| 1 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLSPVC insulated copper conductor single core cable etc. as required. |
| 2 | Group C |
| 3 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 4 | Group C |
| 5 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel / PVC conduit as required. |
| 6 | 3 x 1.5 sq.mm |
| 7 | 3 x 2.5 sq.mm |
| 8 | 3 x 4 sq.mm |
| 9 | 3 x 6 sq.mm |
| 10 | Supplying and fixing following size/modules GI box along with modular base and cover plate for modular switches in recess etc as reqd. |
| 11 | 1 or 2 Module (75mmX75mm) |
| 12 | 3 Module (100mmX75mm) |
| 13 | 6 Module (200mmX75mm) |
| 14 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 15 | 5/6 amps switch |
| 16 | 3 pin 5/6 amps socket outlet |
| 17 | 15 /16 amps switch |
| 18 | 6 pin 15/16 amp socket outlet |
| 19 | Supplying and fixing of Heavy duty PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 20 | 20 mm dia |
| 21 | 25 mm dia |
| 22 | Supplying and fixing suitable size G.I. box with modular plate and cover in front or in recess including providing and fixing 25A modular socket outlet and 25A modular SP MCB \"C\" curve including connections, painting etc. as required. |
| 23 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 24 | Supplying and fixing 2 module stepped type fan regulator on the existing modular plate switch box including connections but excluding modular plate etc as reqd. |
| 25 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 26 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 27 | Supply and fixing of 25mm x5 mm G.I strip on surface or in recess i/c making connection as reqd |
| 28 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 29 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 30 | 8 way (4 + 24), Double door |
| 31 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, “C” curve, miniature circuit breaker suitable for inductive load of single pole MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 32 | Single pole |
| 33 | Three pole |
| 34 | Three pole and neutral |
| 35 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 36 | 63 A |
| 37 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 38 | 4x10 sqmm+2x6 sqmm |
| 39 | Laying and fixing of one number PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 40 | Above 35 sq. mm and upto 95 sq. mm |
| 41 | upto 35 sqmm |
| 42 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, refilling the trench etc as required. |
| 43 | Above 35 sq. mm and upto 95 sq. mm |
| 44 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed steel/ PVC conduit as required |
| 45 | 1 run of cable |
| 46 | 2 run of cable |
| 47 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 48 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 49 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 50 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 51 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 52 | 3.5C X 35 sq. mm (32mm) |
| 53 | 3.5CX 95 sq. mm (45mm) |
| 54 | 4C X 16 sq. mm (28mm) |
| 55 | 3.5C X 300 sq. mm (70mm) |
| 56 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 + 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP completeas per specifications. |
| 57 | Two Loop Panel. |
| 58 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 59 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metalliccover complete with all connections etc as required. |
| 60 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum _ fixed tempreature thermistor complete with base as required. |
| 61 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 62 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
| 63 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 64 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. |
| 65 | Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH _ inner bedding, steel wire armouring & LSZH outer sheath complete as required. |
| 66 | Supply, Installation, testing and commissioning of pre-wired, single box fitting with one no. LED tube of frosted cover design, 18 Watt, 2100 lm, 50000 burning hours, size 1200 mm complete i/c all accessories etc. directly on ceiling/wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor cable and earthing etc. as required. fitting equivalent to Philips Make, Cat No. TMC 502 1xT-LED 22W, Tube equivalent to Philips Make, Cat No. Mas LEDTube 1200mm 18W 865 T8I-2100lm |
| 67 | SITC of 12 inch heavy duty,AC, single phase 230 Volt,50 HZ, 1350 RPM, steel body exhaust fan in existing opening,i/c making good the damage, cable connectionetc etc. as reqd. |
| 68 | Supply, Installation, testing and commissioning of pre wired 2\"x2\" recess mounted 36 watts LED fitting square shape, Commercial grade with luminaire with diffuser complete with all accessories i/c connection with 1.5 sqmm FRLS PVC copper conductor Cable with mounting 4 nos clutch wire /G.I. chain for mounting from true ceiling etc. as required. Make Philips, Model No. - FullGlow G6Cat No. RC380B LED36S-6500 G6 L60W60 PSU OD S1 or equivalent model of Thorn/Trilux |
| 69 | Supplying and fixing of 1 Module RJ-45 computer socket i/o Cat6 on existing box/cover plate andmaking of connection etc. complete as required. Make -Wipro North west Cat No-R5200 or eqivalent model of Legrand/Schneider |
| 70 | Supplying of one no XLPE insulated and PVC sheathed aluminium conductor armoured power cable of 1.1 KV grade of size 4CX16 Sqmm etc. complete as required. |
| 71 | 4CX16 Sqmm |
| 72 | 3.5C X35 Sqmm |
| 73 | 3.5C X95 Sqmm |
| 74 | Supply, Installation, testing and commissioning of 15 watt, LED downlighter, Commercial grade, 220-240 V, 50 Hzcomplete i/c all accessories etc. recesses mounted including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor cable and earthing etc. as required. Make Philips, Model No. - GreenPerform Sleek G2 Cat No. DN296B LED15S-6500 PSE WH S2 or equivalent model of Thorn/Trilux |
| 75 | Supply, erection, testing and commissioning of 415V, 3 phase 4 wire 50 Hz , cubical type feeder pillar, IP 65 (outdoor type) fabricated CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having capacity extensible type DMC / SMC FP bus bars of high conductivity,DMC/ SMC bus bar supports , bottom base channel of MS section of suitable size, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size ofbus bars etc.complete in all respect as per CPWD specificationcomplete with necessary accessories, wiring with 2.5sq. mm. FRLSH insulated copper conductor , cable alleys, cable glandand following incoming and outgoing switchgears with protection andmetering etc.as required at site. All MCCBs above 63A should be provided with Spreader Terminals. Approval shall be taken for each panel before fabrication.Incomer250A FP MCCB (36kA)with microprocessor realease O/L & S/C protection -1 Nos., Incomer should be Suitable for cable termination. RYB on, off trip indication lamp-1 set., Multi-Function Meter with CT-1 nos.Busbar 400A FP Al busbar Extensible typeOutgoing :1. 100A FP MCCB (36kA) thermal magnetic based with O/L,S/CProtection. - 3 nos.RYB on, off trip indication lamp - 2 set, Multi-Function Meter with CT - 2 nos.2. 63A FP MCB (10kA) - 21 nos.3.63A DP MCB (10kA) -3nos.Connecting terminal (Inside cable alley) of all MCB should be suitable for connection with Aluminium armoured cable upto size 16sqmm. |
| 76 | Supply, erection, testing and commissioning of 415V, 3 phase 4 wire 50 Hz , cubical type feeder pillar, IP 65 (outdoor type) fabricated CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having capacity extensible type DMC / SMC FP bus bars of high conductivity,DMC/ SMC bus bar supports , bottom base channel of MS section of suitable size, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size ofbus bars etc.complete in all respect as per CPWD specificationcomplete with necessary accessories, wiring with 2.5sq. mm. FRLSH insulated copper conductor , cable alleys, cable glandand following incoming and outgoing switchgears with protection andmetering etc.as required at site. All MCCBs above 63A should be provided with Spreader Terminals. Approval shall be taken for each panel before fabrication.Incomer125A FP MCCB (36kA)with microprocessor realease -1 Nos. having O/L, E/F andS/CProtection, Incomer should be Suitable for cable termination. RYB on, off trip indication lamp-1 set., Multi-Function Meter with CT-1 set.Busbar 200A FP Al busbar Extensible typeOutgoing :1. 100 Amp Timmer switch - 01 Nos.2. 40 A FP MCB (10kA) - 15 nos.3.63A DP MCB (10kA) -4 nos.Connecting terminal (Inside cable alley) of all MCB should be suitable for connection with Aluminium armoured cable upto size 16sqmm. |
| 77 | Supply, erection, testing and commissioning of 415V, 3 phase 4 wire 50 Hz , cubical type feeder pillar, IP 65 (outdoor type) fabricated CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having capacity extensible type DMC / SMC FP bus bars of high conductivity,DMC/ SMC bus bar supports , bottom base channel of MS section of suitable size, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size ofbus bars etc.complete in all respect as per CPWD specificationcomplete with necessary accessories, wiring with 2.5sq. mm. FRLSH insulated copper conductor , cable alleys, cable glandand following incoming and outgoing switchgears with protection andmetering etc.as required at site. All MCCBs above 63A should be provided with Spreader Terminals. Approval shall be taken for each panel before fabrication. Incomer630A TP MCCB (50kA)with microprocessor realease with O/L &S/C protection -1 Nos., Incomer should be Suitable for cable termination. RYB on, off trip indication lamp-1 set., Multi-Function Meter with CT-1 nos. and rotary handleBusbar 800A FP Al busbar Extensible typeOutgoing :1. 400A TP MCCB (35kA) thermal magnetic based with O/L,S/CProtection., Rotary Handle - 2 nos. RYB on, off trip indication lamp - 2 set, Multi-Function Meter with CT - 2 set.2. 250A TP MCCB (35kA) thermal magnetic based with O/L,S/CProtection. Rotary Handle - 4 nos. RYB on, off trip indication lamp - 4 set, Multi-Function Meter with CT - 4 set.Connecting terminal (Inside cable alley) of all MCB should be suitable for connection with Aluminium armoured cable upto size 300 sqmm. |
| 78 | Providing and fixing of 4.5 Kg capacity carbon dioxide (CO2) Stored Pressure type portable fire extinguishers, fully charged, confirming to IS 15683:2018 complete with delivery hose horn, wheel type release valve, locking arrangement, including hanging arrangement on wall with bracket etc. as required. |
| 79 | Supply and fixing of 6.0 Kg capacity ABC Stored Pressure type portable fire extinguishers, fully charged, ISI marked, confirming to IS 15683:2018 complete with squeeze grip release valve, discharge pipe, locking arrangement, pressure gauge including hanging arrangement on wall with bracket etc. as required. |
| 80 | Supply, Installation, testing and commissioning of 10 watt, LED bulkhead pressure die cast housing with IP65 protection and IK09 impact resistance suitable for surface and wall mounting applications., 220-240 V, 50 Hzcomplete i/c all accessories etc directly on surface including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor cable and earthing etc. as required. Make Philips, Model endura LED Bulkhead, Cat No.WT202W LED10S CW PSU S3 PC or equivalent model of Thorn/Trilux |
| 81 | Supply, Installation, Testing and commissioning of 86” Interactive Flat Panel Display (IFPD) suitable for smart classroom/conference room comprising TFT LCD with DLED backlight and VA panel, Ultra HD 4K resolution (3840 × 2160), complete with latest embedded Android operating system, quad-core ARM Cortex processor or better, minimum 8 GB RAM and 128 GB internal storage, ultra-fine touch technology with minimum 40 touch points (finger and pen), dual-tip touch pen support, anti-glare 9H hardened glass surface, minimum brightness 450 nits, viewing angle 178° (H/V), backlight life minimum 50,000 hours Connectivity: HDMI IN – 3 Nos. (HDMI 2.0), HDMI OUT – 1 No. (HDMI 2.0), USB Type-A – USB 3.0 × 4 Nos. & USB 2.0 × 1 No., USB Type-B – 2 Nos., USB Type-C (front) supporting display, data, LAN sharing and 65W power delivery, VGA/RGB – 1 No., Audio IN/OUT – 1 No. each, SPDIF – 1 No., RS-232 – 1 No., LAN (RJ-45) – 2 Nos., OPS slot (Intel standard compatible), Wi-Fi slot provision.Audio & Camera: Built-in front-facing speakers minimum 20W × 2, provision for top camera mounting plate.Software: Pre-installed interactive whiteboard/annotation software, wireless screen sharing and presentation software, multi-tasking support, device management and collaboration features.Power & Mounting: Power supply 100–240V AC, heavy-duty wall mounting arrangement compatible with VESA 800 × 600 mm.Accessories: Remote control with batteries, minimum two touch pens, HDMI cable, USB touch cable, power cable, mounting hardware (clamps, screws etc.), quick start guide.OPS:SITC of OPS suitable with above 86\" display, i5 processor, 8GB RAM, 512 GB memory. Warranty: Minimum 3 years comprehensive onsite warranty including panel, touch, electronics and software support.Make: ViewSonic Model: IFP8633-G-N or equivalent Model of Samsung, LG, BenQ |
| 82 | Supplying and fixing of following size WallMountRack havingFixedStructurewith0.8mm CRCASheet, completely knocked-down condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with \"U\"Marking, Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting kit,Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required |
| 83 | 15U Rack |
| 84 | Supply and laying of 2 core 14 AWG/2.5 Sq mm, Twisted, unshielded Speaker cable with stranded annealed bare copper conductors, Semi-rigid PVC insulation, NEC CL3R, CEC CMG, RoHS compliant (Make & Model Liberty AV 14-2C-BLK) etc. complete as required. |
| 85 | Supply and laying 2 core Twisted, shielded balanced Audio and control cable with 22AWG or better 7 strand annealed bare copper conductors, Semi-Rigid PVC insulation, Riser rated PVC jacket. UL 444, UL 13 CMR rated etc. complete as required. |
| 86 | Supply, Installation, Testing and Comissioningof Gooseneck mic with mute button, Element Fixed-charge back plate, permanently polarized condenser Polar Pattern Cardioid, Frequency Response 70-16,000 Hz, Open Circuit Sensitivity -37 dB (14.1 mV) re 1V at 1 Pa, Maximum Input Sound Level 134 dB SPL, 1 kHz at 1% T.H.D etc. complete as required. Make - AudioTechnica, Cat No- Pro49qle+AT8668s or Equivalent make of Shure/sennheiser/AKG |
| 87 | Supply, Installation,Testing & Commissioning of 5.25 \"two- Way Speaker with a Frequency Response (-3 dB):-90 Hz-20 KHz; Frequency Range (-10 dB) : 55Hz-20 KHz; & Long Term Program Power Handling of 75Wor more (at Nominal Impedance of 8 ohms). The Loud speaker should have a Sensitivity (1W/1m)> 88 dB with a Max. SPL (Peak)> 113 dB.The Sound Dispersion should be 90x90 Degrees or more;TransformerTaps @70/100V-7.5W, 15W,30W.The Speaker Should have environmental specs of IP54 (per IEC-60529) & should Come with OEM wall Mounting Bracket. |
| 88 | Supplying, Installation, testing and commissioning of Class-D Mixer amplifier 240 W 1 channel,Full power output supporting 4Ω, 8Ω, 70V and 100V; Frequency response,-3 dB:< 20 Hz—20 kHz; Distortion: <0.5%; S/N: >100 dB; Should have 2mic/line, 2 aux, EMG (priority input);Should have 3-pin XLR,balanced/ 5-pin Eurostyle,balanced (3 pin for input,2 pin for trigger Connector). |
| 89 | Supply, Installation, Testing and Commissioning of 10 Channel Mixing Console having 04 mono mic and line inputs+3x stereo input with 02 stereo output ,1x monitor out,1x Aux send, Frequency Response: 20 Hz-48 kHz,Cross talk:-83 dB, THD:0.02%, Phantom power: +48V and power consumption: 23W; Digital I/O: USB Device support like IPOD/Iphone;1 knob compressor, HPF, EQ, level meter;complete with standard accessories. |
| 90 | Supply, Installation, testing and commissioning of Wireless Handheld Microphone with Cardiod polar pattern, dynamic microphone, Frequency response 80 Hz-18 kHz, Signal-to noise ratio ≥ 100 dBA, Modulation - ± 40 kHz, Distortion ≤ 1.0%, Number of Channels: 32Per Band, 8 Simultaneous, Diversity: True Antenna, Image Rejection > 55 dB, Balanced Output: 20 dBV or better, RF Sensitivity :< 1.0μV or better, Power Requirements : 12-16 V DC ,500 mA max,Operating Temperature : 5°C to 45°C and 14hour battery life from twoAA alkaline. |
| 91 | Supply, Installation,testing and commissioning of head worn mic with omni directional polar pattern for transmitter, condenser microphone element ; Frequency Response : 80 Hz-18 kHz +/- 2 dB; RF Sensitivity : <1.0uV ; Receiver Image Rejection : > 55 dB; Number of Channels : 32 ; Signal-to-Noise Ratio : > 100 dB ;Distortion: < 1.0%; |
| 92 | Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : |
| 93 | 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick |
| 94 | 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick |
| 95 | Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotarycompressor. The system shall be able to deliver 100% of Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). |
| 96 | 1.0 TR with 5 Star BEE Rating |
| 97 | 1.5 TR with 5 Star BEE Rating |
| 98 | Providing and fixing of 25 mm PVC drain pipe exposed on wallwith necessary clamps, and fittings etc. duly insulated with 19 mm thickclosed cell elastometric nitrile rubber of minimum 45 Kg/cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class \"O\" insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer in Charge |
| 99 | Supplying of one number PVC insulated and PVC sheathed / XLPE copper conductor unarmoured power cable of 650/1100 KV grade ofsize 3C x 2.5 sqmm etc as required. |
| 100 | Conducting of survey, preparing of all reports, design and drawings of Electrical and HVAC system including required for construction of LGSF structure at 2nd floor level at Arts faculty building. This includes preparing of all shop drawings, GFC drawings, As built drawings in hard and soft copy both as per latest CPWD specifications, IS codes, National building codes, including taking of approval of client at every stage complete as required. |
| 101 | Supplying, Installation, Testing & Commissioning of 13 passenger (884kg) capacity passenger Machine room less (MRL) lift with regenerative drive as per CPWD General Specification for Electrical Works (Part-III Lift & Escalator) 2003, BIS Codes, NBC 2016 as amended upto date having provision for barrier free access as per Harmonised Guidelines & Standards for Universal Accessibility in India - 2021 of MoHUA, serving different floors in the lift shaft as per detailed specifications enclosed and as under including all other equipment and accessories complete as required:- (i) Speed-1 MPS(ii) Floors-3(G+2)(iii)) Stops & opening- 3 stops and 3 openings(iv) Controller: A.C. variable voltage & variable frequency(v) Automatic rescue device (ARD) complete with dry maintenance free batteries as required.vi) Operation: Microprocessor based single automatic push button/simplex selective collective selective with/without attendant(viii) Power-415 Volts+10%, 3 phase, 50 Hz, 4 wires system(ix) Car Enclosure: Stainless steel scratch proof (Honeycomb Finish) on all sides except door and Rear Panel (Rear panel should be of glass) and stainless steel decorative ceiling with fans (indirect throw) and LED fitting.(x) The car flooring should be Granite stone/Tile etc . (xi) Type of doors(a) Car: Power operated, centre opening horizontal sliding madeup of Glass .(b) Landing doors: Glass.(xii) A hand rail not less that 600mm long at 900mm above floor level to be fixed adjacent to control panel in the lift car.(xiii) Voice announcement system in the car to announce the position of the elevator in the hoist way as the car passes or stops at floor served by the elevator.(xiv) Closed loop Control System, protection against power fluctuation, self diagnostic control, Landing doors 1 hours Fire rated, Overload detection and protection, Overspeed Governer, Dot Matrix LED D & P Indicators In Car & Landings, BMS Compatibility, tamper proof infrared curtain covering almost the entire height of the lift car door, Alarm horn, Anti Nuisance Operation, provision of CCTV camera system, Firemen switch, 2/3 way intercom, Emergency Stop Switch with battery backup for fan and light fitting for 1 hour, pit ladder.(xv) The lift doors shall have madeup of glassto enable persons with hearing impairment to signal for help or assistance in the event of an emergency.(xvi) An appropriate technological support be provided (Through emergency messaging |services or alarms etc.) torespond to the emergency requirements of person with hearing impairment or deafness.(xvii) In case of failure of ARD or other electronic devices, a provision of manual rescue be provided. IS 17900 (Parts 1 & 2) shall be followed for this item Make: Kone/OTIS/Mitsubishi |