30 | 15 mm cement plaster |
| 31 | 15 mm cement plaster on rough side of single or half brick wall of mix: 1:4 (1 cement: 4 coarse sand) |
| 32 | Bricks on flat soling |
| 33 | Providing brick soling in earthen shoulder with stone/best quality jhama brick, sand packed and laid to true line and level and in panel after preparing the subgrade including earthwork in excavation as directed including all labour and materials and if necessary dewatering, complete. Bricks on flat soling. |
| 34 | Cement concrete flooring |
| 35 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. 40 mm thick with 20 mm nominal size stone aggregate. |
| 36 | Ceramic glazed floor tile |
| 37 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement slurry @3.3 kg/sqm including pointing the joints with white cement and matching pigment etc., complete. |
| 38 | Ceramic glazed wall tiles |
| 39 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 40 | Wall putty |
| 41 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 42 | Distemper |
| 43 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade : New work (two or more coats) over and including water thinable priming coat with cement primer |
| 44 | Cement paint |
| 45 | Finishing walls with water proofing cement paint of required shade : New work (Two or more coats applied @ 3.84 kg/10 sqm) |
| 46 | Structural Steel work |
| 47 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 48 | Steel work in built up tubular |
| 49 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes. |
| 50 | Enamel paint |
| 51 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade :Two or more coats on new work |
| 52 | T-iron frames for doors |
| 53 | Providing and fixing T-iron frames for doors, windows and ventilators of mild steel Tee-sections, joints mitred and welded, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block. |
| 54 | Flush door shutter |
| 55 | Providing and fixing ISI marked flush door shutters conforming to IS :2202 (Part I) nondecorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both aces of shutters: 30 mm thick including ISI marked Stainless Steel butt hinges with necessary screws. |
| 56 | Providing vision panel |
| 57 | Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured): Rectangular or square. |
| 58 | Aluminium sheet 0.8 mm thick |
| 59 | Providing & fixing GI/Aluminium Sheet (0.8 mm thick) |
| 60 | Aluminium work for windows & ventilators |
| 61 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately). For fixed portion. Anodised aluminium (anodised transparent or dyed to required shade according to IS:1868, Minimum anodic coating of grade AC 15) |
| 62 | Aluminium work for windows & ventilators |
| 63 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately). For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately). Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15) |
| 64 | Glazing in aluminium window & ventilator |
| 65 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 4.0 mm thickness (weight not less than 10kg/sqm) |
| 66 | Frosted glass |
| 67 | Extra for providing frosted glass panes 4 mm thick instead of ordinary float glass panes 4 mm thick in doors, windows and clerestory window shutters. (Area of opening for glass panes excluding portion inside rebate shall be measured). |
| 68 | Aluminium grill |
| 69 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only weight of grill to be measured for payment). |
| 70 | Fly proof wire gauge |
| 71 | Fly proof stainless steel grade 304 wire gauge with 0.5 mm dia. wire and 1.4mm wide aperture with matching wood beading. |
| 72 | Aluminium handle 125 mm |
| 73 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete : 125 mm |
| 74 | Aluminium handle 75 mm |
| 75 | Providing and fixing aluminium handles, ISI marked, anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete : 75 mm |
| 76 | Aluminium tower bolt 250x10 mm |
| 77 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete :250x10 mm. |
| 78 | Aluminium tower bolt 150x10 mm |
| 79 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete :150x10 mm. |
| 80 | Aluminium sliding door bolt 300x16 mm20 |
| 81 | Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868),transparent or dyed to required colour or shade, with nuts and screws etc. complete :300x16 mm. |
| 82 | Wood work in frames |
| 83 | Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia. & length (hold fast lugs or dash fastener shall be paid for separately). Second class teak wood. |
| 84 | 18mm thick Pre-laminated particle board |
| 85 | Providing and fixing 18mm thick both sides Pre-laminated cement bonded wood particle board as per IS : 15786:2008 of approved brand and shade with suitable full threaded steel screws etc. in partitions, boxes, shelves, racks and cupboard, kitchen cabinet under kitchen counter etc. all complete as per direction of Engineer-in-charge (Note: Fittings to be paid separately). 18 mm thick |
| 86 | Cupboard lock |
| 87 | Providing and fixing special quality chromium plated brass cupboard locks with six levers of approved quality including necessary screws etc. complete. Size 75 mm |
| 88 | M.S. Piano hinges |
| 89 | Providing M.S. Piano hinges ISI marked IS : 3818 finished with nickel plating and fixing with necessary screws etc., complete. Overall width 50 mm. |
| 90 | False Ceiling |
| 91 | Providing and fixing flat pressed 3 layer medium density particle board or graded particle board (Grade I) IS: 3087 marked, in ceiling with necessary nails etc. complete (frame work to be paid separately):12 mm thick |
| 92 | Precoated sheet |
| 93 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length up to 12 metre or as desired by Engineer- in-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete up to any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 94 | Precoated sheet roofing accessories |
| 95 | Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+0.05 %) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screws complete:Ridges plain (500 - 600mm). |
| 96 | 12mm thick ply (berge board) |
| 97 | Providing and fixing plain lining with necessary screws/nuts & bolts/nails, including a coat of approved primer on one face, and fixed on wooden /steel frame work,complete as per direction of Engineer-in-charge (Frame work shall be paid for separately). 12mm thick commercial ply conforming to IS : 1328 BWR type. |
| 98 | Tubewell 100 mm diameter |
| 99 | Boring with 100 mm diameter casing pipe for hand pump / tubewell, in all soils except ordinary hard rocks requiring blasting, including removing the casing pipe after the hand pump / tube well is lowered and tested : Beyond 12 m and up to 18 m depth. |
| 100 | U-PVC pipe working pressure 4 kg / cm² |
| 101 | Providing U-PVC pipes (working pressure 4 kg / cm²) Single socketed pipe 110 mm dia. |
| 102 | Polyethylene water storage tank |
| 103 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 104 | CPVC pipe 100mm dia |
| 105 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work 100mm nominal dia. Pipes. |
| 106 | CPVC pipe 80mm dia |
| 107 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work 80mm nominal dia. Pipes. |
| 108 | CPVC pipe 50mm dia |
| 109 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work 50mm nominal dia. Pipes. |
| 110 | CPVC pipe 32mm dia |
| 111 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work 32mm nominal dia. Pipes. |
| 112 | CPVC pipe 25mm dia |
| 113 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work 25mm nominal dia. Pipes. |
| 114 | CPVC pipe 20mm dia |
| 115 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction ofEngineer in Charge. Concealed work, including cutting chases and making good the walls etc. 20 mm nominal dia. Pipes. |
| 116 | UPVC 110mm dia pipe |
| 117 | Providing and fixing on wall face unplasticized Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm diameter. |
| 118 | UPVC 75mm dia pipe |
| 119 | Providing and fixing on wall face unplasticized Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 75 mm diameter. |
| 120 | C.I. cover for manhole |
| 121 | Supplying and fixing C.I. cover without frame for manholes: 500 mm diameter C.I. cover (medium duty) the weight of the cover to be not less than 58 kg. |
| 122 | RCC pipe 150mm dia |
| 123 | Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 150 mm dia. |
| 124 | Floor trap |
| 125 | Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors: 100 mm inlet and 100 mm outlet. Sand cast iron S&S as per IS: 3989. |
| 126 | Nahani grating |
| 127 | Providing & fixing of nahani grating 100 mm dia. |
| 128 | Valve 32mm NB |
| 129 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end): 32 mm nominal bore. WO number/date4300081242-/05.12.2023. |
| 130 | Valve 25mm NB |
| 131 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end): 25 mm nominal bore. |
| 132 | Valve 20mm NB |
| 133 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end): 20 mm nominal bore. |
| 134 | Indian type W.C. pan |
| 135 | Providing and fixing water closet squatting pan (Indian type W.C.pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests. |
| 136 | European type W.C. pan |
| 137 | Providing and fixing white vitreous china pedestal type water closet (European type W.C.pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required : W.C. pan with ISI marked white solid plastic seat and lid. |
| 138 | Half stall urinal |
| 139 | Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm with white PVC automatic flushing cistern, with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS : 2556, C.I.trap with outlet grating and other couplings in C.P. brass, including painting of fittings and cutting and making good the walls and floors wherever required : Single half stall urinal with 5 litre P.V.C. automatic flushing cistern. |
| 140 | Wash basin |
| 141 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tap. |
| 142 | Kitchen sink |
| 143 | Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required : Kitchen sink with drain board, 510x1040 mm bowl depth 225 mm. |
| 144 | Anagle valve |
| 145 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931: 15mm nominal bore. |
| 146 | Towel Rail |
| 147 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. 600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighing not less than 190 gms. |
| 148 | Bib cock |
| 149 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690gms. 15 mm nominal bore |
| 150 | Shower rose |
| 151 | Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet :100 mm diameter. |
| 152 | Soap Dish |
| 153 | Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106gms. |
| 154 | Mirror |
| 155 | Providing & fixing rectangular shape 453x357 mm Mirror with Plastic moulded frame. |
| 156 | 600mm dia RCC pipe NP2 |
| 157 | Providing and laying reinforced cement concrete pipe NP3 for culverts on first class bedding of granular material in single row including fixing collar with cement mortar 1:2 but excluding excavation, protection works, backfilling, concrete and masonry works in head walls and parapets Clause 1106. 600 mm dia. |
| 158 | Interlocking Concrete Block 80mm thick |
| 159 | Providing and laying of inter locking concrete block pavement (ICBP) with cement concrete paver blocks as per IS 15658-2006 of thickness 80mm and of specific 28 days compressive strength over a layer of bedding sand of compacted thickness 30mm, laid either in stretcher/running/ herringbone pattern of bonds as directed bythe engineer in charge and in proper level and grade and compacted with appropriate equipment such as plate vibrator along with spreading of a thin layer of joint filling sand to fill up the gaps between blocks including construction of edge restraint wherever required complete as per drawing and technical specification clause 1504 of MORD. |
| 160 | 1.8 metres high GI barbed wire fencing |
| 161 | Providing and fixing 1.8 metres high GI barbed wire fencing with 2.4 m angle iron posts 50 mm x 50 mm x 6 mm placed every 3 metres center to center founded in M15 grade cement concrete, 0.6 metre below ground level,every 15th piost, last but one end post and corner post shall be strutted on both sides and end post on one side only and provided with 12 horizontal lines and 2 digonals interwoven with horizontal wiers, fixed with GI staples, turn buckles etc complete as per clause 807. |
| 162 | ELECTRICAL WORKS (B): |
| 163 | LT Power cable; 3.5Cx150 sqmm |
| 164 | Supply of 10 SWG GI Wire as per relevant IS standard |
| 165 | \"Supply of 3.5CX50 sq mm LV Power Cable \"Supply of 1.1 kV Grade, 3.5C X 50 sq mm LV Power CableAl conductor, XLPE insulated, Extruded PVC inner sheathed, armoured and FRLS PVC outer sheathed power cable \" as per relevant IS standard |
| 166 | Supply of 1.1 kV Grade, 4C x 10 sq mm LV Power CableCU conductor, XLPE insulated, Extruded PVC inner sheathed, armoured and FRLS PVC outer sheathed power cable as per the attached data sheet of cables as per relevant IS standard |
| 167 | \"Supply of 1.1 kV Grade, 3C x 2.5 sq mm LV Power Cable CU conductor, XLPE insulated, Extruded PVC inner sheathed,armoured and FRLS PVC outer sheathed power cable\"as per relevant IS standard |
| 168 | \"Supply of LED Tube light 1. Wattage : 18W - 20W2. Operating Voltage range : 220-240V, 50 Hz AC System3. Length of tube including pin : 1200mm4. Type of lamp cap : G13 made of polycarbonate5. Make : Philips/Havells/CGL/Bajaj or eqv. |
| 169 | \"Supply, Installation, Testing and commissioning - 160A Feeder PillarFeeder pillars with Thermoplastic Polycarbonate insulated enclosure materials with enclosure protection of IP55 and with canopy, suitable for Outdoor installation. Feeder pillars should be Modular / combinable, Floor Mounting according to IEC 60529, protection class II, totally insulated, having internally embedded gasket, flame retardant, self-extinguishing with glow wire test at 960C according to IEC 60 695-2-11. Impact strength IK 08 (5 Joule) in accordance with DIN EN 50102. All MCCBs with O/C, S/C, E/F release (Microprocessor Based) and shunt trip for earth leakage protection.# 160A MCCB (50KA) as Incomer Breaker.# 4 Nos 125A MCCB, 3 Nos 63A MCCB, 2 Nos 32A MCCB (timer controlled) outgoing feeders# Supply shall include commissioning spares as required(List shall be provided by bidder)Feeder pillar panels shall comply the following requirement : The Thermoplastic enclosure manufacturer and the Panel manufacturer should be same.# With the OEM authorization, they should confirm that they will make the FRP / thermoplastic Panels & the Guarantee,Warranty; Servicing should be taken care by them only. #Feeder Pillar Panels should be in accordance with IEC 61439-1 &2.# The OEM of board / panel shall submit #Type test report” (ASTA certification\" by CPRI) for the offered board made of FRP OR Polycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following type tests performed and passed out satisfactorily : # Temperature Rise. # Dielectric Properties. # Short circuit withstand current # Rated peak & short time withstand current and Rated Conditional Short Circuit Current. # Degree of Protection.# Clearance & Creepage Distance. # Mechanical Operation # Effectiveness of Protective Circuits # The Panels should have padlock facility for security point of view.# Routine Test Certificate should be from OEM only and submit according to IEC 61439-1 & 2 along with Panel.Technical Data Sheet (TDS) of Feeder Pillar panel to be submitted alongwith the bid.(make Hensel or equivalent) |
| 170 | SITC Fabrication and installation of of 150 mm dia, class B, GI pipes/ sleeves for cable protection, fixed on steel, concrete or similar structure, in trenches, ready to be buried inconcrete including cutting, bending, grinding, threading and similar works, supply & fixing of required GI fastners, clamps,small iron structures, spacers, cleats, plug, bushings, sealing compound/ material etc., cutting and remaking of concretesurface including supply of civil material, all labour and materials complete as per approved drawings, specification of this tender and directions of Engineer-in-charge. |
| 171 | \"SUPPLY AND INSTALLATION OF ANCHOR BOLTS\"\"Fabricating,supplying and installing thread Anchor Bolts of specified diameter conforming to IS 2062 Grade BR as per drawings, including the cost of M.S. rounds and plates, nuts, washers , anchor plates, fine plates, stiffness, pipes sleeves etc, material as per relevant IS codes, fixing in position withnecessary, tools, templates, labour etc for all heights and depths, all complete. Materials to be supplied as per approved vendor lists attached with special conditions of contract |
| 172 | \"Making horizontal bore under the WBM etc. of the roads: making horizontal bore under the WBM of the roads etc., manually or by machinefor laying upto 150 mmNB GI/RCC pipes,excavating the side approach to facilitate boring,backfilling the same after completion of works including supply of tools,tackles and equipments etc. personal protective equipments to complete the job as required ,excluding the supply of GI pipes and as per direction Engineer-in-Charge. |
| 173 | \"Cross linked fencing works Preparation of fencing around the periphery of panelsincluding supply of all materials,labour and as per direction of Engineer-in-Charge\" |
| 174 | Supplying and fixing following way surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet, dust protected, duly powder painted, inclusive of 200 As tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB\"s (but within MCB\"S and incomer ) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (4+24), Double door. |
| 175 | Supplying and fixing of following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existingVTPN DBl making connections etc. as required. 100A 4P MCCB,25 KA with all accessories as required as per site condition and site requirement |
| 176 | Supplying and fixing following way, horizontal type three pole and neutral, sheetsteel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, interconnections, powderpainted including earthing etc. as required.(But without MCB/RCCB/Isolator)4 way (4+12), double door. |
| 177 | Supplying and fixing 5A to 32 As rating, 240/415 volts, 10kA, \"C\"curve,miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required single pole. |
| 178 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts,40A residual current circuit breaker (RCCB), having a sensitivity current 300 mA in the extisting MCB DB complete with connections, testing and commissioning etc. as required . |
| 179 | Supply Fixing of of 3P MCB 63A #C” curve, 10 kA breaking capacity,Utilisation category A, Make : Legrand/Havells/Schneider or equivalent and as per thedirection of E-I-C. |
| 180 | Wiring for light point / fan point /exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC Conduit, with modular switch,modular plate ,suitable GI Box and earthing the 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C (including supply of all material) |
| 181 | Wiring forcircuit/submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required 2X2.5sq.mm + 1X2.5sq.mm earth wire including supply all material as required |
| 182 | Wiring forcircuit/submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required 2X4sq.mm + 1X4sq.mm earth wire including supply all material as required |
| 183 | Wiring forcircuit/submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required 2X6sq.mm + 1X6sq.mm earth wire. |
| 184 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 185 | Supplying of 300 mm 900 RPM exhaust fan complete with louver and bird guard screen with 3 core flexible wire as required. |
| 186 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess,including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch connection etc. as required |
| 187 | Supplying and fixing suitable size GI box with modular plate and cover in FRLS on surface or in recess,Including providing and fixing 6 pin 5/6 & 15/16A modular socket outlet and 15/16A modular switch, connection etc. as required. |
| 188 | \"Cable termination LT upto 40mmTermination of cable havingouter diameter upto 40mm; CABLE TERMINATION : (Commonspecification for this & same category of items below):Termination of armoured power cables (Typically PVC/XLPE insulated up to 1100 V grade). Job includes earthing the cable armour, connecting to the terminals, supply and marking of upto 1100V 3/3.5/ 4 core of size wire number ferrules/ cable tags(ss/ aluminium/ lead strip minimum 2 mm thick and 20 mm wide at the termination point), drilling in equipment,removal, cutting, fixing of gland plate, fixing of cable glands, supply and fixing of PVC shrouds for outdoor terminations, cutting and stripping of cable insulation, crimping the lug on to the conductor, clamping of the cable-cores, consumable items like Crimping paste, insulation Tapes, Including Supply of cable WP GLAND and LUGS etc complete, including all labour and materials complete, as per approved drawings, specifications of this tender and directions of EIC. \" |
| 189 | \"Cable termination LT above 40mm Termination of cable having outer diameter above 40mm; CABLE TERMINATION : (Common specification for this & same category of items below):Termination of armoured power cables (Typically PVC/XLPE insulated up to 1100 V grade). Job includes earthing the cable armour, connecting to the terminals, supply and marking of upto 1100V 3/3.5/ 4 core of size wire number ferrules/ cable tags(ss/ aluminium/ lead strip minimum 2 mm thick and 20 mm wide at the termination point), drilling in equipment, removal,cutting, fixing of gland plate, fixing of cable glands, supply and fixing of PVC shrouds for outdoor terminations, cutting and stripping of cable insulation, crimping the lug on to the conductor, clamping of the cable-cores, consumable items like Crimping paste, insulation Tapes, Incliding Supply of cable WPGLAND and LUGS etc complete, including all labour and materials complete, as per approved drawings, specifications of this tender and directions of EIC. \" |
| 190 | \"Lettering and Stenciling of Letter\"\"Lettering and Stenciling of 32 mm height including supply of approved colour of Paint/Paints , painting of tag number of Electrical equipments as specified in specification & by Engineer -In-Charge.Supply of various types of paints, primers, preparation of surfaces by manual, hand tool cleaning, power tool cleaning and application of primer and finish paints for equipments surfaces/concrete surfaces, identification (Equipment name) lettering, stenciling,colour bands, colour coding etc as specified including rubdown and touch up of shop primer wherever required, providing scaffolding at all elevations, various locations, labour, materials, tools & tackles, consumables, safety, PPE\"s, supervision, etc. to complete the work in all respect as per the Painting Specifications drawings, and direction & full satisfaction of owner\"s/engineer in charge for all types of equipment as specified in the Painting specifications:\" |
| 191 | \"Supply, Fabr. and inst. of steel Supply, Fabrication and installation of various sizes steel for supports, brackets for miscellaneous electrical equipment, base frames, support for switchgear, supports for outdoor lighting fixtures, hangers, risers, clamps etc. for miscellaneous electrical equipment /items, cable and cable tray supports with rolled MS sections, pipes, plates, strip etc., including shot blasting, welding, bolting,rivetting,supply of necessary anchor bolts and grouting etc. Including surface finish, painting with one coat of 60 micron DFT of inorganic zinc silicate primer, 1 coat of 100 micron Two pack Epoxy HB Poly amide cured, including breaking walls, floors etc. for structures as required,including supply of all G.I hardware materials, including all labour and materials, complete as per approved drawings, specification of this tender and directions of Engineer-In-charge. Any item weighing up to 1 kg or less shall neither be measured nor paid.\" |
| 192 | Supply and makingof heat shrinkable Straight Through cable jointing kit for 3/3.5/4 Core LT cables ( 1.1KV ) of size: 70 to 150 Sq.mm, Make: Raychem RPG/3M or equivalent, and as per the direction of E-I-C. |
| 193 | Laying, clamping and connecting of 8/10 SWG GI Wire for main earth grid/earthing network under ground, along structure, cable trays, racks walls, roofs, in trench etc. including excavation and filling of earth, chipping and remaking of concrete surface, supply and fixing of GI clamps, Supply of fixing GI fastners at earth plate & at equipment end wherever required. Supply & applying bitumin paint & hessian tape on underground joints & cold zinc spray on aboveground joints. Earthing to be carreid out as per IS:3043 It also includes any modification work because of fouling with under ground/above ground piping. |
| 194 | Supply,Erection ,Testing and Commissioning of Earthing with G.I. earth pipe 4.5 metre long, 40 mm diaincluding accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 195 | Supply and spreading of approved fine river sand in cable trenches including all labour and materials complete as per specifications and direction of Engineer- in-charge. |
| 196 | Supply, fabrication and installation of canopies for miscellaneous outdoor equipment like motors, fire alarm points, telephones, communication hand set stations etc. to render them weatherproof made out of 1.6 mm (16 gauge) sheet steel including supply of hardware and paint, painting, including all labour and materials, as per approved drawings, specifications of this tender and directions of Engineer-in-Charge. |
| 197 | Supply and laying of approved second class bricks of thickness 3\" in cable trenches for cable protection including all labour and materials complete as per specifications and direction of Engineer- in-charge.(Actual area of laid brick surfaces shall be measured) |
| 198 | Supplying and fixing following modular base & cover plate on existing modular metal boxes etc. as required 6Module |
| 199 | Installation, testing and commissioning of wall bracket /celling fittings of all sizes and shapes containg upto two GLS/CFL/LED/Flood light per fitting,complete with all accessories including connection etc.as required. |
| 200 | Installation, testing and commissioning of pre-wired, fluorescent fitting /compant fluorescent fitting of all types, complete with all accessories and tube etc.directly on celling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 201 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc.as required upto 450 mm sweep. |
| 202 | \"Cable laying OD upto 40 mm Laying of cables with outer diameter upto 40 mm. LAYING CABLE : (Common specification for this & same category of items below) : Laying, testing and commissioning of following sizes LV, MV & HV Cables and sealed properly of upto /3.5/ 4 of size PVC caps in designated cable route (in built-up readymade trenches; overhead cable trays; pull through pipes; exposed on wall/ beam/ rakes/ trusses tie/beam/ embedded in floor or buried directly underground; or through G.I.pipe ). Cables shall be PVC/XLPE insulated; PVC Sheathed; FRLS armoured Aluminium/ Copper Cables or similar types as per IS:1554 (PART-I), IS 7098 PART I & IS 1225-latest version.;Unit rates quoted for installation of cables shall besame irrespective of route and method of laying. The item shall include laying, pulling of cables, proper dressing of cables on cable trays, racks, vertical raceways etc. and supply and installation of saddles, spacers and nylon chord for tying as required, stainless steel/aluminium/lead strip identification tags at strategic points/ every 50 meter intervals, aluminium clamps. etc. The straight through Jointings/ tying of upto1100V 3/3.5/ 4 core of size armour in the cables should be avoided/ minimised. (Structural steel, tray, pipe, excavation,sand and bricks shall be paid under separate item of BOQ).Item includes transportation from store/yard to site at the place of installation, unpacking, including all labour and materials.Empty drums and excess cable to be rerolled and transported back to desigated store/yard. |
| 203 | \"Laying of cables with outer diameter above 40 mm. LAYING CABLE : (Common specification for this & same category of items below) : Laying, testing and commissioning of following sizes LV, MV & HV Cables and sealed properly of upto /3.5/ 4 of size PVC caps in designated cable route (in built-up readymade trenches; overhead cable trays; pull through pipes; exposed on wall/ beam/ rakes/ trusses tie/ beam/ embedded in floor or buried directly underground; or through G.I.pipe ). Cables shall be PVC/XLPE insulated; PVC Sheathed; FRLS armoured Aluminium/ Copper Cables or similar types as per IS:1554 (PART-I), IS 7098 PART I & IS 1225-latest version.;Unit rates quoted for installation of cables shall be same irrespective of route and method of laying. The item shall include laying, pulling of cables, proper dressing of cables on cable trays, racks, vertical raceways etc. and supply and installation of saddles, spacers and nylon chord for tying as required,stainless steel/aluminium/lead strip identification tags at strategic points/ every 50 meter intervals, aluminium clamps. etc. The straight through Jointings/ tying of upto 1100V 3/3.5/ 4 core of size armour in the cables should be avoided/ minimised. (Structural steel, tray, pipe, excavation, sand and bricks shall be paid under separate item of BOQ).Item includes transportation from store/yard to site at the place of installation, unpacking, including all labour and materials.Empty drums and excess cable to be rerolled |
| 204 | SITC of Solar Street Light along with lighting pole Solar LED Street Light :Solar LED Street Light : Supply, installation, testing and commissioning of All In One Solar Street Light street lighting of wattage - 60W LED, complete with all necessary accessories suitable for 2 days autonomy including solar PV panel Monocrystalline type 90 Wp +/_ 10%, Lithium Ferro Phosphate Battery 12.8V 42 Ah , Efficiency >90%, System Lumen Efficacy 150 Lumen/W , MPPT charge controller 12V , 7A ,LED Make OSRAM/Cree/ Equivalent with Life span of 50000 Hours , Inbuilt DC Type Driver, Aluminium Extruded Body with OEM Logo, battery casing with IP 65 protection, Dusk to Dawn Operation provided along with intelligent dimming profile, with necessary protections like i. Over charged Protection , ii. Deep Discharge protection , iii. Over current protection iii. Short Circuit Protection ,v. Overvoltage Projection as required mounting brackets, , etc. with LED display to indicate the charging status of battery , , automatic ON-OFF system and other accessories and systems complete, brackets and supports,mounting clamps, necessary cabling, wiring and conduiting etc. as may be required. Make - Bajaj, CG, Philips, HAVELLS, GE, equivalent as approved by E-I-C.Supply, Erection, Testing and commissioning of 9 Meter Height Hot dip Galvanised Octagonal Street Lighting Pole of Single ARM including four nos foundation Anchor bolts and accessories. The lighting pole shall be bolted on a pre-cast foundation with a set of four Foundation bolts for greater rigidity.Supply, Installation, earthing,glanding, termination of incoming and outgoing cables/ wires at luminaire , testing and commissioning of lighting luminaires (including junction box) and other accessories suitable for outdoor installation. This shall include transportation from owner\"s issue point to actual place of installation by contractor\"s own lifting & transporting arrangement, unpacking, assembly of luminaries, drilling etc. as required, all labour and material complete as per drawings, specification of this tender and directions of Engineer-in-charge. Following Site Conditions will be considered for design and installation of 9 meter height Single ARM Octagonal Street Lighting Pole:# Maximum Ambient temperature : 38 Deg C# Minimum Ambient temperature : 5 Deg C# Equipment design temperature : 40 Deg C#Earthquake Design factor:(Code IS-1893 Zone-V/Site spectra whichever is governing), As per IS 1893,Seismic factor = 0.36# Wind speed : 50 meter / sec# Site Altitude : 90 m above MSL# Relative humidity : 85% at 3 Deg C#Environmental conditions : Corrosive Industrial Environment / Extreme Moisture (Tropical Climate)The Lighting Pole will comply the following specification as minimum, but not limited to the following :# Poles shall be bolted on a pre-cast foundation with a set of four Foundation bolts for greater rigidity.# The pole shaft shall be made from sheet steel .# The pole shaft shall have tubular / octagonal cross section and shall be continuously tapered with single longitudinal welding.There shall not be any circumferential welding.( Item is inclusive of excavation and backfilling, RCC work, accessories etc. completewith all associated works).Technical Data Sheet (TDS) of lighting pole, lighting fixtures to be submitted alongwith the bid. |
| 205 | \"Supply and installation of cable markers Supply and installation of cable markers for buried HV/MV cable at a regular interval , at every bend & at every cable joint location, supply of associated materials including engraving \"\"BURIED ELECTRIC CABLES HT/LT\"\" complete with support and foundation, painting as per approved drawing, specification of this tender and directions of Engineer-in-charge. This includes supply & installation of all necessary consumables, GI hardwares |
| 206 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts,washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 207 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 208 | Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. |
| 209 | Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. |
| 210 | Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A 415 V \"C\" curve DP MCB complete with connections, testing and commissioningetc. as required. |
| 211 | Supply installation testing comissioning of 3 KVA/12960 VAH5 Star Sine Wave Inverter with battery and trolly for mounting conforming to following technical specification : Technology- IGBT-PWM, Type of Battery- Tubular battery confirming to IS:13369 Backup time (Minutes)-Minimum 180 MinutesSpecification :(1)Rating of Inverter-3KVA(2)Inverter shall be designed for standard frequency of 50 Hz.(3)Min VAH of Battery-8640 VAH(4)Technology-IGBT-PWM(5)Battery Type: Tubular Battery Conforming to IS:13369(6)Inverter shall incorporate an arrangement for automatic change over of load from mains supply to the inverter ac output in case of failure of mains supply,with corresponding indication.(7)On/Off switch conforming to IS 3854 and a pilot lamp to indicate that the ac output is ON.(8)Fast acting fuses in the DC input circuit and rewirable type slide lock fuses conforming to IS 2086:1982 in the acoutput circuits(Alternatively,suitable glass cartidge fuse may be used on ac side)(9)An earthing terminal on the outside of the inverter.(10)Protection against: (a)Pole reversal of dc input, (b)Under voltage of dc input (c)Overload of ac output(11)Visual and Audible indication for conditions (a) & (c) above.(12)Ambient temperature: -10 deg celcius to 45 deg celcius(13)Efficiency: >80% (14)Harmonic content in output supply: (a) Total harmonics: 5% (b)Single harmonics: 3% (15)Input: Single Phase sine wave(120 to 260 V)(16)Output :Single Phase sine wave 240 V (17)Overload Time (in Minutes) >/=10 (18)Overload of rated load (in %) >/=10(19)Battery cut-off-voltage to protect from overdischarge (in Volt) >10.5 (20)Degree of protection: IP 21(21)Inverter Governing specication Generally conforming to IS:13314 (22)Battery should be Maintenance Free(Tubular Type) (23)Thickness of sheet for trolley (in mm) minimum 1.2(24)Thickness of sheet for trolley (in mm) minimum 1.2 Trolley Material CRCA Steel Type of enclosure CRCA Steel |
| 212 | Supplying,i nstallation, testing and comissioning of Astronomical time switch with suitable contactor and accessories of following configuration to be mounted in feeder pillars/ Lighting DBs for automatic switching ON & OFF of street lights at sun set & sun rise or twilight(Auto ON,Auto OFF ,Auto modes ) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required. 1 output per phase and suitable for single phase supply. |
| 213 | Supply and installation of polycarbonate weather proof junction boxes for outdoor installation having dimension of 155mm x 210mm x 92mm with IP67 and IK09,alongwith and 2P MCB including knockouts for cable entry and suitable terminal blocks mounted in DIN rail for termination of 3.5C x 16 sq.mm Al cable size. The junction box will be supplied with minimum 2nos PVC glands with locknut threads in each junction box. The junction box shall be weather proof,protected against rainwater, temperature resistant, impact resistant,flame retardant.The junction boxes shall be equipped with top canopy.Cable entry will be from bottom only.Junction box colour: Black. Make: Hensel or equivalent. |
| 214 | Supply and installation of CO2 Fire Extinguishers (5 kg) including the supply of necessary clamps, bolts, rawl plugs etc., breaking and making good of walls, if required, mounting, including all labour and materials, complete and as per applicable latest Indian standards, CEA regulations and as per directions of Engineer-in-charge. |
| 215 | Supply and laying of 1000 mm wide safety insulating Rubber Mat suitable for 415V System 1.1 KV Voltage graderequired for maintenance of electrical equipment in substation, including cutting to required shape in running length, including all labour and materials, as per applicable latest Indian or International standards, CEA regulations and as per directions of Engineer-in-charge |
| 216 | Supply and installation of Shock hazard charts printing with three (3) language ie. English, Hindi & Assamese complete with aluminium frame and glass including the supply of necessary clamps, bolts, rawl plugs etc., breaking and making good of walls, if required, mounting, including all labour and materials, complete and as per applicable latest Indian standards, CEA regulations and as per directions of Engineer-in-charge. |
| 217 | Supply and installation of Enamelled caution boards printing with three (3) language ie. English, Hindi & Assamese including the supply of necessary clamps, bolts, rawl plugs etc., breaking and making good of walls, if required, mounting, including all labour and materials, complete and as per applicable latest Indian standards, CEA regulations and as perdirections of Engineer-in-charge. |
| 218 | Supplyof 200W Flood light luminaires with required accessories IP 66, IK08, electronic potted driver,toughened glass with minimum 4mm thickness ,lower THD,Output open/short circuit protection,over voltage protection ,surge voltage protection upto 10 KV with SPD & other safety test as per IS 15885 part-2 |
| 219 | SITC of High Mast Lighting : |
| 220 | Supply, Installation, earthing, glanding, termination of incoming and outgoing cables/wires at luminaire , testing and commissioning of lighting luminaires and other accessories suitable for outdoor installation. This shall include transportation from owner\"s issue point to actual place of installation by contractor\"s own lifting & transporting arrangement, unpacking, assembly of luminaries, drilling etc. as required, all labour and material complete as per drawings, specification of this tender and directions of Engineer-in-charge. This will include any modifications required to be carried out on the mounting bracket to suit mounting of lighting fixtures & any modifications required for proper commissioning of fixture.Following Site Conditions will be considered for design and installation of 30 meter heigh High Mast : |
| 221 | # Maximum Ambient temperature : 38 Deg C# Minimum Ambient temperature : 5 Deg C# Equipment design temperature : 40 Deg C# Earthquake Design factor : (Code IS-1893 Zone-V/Site spectra whichever is governing), As per IS 1893,Seismic factor = 0.36# Wind speed : 50 meter / sec# Site Altitude : 90 m above MSL# Relative humidity : 85% at 3 Deg C# Environmental conditions : Corrosive Industrial Environment / Extreme Moisture (Tropical Climate) The High Mast shall be comply the flowing codes and standards as minimum, but not limited to the following :#PLG 7 High Masts for Lighting and CCTV#SANS 10225:2012 High Mast natural frequency calculation#IS 875 Part # 3 Wind Loading#IS 2062/ BS EN 10025 High Tensile Steel Sheets#IS 2062 Mild Steel#BS EN ISO 1461 Galvanization#IS 3459 / 2266 Stainless steel Wire rope#IS 9968 Part # 1 Trailing Cable#IS 12615 Motor#IP66, IK08, wind tunnel test on a specimen to establish the force coefficients of the 20-side polygon and the value received from the wind tunnel test is to be taken in Design. |
| 222 | The winches are to be type tested through reputed institutions like IIT asconsultants. 30 Meter High Mast with 12x400W LED Lighting fixtures comprising of the following as a minimum :# 30 Meter High Mast shaft in three sections suitable for required wind speed with raising / lowering system comprising of frame for luminaries carriage suitable to install 12 nos luminaries in symmetrical arrangement, SS Wire rope, trailing cable, motor, manual handle, junction box, lightning protections including lighting finile and all other accessories required for the complete installation of the High Mast.# GI Anchor Foundation bolts as per Civil drawing along with nuts, washers, anchor plates and templates# Non-integral flood light luminaries of 400W LED Fixtures with control gear boxes# Two nos. aviation obstruction lights with 9W LED Lamps# Outdoor stand mounted weatherproof (IP-55) MCB DB/ weather proof Feeder (IP-55) pillar distribution box with Incomer / outgoing MCB, ELCB,Temp. Class T3.# Trailing cables, wires as required (except the incoming power cables to Feeder Pillar Box / MCB Distribution Box).# Supply shall include commissioning spares as required (List shall be provided by bidder). Technical Data Sheet (TDS) of the mast, lighting fixtures, outdoor lighting panel, trailing cables to be submitted along with the bid. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
| 7 | Click here to download tender document | Tender Documents |
| 8 | Click here to download tender document | Tender Documents |
| 9 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy