| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable insurface /recessedmediumclassPVCconduit,withmodular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group B. |
| 2 | Wiringforcircuit/submainwiringalongwithearthwirewiththe followingsizesofFRLSPVCinsulatedcopper conductor,single corecableinsurface/recessedmediumclassPVCconduitas required. i) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire. |
| 3 | Wiringforcircuit/submainwiringalongwithearthwirewiththe followingsizesofFRLSPVCinsulatedcopper conductor,single corecableinsurface/recessedmediumclassPVCconduitas required. i) 2 X 6 sq. mm + 1 X 6 sq. mm earth wire. |
| 4 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cablein surface/ recessedmedium class PVC conduit alongwith 1No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 5 | Supplying and fixing following modular switch/ socket on the existing modularplate&switchboxincludingconnectionsbutexcluding modular plate etc. as required. i) 5/6 A switch. |
| 6 | Supplying and fixing following modular switch/ socket on the existing modularplate&switchboxincludingconnectionsbutexcluding modular plate etc. as required. ii) 15/16 A switch. |
| 7 | Supplying and fixing following modular switch/ socket on the existing modularplate&switchboxincludingconnectionsbutexcluding modular plate etc. as required. iii) 3 pin 5/6 A socket outlet. |
| 8 | Supplying and fixing following modular switch/ socket on the existing modularplate&switchboxincludingconnectionsbutexcluding modular plate etc. as required. iv) 6 pin 15/16 A socket outlet. |
| 9 | Supplyingand fixingtwo module steppedtypeelectronicfan regulatorontheexistingmodularplateswitch boxincluding connections but excluding modular plate etc. as required. |
| 10 | Supplyingandfixingfollowingsize/modules,GIboxalongwith modular base & cover plate for modular switches in recess etc. as required. i) 1 or 2 Module (75mmX75mm) |
| 11 | Supplyingandfixingfollowingsize/modules,GIboxalongwith modular base & cover plate for modular switches in recess etc. as required. ii) 3 Module (100mmX75mm) |
| 12 | Supplyingandfixingfollowingsize/modules,GIboxalongwith modular base & cover plate for modular switches in recess etc. as required. iii) 4 Module (125mmX75mm) |
| 13 | Supplyingandfixingfollowingsize/modules,GIboxalongwith modular base & cover plate for modular switches in recess etc. as required. iv) 6 Module (200mmX75mm) |
| 14 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar,din bar,interconnections,powderpaintedincluding earthing etc. as required. (But withoutMCB/RCCB/Isolator).8 way , Double door. |
| 15 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles intheexistingMOBDBcompletewithconnections,testingand commissioning etc. as required. i) Single pole. |
| 16 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles intheexistingMOBDBcompletewithconnections,testingand commissioning etc. as required. i) Single pole and neutral. |
| 17 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \"C\" curve including connections, painting etc. as required. |
| 18 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories,andprovidingmasonryenclosurewithcoverplate havinglocking arrangement and wateringpipe etc. with charcoal/ coke and salt as required. |
| 19 | Providing and laying earth connection from earth electrode with 6 SWG diaG.I.Wirein15 mm diaG.I.pipe fromearthelectrode including connection withG.I. thimble excavation andre-filling as required. |
| 20 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. i) 3½ X 95 sq. mm (45mm). |
| 21 | S/I/T/C of 240V, 50 HZ 1400 mm SweepCeiling Fan, having 02 Nos Canopy including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required of Havells / Crompton/Bajaj/usha including connection etc as required. |
| 22 | S/I/T/C of 20 Watt, 3000-6500 K LED batten Decorative ultra slim square profile LED lighting fixture with polycarbonate housing, environmental friendly, energy efficient with LED inbuilt driver Havells make (lumline nxt batten) or equivalent make of Philips/CG/Bajaj/Orient including connection etc as required. |
| 23 | Supplying and fixing of 70 Watt, 230 V , LED post top, Color Temp. 30k / 57k, IP65 die cast aluminium Post top lantern designed with long life LED engine & Electronic Driver, designed for glare free symmetrical light distribution, Suitable for pole dia Ø 76 mm including fixing in the existing pole including connection testing commissioning etc as required as per direction of engg-in-charge. Havells make or equivalent of Philips/bajaj/CG/wipro. |
| 24 | Supplying and fixing of AC Single Phase Static Energy meter of Accuracy Class 1.0, 240V, 50Hz, with Backlit LCD Display of rating 5-30A & with 1 push button. (Measures & displays kWh, kVAh, V,I,PF, frequency, kW, kVA, six months history of Energy & MD in kW & kVA) with Transparent Hinge type Box. including connection testing commissioning etc as required as per direction of engg-in-charge. HPL make or equivalent of Havells/Philips/bajaj/CG/wipro. |
| 25 | Supplying, Installation, testing and commissioning ofwater prrof 900 X 600 X 400 mm size, 2 mm thick CRCA metal sheet , double door outdoor type powder coated panel finished with prime/paint (CPRI approved/specified)with 500mm long, 20mmx4mm thick, 04 Nos. insulated aluminium busbar suitable for 415 volt 3 phase, 50 Hz AC supply, 125 Amp, 25 KA, 4 Pole MCCB, interconnections. Arrangement for incoming/outgoing cabling/cable termination, separate detachable gland plate, includingbase frame made out ofrolled steel channel of size 125mm x 65mm x 6mm thick of suitable size of the panel , hinged, door, locking arrangement for inside and outside separately, earth bar/stud. The panel shall be embeded in 1:3:6 cement concrete foundation of required size (minimum 30 cm belowand 45 cm above ground level) including finishing etc as required at site as per direction of engineer-in-charge. |