| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | a)Group A |
| 3 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mmFRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 5 | a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth |
| 6 | b) 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 7 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 8 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 9 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 10 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 11 | Supplying and fixing PVC batten/ angle holder including connections etc. as required. |
| 12 | Supplyingof9W LED lamp, B22, CDL/WW 2S lamp V8i Make:HavellsModel :-LEDPLUS 9W B22 or equivalentin Bajaj/Crompton/Philipsinthelamp holder etc as required. |
| 13 | Supplying of LED batten CRCA housing box type luminaire suitable for 1 x 18/20W T8 LED retrofit tube lampMake:-BajajCat.No. BLRB-DB-118 or equivalentin Havells /Crompton /Philipscomplete with all accessories etc as required. |
| 14 | Supplying of20W LEDT8 RetrofitTube lightwith polycabonate housingMake :- Bajaj- Model No. BLRB 20W CW LEDor equivalent in Havells/Philips/Crompton. |
| 15 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 16 | Supplying of 10WLED Bulkhead fitting Make:- PhilipsVistaGlowCat.No.WT140W LED7S CW PSU S1 PCor equivalent in Havells/Bajaj/Crompton/C&S /Philipscomplete with all accessories etc as required. |
| 17 | Erection of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS lamps per fitting, complete with all accessories including connection etc. as required. |
| 18 | Supplying of 1200mm sweep BLDC 5 star energy saving AC ceiling fan Make:- USHA 1200mm TECHNIX BLDC ISI5 star-28W(w/o remote)or equivalent in Havells/Bajaj/Crompton/RR Fans/Orient complete with all accessories etc as required. |
| 19 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
| 20 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 21 | Supplying of230mm sweep Exhaust fan(Metallic Range) Make: USHA- AEROCLEAN LD GBD or equivalentin Bajaj/Havells/Crompton/RR Fans/Orient complete with all accessories etc as required. |
| 22 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
| 23 | a) Upto 450 mm sweep |
| 24 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A \"C\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket outlet and complete with connections, testing and commissioning etc. as required. |
| 25 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 26 | a) 12 way, Double door |
| 27 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 28 | a) Single pole |
| 29 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 30 | a)40 A |
| 31 | Supplying, Installation, testing and commissioning of Earthing withASHLOK make SEE brand safe earthing electro type-19, 48mm dia,length 2 mtrsequivalent by filling inner space with 50 Kg ( 2 bags) Electrodite (Back fill compound) required for safe earth electrode and providing masonary enclosure with C.Icover plate having locking arrangement etc. as required. |
| 32 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 33 | Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15 mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. |
| 34 | Supplyingandfixing ofSMC Sintex box ofsizeinside dimension 390 x 225 x 140Code No. GSJB-3923, single door (R) with 01 No. cut-out 32A/240Vincluding connectionetc. as required. |