| Sl. No. | Item Description |
| 1 | Supply, installation, commissioning and testing transformer floor mounted capacity 100 KVA step down, outddor type, 50 cycle/sec (50 Hz), oil immersed air naturally cooled (ONAN) with external cooling tubes, raditors, core type having no load ratio 11 KV/433 volt corresponding to principal tapping, copper winding, delta connected to primary side (HV side)and star connected on secondary side (LV side) in accordance with vector Symbol Dy 11 (Vector group 4) with neutral brought out on LV side and having tapping on HV side for constant output so as to alter/vary secondary voltage in step of +/- 2.5% to +/- 7.5% be changed by means of manual off load tap changing arrangement.The voltage regulation shall be as per relevant IS.The limit of temperature rise after continuous full load run as specified in SSR Part I & IS 2026 (Part 1)/Relevant IS, latest energy level & standard(BIS) shall be suitably adjusted to suit the maximum ambient temperature prevalling at site (Leh/Ladakh) all as specified.The transformer shall be completed with following fittings and accessories:- (a)Oil conservator with filling hole and cap drain valve.(b)Silica gel breather with connecting pipe, first fill of dehydrating agent. (c)Expansion relief mounted on tank with double diaphram and equalizer pipe connected to conservator (Pressure release valve.) (d)Air release plug (e) Oil temperature indicator of approved range, including shut off valve between conservator and main tank. (f) Winding temperature indicator of approved range. (g)Drain valve with threaded adopter. (h)Sample valve. (i)HV CableBox at HT Side (j) LT cable box at LT Side |
| 2 | Supply, installation, commissioning and testing transformer floor mounted capacity 160 KVA step down, outddor type, 50 cycle/sec (50 Hz), oil immersed air naturally cooled (ONAN) with external cooling tubes, raditors, core type having no load ratio 11 KV/433 volt corresponding to principal tapping, copper winding, delta connected to primary side (HV side)and star connected on secondary side (LV side) in accordance with vector Symbol Dy 11 (Vector group 4) with neutral brought out on LV side and having tapping on HV side for constant output so as to alter/vary secondary voltage in step of +/- 2.5% to +/- 7.5% be changed by means of manual off load tap changing arrangement.The voltage regulation shall be as per relevant IS.The limit of temperature rise after continuous full load run as specified in SSR Part I & IS 2026 (Part 1)/Relevant IS, latest energy level & standard(BIS) shall be suitably adjusted to suit the maximum ambient temperature prevalling at site (Leh/Ladakh) all as specified.The transformer shall be completed with following fittings and accessories:- (a)Oil conservator with filling hole and cap drain valve.(b)Silica gel breather with connecting pipe, first fill of dehydrating agent. (c)Expansion relief mounted on tank with double diaphram and equalizer pipe connected to conservator (Pressure release valve.) (d)Air release plug (e) Oil temperature indicator of approved range, including shut off valve between conservator and main tank. (f) Winding temperature indicator of approved range. (g)Drain valve with threaded adopter. (h)Sample valve. (i) HV CableBox at HT Side(j) LT cable box at LT Side |
| 3 | Supply, installation, commissioning and testing transformer floor mounted capacity 200 KVA step down, outddor type, 50 cycle/sec (50 Hz), oil immersed air naturally cooled (ONAN) with external cooling tubes, raditors, core type having no load ratio 11 KV/433 volt corresponding to principal tapping, copper winding, delta connected to primary side (HV side)and star connected on secondary side (LV side) in accordance with vector Symbol Dy 11 (Vector group 4) with neutral brought out on LV side and having tapping on HV side for constant output so as to alter/vary secondary voltage in step of +/- 2.5% to +/- 7.5% be changed by means of manual off load tap changing arrangement.The voltage regulation shall be as per relevant IS.The limit of temperature rise after continuous full load run as specified in SSR Part I & IS 2026 (Part 1)/Relevant IS, latest energy level & standard(BIS) shall be suitably adjusted to suit the maximum ambient temperature prevalling at site (Leh/Ladakh) all as specified.The transformer shall be completed with following fittings and accessories:- (a)Oil conservator with filling hole and cap drain valve.(b)Silica gel breather with connecting pipe, first fill of dehydrating agent. (c)Expansion relief mounted on tank with double diaphram and equalizer pipe connected to conservator (Pressure release valve.) (d)Air release plug (e) Oil temperature indicator of approved range, including shut off valve between conservator and main tank. (f) Winding temperature indicator of approved range. (g)Drain valve with threaded adopter. (h)Sample valve. (i)HV CableBox at HT Side (j) LT cable box at LT Side |
| 4 | Supply, installation, commissioning and testing transformer floor mounted capacity 250 KVA step down, outddor type, 50 cycle/sec (50 Hz), oil immersed air naturally cooled (ONAN) with external cooling tubes, raditors, core type having no load ratio 11 KV/433 volt corresponding to principal tapping, copper winding, delta connected to primary side (HV side)and star connected on secondary side (LV side) in accordance with vector Symbol Dy 11 (Vector group 4) with neutral brought out on LV side and having tapping on HV side for constant output so as to alter/vary secondary voltage in step of +/- 2.5% to +/- 7.5% be changed by means of manual off load tap changing arrangement.The voltage regulation shall be as per relevant IS.The limit of temperature rise after continuous full load run as specified in SSR Part I & IS 2026 (Part 1)/Relevant IS, latest energy level & standard(BIS) shall be suitably adjusted to suit the maximum ambient temperature prevalling at site (Leh/Ladakh) all as specified.The transformer shall be completed with following fittings and accessories:- (a)Oil conservator with filling hole and cap drain valve.(b)Silica gel breather with connecting pipe, first fill of dehydrating agent. (c)Expansion relief mounted on tank with double diaphram and equalizer pipe connected to conservator (Pressure release valve.) (d)Air release plug (e) Oil temperature indicator of approved range, including shut off valve between conservator and main tank. (f) Winding temperature indicator of approved range. (g)Drain valve with threaded adopter. (h)Sample valve. (i)HV CableBox at HT Side(j)LT cable box at LT Side |
| 5 | Supply, laying, jointing, testing and commissioning of High Tension (HT)XLPEinsulated, galvanised steel strip or wire armoured, heavy duty, electric power cable, cross sectional area 95 Sqmm 3 core aluminum conductor 11000 volts (earthed) grade ISI marked under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc,complete all as specified and as directed. Note(s):(i) Earth work, sand cushioning and PCC cover for protection of cable shall be measured and paid separately in respective item of Schedule \"A\". |
| 6 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPEinsulated, armoured, heavy duty, electric power cable, cross sectional area 500 Sqmm 3.5 core aluminum conductor 1100volts grade underground cable ISI marked including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc,complete all as specified and as directed.Note(s): (i) Excavation & earth work, sand cushioning and PCC cover for protection of cable shall be measured and paid separatelyin respective item of Schedule \"A\". |
| 7 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPEinsulated, armoured, heavy duty, electric power cable, cross sectional area 400 Sqmm 3.5 core aluminum conductor 1100volts grade underground cable ISI marked including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc,complete all as specified and as directed.Note(s): (i) Excavation & earth work, sand cushioning and PCC cover for protection of cable shall be measured and paid separatelyin respective item of Schedule \"A\". |
| 8 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPEinsulated, armoured, heavy duty, electric power cable, cross sectional area 185 Sqmm 3.5 core aluminum conductor 1100volts grade underground cable ISI marked including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc,complete all as specified and as directed.Note(s): (i) Excavation & earth work, sand cushioning and PCC cover for protection of cable shall be measured and paid separatelyin respective item of Schedule \"A\". |
| 9 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPEinsulated, armoured, heavy duty, electric power cable, cross sectional area 150 Sqmm 3.5 core aluminum conductor 1100volts grade underground cable ISI marked including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc,complete all as specified and as directed.Note(s): (i) Excavation & earth work, sand cushioning and PCC cover for protection of cable shall be measured and paid separatelyin respective item of Schedule \"A\". |
| 10 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPEinsulated, armoured, heavy duty, electric power cable, cross sectional area 120 Sqmm 3.5 core aluminum conductor 1100volts grade underground cable ISI marked including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc,complete all as specified and as directed.Note(s): (i) Excavation & earth work, sand cushioning and PCC cover for protection of cable shall be measured and paid separatelyin respective item of Schedule \"A\". |
| 11 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPEinsulated, armoured, heavy duty, electric power cable, cross sectional area 95 Sqmm 3.5 core aluminum conductor 1100volts grade underground cable ISI marked including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc,complete all as specified and as directed.Note(s): (i) Excavation & earth work, sand cushioning and PCC cover for protection of cable shall be measured and paid separatelyin respective item of Schedule \"A\". |
| 12 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPEinsulated, armoured, heavy duty, electric power cable, cross sectional area 50 Sqmm 3.5 core aluminum conductor 1100volts grade underground cable ISI marked including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc,complete all as specified and as directed.Note(s): (i) Excavation & earth work, sand cushioning and PCC cover for protection of cable shall be measured and paid separatelyin respective item of Schedule \"A\". |
| 13 | Supply and fix, steel water tubing of 80mm dia bore, light grade, galvanised, with all standard fittings ISI marked , laid in trenches/crossing the road/fixed to pole,complete all as specified and directed. Note :Excavation & earth work as required will be measured and paid separatelyin respective item of Schedule \"A\". |
| 14 | Supply and fix, steel water tubing of 50mm dia bore, light grade, galvanised, with all standard fittings ISI marked , laid in trenches/crossing the road/fixed to pole,complete all as specified and directed. Note :Excavation & earth work as required will be measured and paid separatelyin respective item of Schedule \"A\". |
| 15 | Excavation in trenches in any type of soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying of cables and foundation of poles etc. and getting out, complete all as specified and directed. |
| 16 | Excavation in trenches in any type of soil not exceeding 1.5 metre wide and depth exceeding 1.5 metre but not exceeding 3.0 metre deep for laying of cables and foundation of poles etc. and getting out, complete all as specified and directed. |
| 17 | Material and labour, sand cushioning with a layer of dry river sand, 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts, complete all as specified and directed.Note : Punned down thickness (overall 18cm), shall be considered for measurement and payment. |
| 18 | Returning, filling in trenches (soil), including spreading, leveling and well ramming in layers not exceeding 25 cm thick, complete all as specified and directed. |
| 19 | Removal of surplus excavated soil to a distance not exceeding50 metre and depositing where directed at a level not exceeding1.5metre above the starting point,complete all as specified and directed. |
| 20 | Supplying and laying,factory made unreinforced precast concrete cable cover HV type-1, flat, of size 300x180x40mm,ISI marked for protection of HT cable , complete all as specified and directed. |
| 21 | Supplying and laying,factory made unreinforced precast concrete cable cover LV type-1, flat, of size 250x150x40mm, ISI marked for protection of LT cable , complete all as specified and directed. |
| 22 | Material & labour for cutting existing road/Hard Rock/ PCC hard Standing/ pavement/drain for taking out / laying of indergroung water pipe/cable and including necessary earth work and making good to match with the existing surface with PCC work in type B2 (1:2:4) cement mortar with 40mm graded aggregatecomplete all as specified and as directed. |
| 23 | Material & labour for PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete in foundation of pole/stays etc completeall as specified &directed. |
| 24 | Material & labour for PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete in foundation of pole/stays etc completeall as specified &directed. |
| 25 | Material & labour for PCC 1:2:4 type B-1 (using 20mm graded crushed stone aggregates) as in coping/above ground level around the pole etc completeall as specified &directed. |
| 26 | Supply, installation, testing & commissioning ofRMU 11 KV ,3 phase, 50 cycles totally enclosed metal clad SF6 switchgear having STC of 250 MVA, as per Specifications and details given below with 01 No 400A VCB Incomer & 02 Nos Load breaker switch 630 Amp as outgoing, outdoor typecompleteall as specified &directed . The details specifications of RMU is as below :- Design, Supply, Erection, Testing and Commissioning of 11 KV, 400A, 50Hz, 21KA for 3sec, SF6 insulated, Motorized, Outdoor , One side extensible RMU along with air insulated side connected bus metering unit , type tested in line with latest IEC standards. The RMU shall be suitable for operations at a height up to 3500 meters above sea level at Leh. The RMU should operate at -20 degreeto +40 degree ambient temperature . The switchgear and busbar shall all be contained in a stainless steel enclosure filled with SF6 at 0.3 bar (300 KPa) relative pressure. The RMU tank shall provide full insulation, making the switchgear insensitive to the environment with degrees of protection of rating IP 67 . The switchgear operating mechanism shall have an IP2X protection and cable chamber shall have IP 3X Protection for Indoor & for Outdoor- IP55 protection. The outer enclosure should be IP 55 type tested, should be powder coated with pure polyester based paint , suitable for the site installation condition. Outer enclosure should be a integrated one and indoor RMU placed inside outdoor canopy is not acceptable. All operations shall be from front of the RMU, including access to cable bushings. |
| 27 | (A).Load Break Switch (LBS) as Incomer/outgoing each comprising of the following:-12 KV, 630A, 21KA for 3sec Motorized Load break switch; with built in line side manual earth switch. Earthing should be completed within 2 operations only(i.e 1. Main switch - OFF, 2. Earth switch - ON). LBS shall have 3 positions, open or disconnected, closed and earthed, and shall be constructed in such a way that interlocking prevents unauthorized operations. For earth switch, manual opening and closing shall be driven by a fast-acting /snap action mechanism, independent of operator action. LBS and earth switch shall have a min of 1000 (M1) mechanical operations ,and 5 Nos closing operations at rated SC current. LBS should have 100 electrical operations at rated current - 1 No.(B). Position indicator through clear front mimic in line with IEC 62271-103/Relivant IEC; Live cable indicator with indications (Voltage Presence Indicator) at the front and three inlets provision to check the synchronization of phases. VPI should be of same make as that of RMU; Cable box with termination bushing suitable for upto 2 RUN 3 Core x300 Sq mm, XLPE cable; Auxilary switch : LBS - 2 NO +2 NC, Earth switch - 1 NO + 1 NC; Suitable ratio CT 100/1 A, Metering class 1.0, 2.5VA ; MFM Class 1.0; Electrical & Mechanical Interlock between 2 Incomers with Key-Lock (2 Locks & 1 Key failsafe interlock); Mechanicaloperation counter; Touch proof type cable termination kit for 22 kV dielectric. C. Vacuum circuit breaker (VCB) each comprising of the following:- 11 KV, 400,21KA for 3sec Motorized VCB with spring assisted mechanism and series trip coil; with built in manual line side three position disconnector cum earth switch.Earthing should be completed within 2 operations only(i.e 1. Main switch - OFF, 2. Earth switch - ON). Vaccuum interrupter should be of same make as that of RMU. The circuit breakers shall have 2 positions: open or disconnected and closed. |
| 28 | (C). A separate and independent 3 position earthing switch and disconnector shall be fitted to open and earth the cables in such way that interlocks prevent all unauthorized operations. An independent mechanism shall be fitted for the 3 positions earthing switch and disconnector.Circit breaker shall have a min of 2000 mechanical and 2000 electrical operations at rated current and 50 Nos of operations at rated short circuit current. Disconnectorand earthswitch shall have a min of 1000 (M1) mechanical operations. The earthing switch shall be fitted with its own operating mechanism and manual closing shall be driven by a fast-acting mechanism, independent of operator action. Breaker shall have breaking capacity of 20 kArms fault current.Position indicator through clear front mimic in line with IEC 62271-103; Self powered relay with O/C , E/F protection. Relay should have a front USB port for laptop interface , LCD display ,10 event records, 5 fault records with time stamp, min 2 setting group and keypad for setting parameters for the relay. Relay should be of same make as that of RMU; Suitable ratio CT 30-60/1+1A, Class 10P5-5P10 2.5VA for protection / Metering class 1.0, 2.5VA ; MFM Class 1.0; Live cable indicator with indications (Voltage Presence Indicator) at the front and three inlets provision to check the synchronization of phases.VPI should be of same make as that of RMU; Cable box with termination bushing suitable for upto 1 RUN 3 Core x300 Sq mm, XLPE cable alluminium armoured power cable, Touch proof type cable termination kits / boots suitable for actual cable size; Mechanical operation counter; Emergency trip push button.(D). Air Insulated Bus Connected Unit comprising the following- Air Insulated enclosure with necessary bus connection via bushing. VT’sfrom the manufacturer and according to IS 3156 shall be accepted. 11KV/rt3/110V/rt3; 50VA Class 1.0. Single phase bus PT for metering . E. Accessories - Antireflex operating handle - 1No.; Battery 24V DC , 12Ah,- 1 No.; Battery charger (I/P-230V AC, O/P - 24V DC) - 1 No; Manometer with remote contact - 1 No. |
| 29 | \"Supply Installation,Testing & Commissioning of metal clad floor mounted vermin proof horizontal drawout and vertical isolation , fully interlockedvacuum circuit breaker (VCB) panel board fabricated out of minimum 3 mm thick CRCA sheet powder coated of IP4X protection for operation on 11kV,400 Amp, breaking capacity 26.3 kA for 3 Sec and having rupturing capacity 250 MVA, 3 Phase, 50 Hz, AC supply system suitable for indoor installation, manufactured in conformation to IS 3427, IEC 62271-200, BS 5227, complete with power and control wiring, interconnections,three phase Copper Bus bar fully tinned and totally covered with colour coded heat shrinkable sleeves and non-hygroscopic, high dielectric strength, Bus bar support insulators comprising01 Nos outgoing, having cable termination boxes suitable for armoured, aluminium conductor cable for outgoing feeder, foundation bolts etc. complete as required and as specified below:-\"(i)11 KV, 400 Amps. Electrically operated draw out type vacuum circuit breaker complete with motor and spring charged closing mechanism. necessary auxiliary relays, control switches, emergency hand trip devices and mechanical ON / OFF indicator.(ii) Multifunction Meter showing all Electrical Parameterie Volt, Ampere, kw, kVA, P.F., kWH.(iii)Phase indication lamps with 2 Amp SP MCB for protection (Red, Yellow and Blue).(iv) Red/ Green indicating lamp for close and open position.(v) Amber indicating lamp for auto trip.(vi)Clear indicating lamp for trip circuit healthy.(vii)Blue indicating lamp for spring charged.(viii) Strip heater to prevent absorption of moisture.(ix) Three phase over current and earth fault digital numeric relay having Instantaneous and Inverse time phase over current protection (50/51), Instantaneous and Inverse time Earth fault protection(51/51N), Phase unbalance Protection with 3 Nos. 11kV Resin Cast CTs of ratio100-50/1-1A CL 5P10, 15VA.(x)Master Trip Relay.(xi) Trip circuit supervision relay(xii) Potential transformer of 11 KV /v3/110/v3 V of suitable burden (xiii)Power pack (230VAC -110V DC)\" |
| 30 | Supply, installation, testing & commissioning of HT 11 KV, 630 Amp, 26.3 KA Load break switch (LBS) outdoor typewith fuse trip, earth switch, dynamic MIMIC arrangement, 230V AC shunt trip coil and 02 NO +2 NC Aux Contacts complete all as required and specified below ;-(i) 11Kv HTHRC Fuses Rating: 50A -03 Nos (ii) Indication Lamps LBS off / on Indication -01 set (iii)Control Wiring with appropriate colours-01 Lot(iv)Space Heater with ON/OFF Switch and Thermostat, and Fuses for AC Control-01 Set(v) MS Steel Sheet enclosure suitable for Outdoor Type Installation with MS base channel.-01 Set(vi) Provision for receiving Incoming from side cable box and Outgoing cables thro Bottom entry, - 01 Set (vii)Main Bus - 50x12mm- Aluminum - 01 Set (viii)Earth Bus - 40x6 mm- Aluminum - 01 Set |
| 31 | Supply install, test and commissioning LT Load Panel / Panel board cubical type outdoor Confirming to IS 8623 Part 1 1993, free floor standing / wall mountingfactory fabricatedmade out of 3.15 mm thick CRCA sheet & suitable size to accomodate all accessories/fittings, compartmentalized in construction to accommodate incoming and outgoingLT cables, Copper bus bars of rating not less 1.5 times the rated cap of incomer LT cable Load Capacity.The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator of size not less than 50 x 50 mm conical type at an interval of not more than 500 mm through out the length of the TPN bus bar. The LT Changeover Switch to accomodate the Civil & DG Supply shall have copper extension links of current carrying cap not less than 1.5 times the rated capacity LT Feede Cable. The extension links shall be supported on DMC / Epoxy insulators having provision for termination of incoming and out going cables.All extension links /interconnection shall be insulated with heat shrinkable colour coaded sleeves. Thecubicle shallhaveabottomchannelof sizeas designed by the manufacturer . A detachable predrilled gland plateof thickness not less than 3 mm thickshould be used at thebottom for entry of armoured cableof adequate size with glands.The above panel shall be front and back openable lockable /openable by key from both side and shall have louvers and air vent gasket for natural flow of air.3 mm XLPE adhesivetype gasket shall be used to make panel weather, dust and vermin proof with IP65 degree of protection , complete as specified and consisting the following switchgears and accessories:- a) Main Incoming MCCB four pole 415 V AC, current rating 400 amps, breaking cap 36 KA at 415 volts. b)Outgoing MCCB Four Pole 415 V AC, current rating(i)4 Pole MCCB 250 Amp, 50 Hz, 415 V with Ics = 80% of Iec, rupturing capacity 35 KA, Make: Havells or Eqt. - 01 Nos (ii)4 Pole MCCB 160 Amp, 50 Hz, 415 V withIcs = 80% of Iec, rupturing capacity 35 KA, Make: Havells or Eqt. - 02 Nos (iii)4 Pole MCCB 125 Amp, 50 Hz, 415 V withIcs = 80% of Iec, rupturing capacity 25 KA, Make: Havells or Eqt. - 02 Nos. \"(c)Outgoing MCB TPN 415 V AC, current rating 63 amps,breaking cap 10 KA at 415 V AC = 02 Nos (d) Outgoing MCB SP 415 V AC, current rating 32 amps,breaking cap 10 KA at 415 V AC = 02 Nos (e) Bus bar electrolytic grade copper strip with heat shrikable sleeves with colour code supported on epoxy resin based insulators, 4 strips of suitable length for current rating 630 amps. |
| 32 | (f) Changeover switch4 pole, 400 Amp Load carrying Capacity, 415V, onload changeover switch inbuild type- 02 Nos(g) LED Multifunction meter flush panel mounting 96x96 mm,having parameters such as V,A,F,PF,KW,KVA,KVAR,KWH,KVAR,neutral currant,% Load,Max Demand(KW&KVA)-01 Nos(Onincoming) (h) LED indicator (R,Y,B) of suitable capacity (i) Complete wiring of the panel board with FRLS PVC insulated multistrand copper conductor cables of suitable current carrying capacity, end terminated with lugs and bolts, nuts and washers of galvanised iron. (j) Current transformer (Bar primary low tension) type CBF-0.6-D1 of suitable CT ratio as per load requirement(k) Installing,commissioning ,testing,earth work PCC etc.Note: Size of panel shall be incorporated at site, only after duly approved by GE. |
| 33 | Supply install, test and commissioning LT Load Panel /DistributionPanel board cubical type outdoor Confirming to IS 8623 Part 1 1993, free floor standing / wall mountingfactory fabricatedmade out of 3.15 mm thick CRCA sheet & suitable size to accomodate all accessories/fittings, compartmentalized in construction to accommodate incoming and outgoingLT cables, Copper bus bars of rating not less 1.5 times the rated cap of incomer LT cable Load Capacity.The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator of size not less than 50 x 50 mm conical type at an interval of not more than 500 mm through out the length of the TPN bus bar. The LT Changeover Switch to accomodate the Civil & DG Supply shall have copper extension links of current carrying cap not less than 1.5 times the rated capacity LT Feede Cable. The extension links shall be supported on DMC / Epoxy insulators having provision for termination of incoming and out going cables.All extension links /interconnection shall be insulated with heat shrinkable colour coaded sleeves. Thecubicle shallhaveabottomchannelof sizeas designed by the manufacturer . A detachable predrilled gland plateof thickness not less than 3 mm thickshould be used at thebottom for entry of armoured cableof adequate size with glands.The above panel shall be front and back openable lockable /openable by key from both side and shall have louvers and air vent gasket for natural flow of air.3 mm XLPE adhesivetype gasket shall be used to make panel weather, dust and vermin proof with IP65 degree of protection , complete as specified and consisting the following switchgears and accessories: ( LGSF, 2223 Sqdn & 2417 Sqdn Living) |
| 34 | (a) Main Incoming MCCB four pole 415 V AC, current rating 320 amps, breaking cap 36 KA at 415 volts (b)Outgoing:-(i) 4 Pole MCCB 160 Amp, 50 Hz, 415 V with Ics = 80% of Iec, rupturing capacity 35 KA, Make: Havells or Eqt. - 04 Nos(c)Outgoing MCB TPN 415 V AC, current rating 63 amps,breaking cap 10 KA at 415 V AC = 03 Nos (e) Bus bar electrolytic grade copper strip with heat shrikable sleeves with colour code supported on epoxy resin based insulators, 4 strips of suitable length for current rating 500 amps.(f)Changeover switch4 pole, 400 Amp Load carrying Capacity, 415V, onload changeover switch inbuild type- 02 Nos(g)LED Multifunction meter flush panel mounting 96x96 mm,having parameters such as V,A,F,PF,KW,KVA,KVAR,KWH,KVAR,neutral currant,% Load,Max Demand(KW&KVA)-01 Nos(Onincoming) (h)LED indicator (R,Y,B) of suitable capacity (i) Complete wiring of the panel board with FRLS PVC insulated multistrand copper conductor cables of suitable current carrying capacity, end terminated with lugs and bolts, nuts and washers of galvanised iron. (j)Current transformer (Bar primary low tension) type CBF-0.6-D1 of suitable CT ratio as per load requirement(k)Installing,commissioning ,testing,earth work PCC etc.Note: Size of panel shall be incorporated at site, only after duly approved by GE |
| 35 | \"Supply install, test and commissioning LT Load Panel / Panel board cubical type indoor Confirming to IS 8623 Part 1 1993, free floor standing / wall mountingfactory fabricatedmade out of 2.0 mm thick CRCA sheet & suitable size to accomodate all accessories/fittings, compartmentalized in construction to accommodate incoming and outgoingLT cables, Copper bus bars of rating not less 1.5 times the rated cap of incomer LT cable Load Capacity.The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator of size not less than 50 x 50 mm conical type at an interval of not more than 500 mm through out the length of the TPN bus bar. The LT Changeover Switch to accomodate the Civil & DG Supply shall have copper extension links of current carrying cap not less than 1.5 times the rated capacity LT Feede Cable. The extension links shall be supported on DMC / Epoxy insulators having provision for termination of incoming and out going cables.All extension links /interconnection shall be insulated with heat shrinkable colour coaded sleeves. Thecubicle shallhaveabottomchannelof sizeas designed by the manufacturer . A detachable predrilled gland plateof thickness not less than 3 mm thickshould be used at thebottom for entry of armoured cableof adequate size with glands.The above panel shall be front and back openable lockable /openable by key from both side and shall have louvers and air vent gasket for natural flow of air.3 mm XLPE adhesivetype gasket shall be used to make panel weather, dust and vermin proof with IP65 degree of protection , complete as specified and consisting the following switchgears and accessories: -(a)Bus bar electrolytic grade copper strip with heat shrikable sleeves with colour code supported on epoxy resin based insulators, 4 strips of suitable length for current rating 630 amps.(b) Changeover switch4 pole, 400 Amp Load carrying Capacity, 415V, onload changeover switch inbuild type - 02 Nos(c) LED Multifunction meter flush panel mounting 96x96 mm,having parameters such as V,A,F,PF,KW,KVA,KVAR,KWH,KVAR,neutral currant,% Load,Max Demand(KW&KVA)-01 Nos (On incoming) (d)LED indicator (R,Y,B) of suitable capacity (e)Complete wiring of the panel board with FRLS PVC insulated multistrand copper conductor cables of suitable current carrying capacity, end terminated with lugs and bolts, nuts and washers of galvanised iron. (f)Current transformer (Bar primary low tension) type CBF-0.6-D1 of suitable CT ratio as per load requirement(g)Installing,commissioning ,testing,earth work PCC etc.Note: Size of panel shall be incorporated at site, only after duly approved by GE. |
| 36 | Supply install, test and commissioning LT Load Panel / Panel board cubical type indoor Confirming to IS 8623 Part 1 1993, free floor standing / wall mountingfactory fabricatedmade out of 2.0 mm thick CRCA sheet & suitable size to accomodate all accessories/fittings, compartmentalized in construction to accommodate incoming and outgoingLT cables, Copper bus bars of rating not less 1.5 times the rated cap of incomer LT cable Load Capacity.The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator of size not less than 50 x 50 mm conical type at an interval of not more than 500 mm through out the length of the TPN bus bar. The LT Changeover Switch to accomodate the Civil & DG Supply shall have copper extension links of current carrying cap not less than 1.5 times the rated capacity LT Feede Cable. The extension links shall be supported on DMC / Epoxy insulators having provision for termination of incoming and out going cables.All extension links /interconnection shall be insulated with heat shrinkable colour coaded sleeves. Thecubicle shallhaveabottomchannelof sizeas designed by the manufacturer . A detachable predrilled gland plateof thickness not less than 3 mm thickshould be used at thebottom for entry of armoured cableof adequate size with glands.The above panel shall be front and back openable lockable /openable by key from both side and shall have louvers and air vent gasket for natural flow of air.3 mm XLPE adhesivetype gasket shall be used to make panel weather, dust and vermin proof with IP65 degree of protection , complete as specified and consisting the following switchgears and accessories( URP) :-(a)Bus bar electrolytic grade copper strip with heat shrikable sleeves with colour code supported on epoxy resin based insulators, 4 strips of suitable length for current rating 400 amps.(b)Changeover switch4 pole, 250 Amp Load carrying Capacity, 415V, onload changeover switch inbuild type -02 Nos(c) LED Multifunction meter flush panel mounting 96x96 mm,having parameters such as V,A,F,PF,KW,KVA,KVAR,KWH,KVAR,neutral currant,% Load,Max Demand(KW&KVA)-01 Nos(Onincoming) (d)LED indicator (R,Y,B) of suitable capacity(e)Complete wiring of the panel board with FRLS PVC insulated multistrand copper conductor cables of suitable current carrying capacity, end terminated with lugs and bolts, nuts and washers of galvanised iron.(f) Current transformer (Bar primary low tension) type CBF-0.6-D1 of suitable CT ratio as per load requirement(g)Installing,commissioning ,testing,earth work PCC etc.Note: Size of panel shall be incorporated at site, only after duly approved by GE. |
| 37 | \"Supply install, test and commissioning LT Load Panel / Panel board cubical type indoor Confirming to IS 8623 Part 1 1993, free floor standing / wall mountingfactory fabricatedmade out of 2.0 mm thick CRCA sheet & suitable size to accomodate all accessories/fittings, compartmentalized in construction to accommodate incoming and outgoingLT cables, Copper bus bars of rating not less 1.5 times the rated cap of incomer LT cable Load Capacity.The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator of size not less than 50 x 50 mm conical type at an interval of not more than 500 mm through out the length of the TPN bus bar. The LT Changeover Switch to accomodate the Civil & DG Supply shall have copper extension links of current carrying cap not less than 1.5 times the rated capacity LT Feede Cable. The extension links shall be supported on DMC / Epoxy insulators having provision for termination of incoming and out going cables.All extension links /interconnection shall be insulated with heat shrinkable colour coaded sleeves. Thecubicle shallhaveabottomchannelof sizeas designed by the manufacturer . A detachable predrilled gland plateof thickness not less than 3 mm thickshould be used at thebottom for entry of armoured cableof adequate size with glands.The above panel shall be front and back openable lockable /openable by key from both side and shall have louvers and air vent gasket for natural flow of air.3 mm XLPE adhesivetype gasket shall be used to make panel weather, dust and vermin proof with IP65 degree of protection , complete as specified and consisting the following switchgears and accessories: -(a)Bus bar electrolytic grade copper strip with heat shrikable sleeves with colour code supported on epoxy resin based insulators, 4 strips of suitable length for current rating 250 amps.(b)Changeover switch4 pole, 200 Amp Load carrying Capacity, 415V, onload changeover switch inbuild type - 02 Nos(c) LED Multifunction meter flush panel mounting 96x96 mm,having parameters such as V,A,F,PF,KW,KVA,KVAR,KWH,KVAR,neutral currant,% Load,Max Demand(KW&KVA)-01 Nos(On incoming) (d)LED indicator (R,Y,B) of suitable capacity(e)Complete wiring of the panel board with FRLS PVC insulated multistrand copper conductor cables of suitable current carrying capacity, end terminated with lugs and bolts, nuts and washers of galvanised iron. (f)Current transformer (Bar primary low tension) type CBF-0.6-D1 of suitable CT ratio as per load requirement(g) Installing,commissioning ,testing,earth work PCC etc. Note: Size of panel shall be incorporated at site, only after duly approved by GE. |
| 38 | Supply install, test and commissioning LT Load Panel / Panel board cubical type indoor Confirming to IS 8623 Part 1 1993, free floor standing / wall mountingfactory fabricatedmade out of 2.0 mm thick CRCA sheet & suitable size to accomodate all accessories/fittings, compartmentalized in construction to accommodate incoming and outgoingLT cables, Copper bus bars of rating not less 1.5 times the rated cap of incomer LT cable Load Capacity.The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator of size not less than 50 x 50 mm conical type at an interval of not more than 500 mm through out the length of the TPN bus bar. The LT Changeover Switch to accomodate the Civil & DG Supply shall have copper extension links of current carrying cap not less than 1.5 times the rated capacity LT Feede Cable. The extension links shall be supported on DMC / Epoxy insulators having provision for termination of incoming and out going cables.All extension links /interconnection shall be insulated with heat shrinkable colour coaded sleeves. Thecubicle shallhaveabottomchannelof sizeas designed by the manufacturer . A detachable predrilled gland plateof thickness not less than 3 mm thickshould be used at thebottom for entry of armoured cableof adequate size with glands.The above panel shall be front and back openable lockable /openable by key from both side and shall have louvers and air vent gasket for natural flow of air.3 mm XLPE adhesivetype gasket shall be used to make panel weather, dust and vermin proof with IP65 degree of protection , complete as specified and consisting the following switchgears and accessories:-(a) Bus bar electrolytic grade copper strip with heat shrikable sleeves with colour code supported on epoxy resin based insulators, 4 strips of suitable length for current rating 800 amps.(b) Changeover switch4 pole, 630 Amp Load carrying Capacity, 415V, onload changeover switch inbuild type -02 Nos(c)LED Multifunction meter flush panel mounting 96x96 mm,having parameters such as V,A,F,PF,KW,KVA,KVAR,KWH,KVAR,neutral currant,% Load,Max Demand(KW&KVA)-01 Nos(Onincoming) (d)LED indicator (R,Y,B) of suitable capacity(e)Complete wiring of the panel board with FRLS PVC insulated multistrand copper conductor cables of suitable current carrying capacity, end terminated with lugs and bolts, nuts and washers of galvanised iron.(f) Current transformer (Bar primary low tension) type CBF-0.6-D1 of suitable CT ratio as per load requirement(g)Installing,commissioning ,testing,earth work PCC etc.Note: Size of panel shall be incorporated at site, only after duly approved by GE. |
| 39 | S&F weather proof outdoor bus bar chamber, made out of 3.15mm thick MS sheet with front & rear Opening, powder coated, dust & vermin proof, IP-66 Protection comprising4 Nosaluminium strips each of 250 Amps, 80cm longhaving 10cm min distance from the body and between bus bars, fixed in steped way duly insulated mounted on epoxy insulators in horizontal position in stepped manner with 4 No’s mounting legs made out of 40mm x 40mm x 6mm angle iron grouted in PCC block(30cm depth below ground level and 60cm above ground level) in cement concrete 1:3:6, type C-2 (using 40mm grade crushed stone aggregate), andone MCCB of 250 Amps, 36 KA as incomer connected with bus bars by means of suitable size of aluminium thimbles, nuts, bolts & washers including cable glands at entry and outlet points including excavation and earth work, returning filling and removal of surplus soils complete all as specified and directed. |
| 40 | S&F weather proof outdoor bus bar chamber, made out of 3.15mm thick MS sheet with front & rear Opening, powder coated, dust & vermin proof, IP-66 Protection comprising4 Nosaluminium strips each of 160 Amps, 80cm longhaving 10cm min distance from the body and between bus bars, fixed in steped way duly insulated mounted on epoxy insulators in horizontal position in stepped manner with 4 No’s mounting legs made out of 40mm x 40mm x 6mm angle iron grouted in PCC block(30cm depth below ground level and 60cm above ground level) in cement concrete 1:3:6, type C-2 (using 40mm grade crushed stone aggregate), andone MCCB of 160 Amps, 25 KA as incomer connected with bus bars by means of suitable size of aluminium thimbles, nuts, bolts & washers including cable glands at entry and outlet points including excavation and earth work, returning filling and removal of surplus soils complete all as specified and directed. |
| 41 | S&F weather proof outdoor bus bar chamber, made out of 3.15mm thick MS sheet with front & rear Opening, powder coated, dust & vermin proof, IP-66 Protection comprising4 Nosaluminium strips each of 125 Amps, 80cm longhaving 10cm min distance from the body and between bus bars, fixed in steped way duly insulated mounted on epoxy insulators in horizontal position in stepped manner with 4 No’s mounting legs made out of 40mm x 40mm x 6mm angle iron grouted in PCC block(30cm depth below ground level and 60cm above ground level) in cement concrete 1:3:6, type C-2 (using 40mm grade crushed stone aggregate), andone MCCB of 125 Amps, 16 KA as incomer connected with bus bars by means of suitable size of aluminium thimbles, nuts, bolts & washers including cable glands at entry and outlet points including excavation and earth work, returning filling and removal of surplus soils complete all as specified and directed. |
| 42 | Material & Labour for Earthing complete with galvanised steel earth electrode plate of size 600mmx600mmx6mm thick, buried directly in ground(earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.50m below normal ground level, connected to galvanised iron strip of size 32mm x 6 mm as earth lead up to test point with suitable GI nuts/bolts and brazed properly up to main board including earth pit in cement concrete (1:2:4) type B-1 (using 20mm graded crushed stone aggregates),40mm thick precast RCC cover in 1:2:4 reinforced with expanded metal(weight not less than 4 kg/sqm), and frame of angle iron 25mmx25mmx6mm with lugs 02 Nos with 6mm dia MS bar handle made to shape, excavation and earth work in any type of soil and including medium grade GI watering pipe 20mm bore with funnel andwire mesh and medium grade GI earth lead protection pipe 40mm bore up to main board complete as shown in electrical plate No 3 of MES Schedule Part-I , connected to earthing testing point and testing on completion complete all as specified anddirected by Engr-in-charge. Note: (i) The unit rate includes GI pipe up to 7.5m for protection of earth lead. For any additional length the same shall be adjusted through deviation order.(ii) The unit rate includesmain earthing lead/strip from earth electrode to test point up to 7.5 meter (iii) In case measured value of earth resistance is recorded more than 5.0 ohms then the earthing shall be redone by the contractor without any extra cost to the department. |
| 43 | Material & Labour for Earthing complete with galvanised steel earth electrode plate of size 600mmx600mmx6mm thick, buried directly in ground(earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.50m below normal ground level, connected to 4mm dia galvanised ironwire as earth lead up to test point with suitable GI nuts/bolts and brazed properly up to main board including earth pit in cement concrete (1:2:4) type B-1 (using 20mm graded crushed stone aggregates),40mm thick precast RCC cover in 1:2:4 reinforced with expanded metal(weight not less than 4 kg/sqm), and frame of angle iron 25mmx25mmx6mm with lugs 02 Nos with 6mm dia MS bar handle made to shape, excavation and earth work in any type of soil and including medium grade GI watering pipe 20mm bore with funnel andwire mesh and medium grade GI earth lead protection pipe 40mm bore up to main board complete as shown in electrical plate No 3 of MES Schedule Part-I , connected to earthing testing point and testing on completion complete all as specified anddirected by Engr-in-charge. Note: (i) The unit rate includes GI pipe up to 7.5m for protection of earth lead. For any additional length the same shall be adjusted through deviation order.(ii) The unit rate includesmain earthing lead/strip from earth electrode to test point up to 7.5 meter (iii) In case measured value of earth resistance is recorded more than 5.0 ohms then the earthing shall be redone by the contractor without any extra cost to the department. |
| 44 | Supply and fixing for earth continuity conductor or main earthing lead/strip fixed to wall or burried in ground or drawn in conduit (pipe/fixed to poles) of any type or any other situation for loop earthing etc with GI Strip of size 32mm x 6mm complete all as specified and as directed . |
| 45 | Supply and fixing for earth continuity conductor or main earthing lead/strip fixed to wall or burried in ground or drawn in conduit (pipe/fixed to poles) of any type or any other situation for loop earthing etc with 4mm dia galvanised iron or steel wire complete all as specified and as directed. |
| 46 | M&L for transformer platform made out of rubble stone masonry with 75mm thick cement concrete 1:2:4 type B-1 nominal mix using 20mm graded stone aggregate with rendering 15mm thick on stone masonary surfaces in cement mortar 1:4 finished even and smooth without using extra cement including necessary excavation, removal, returning filling and cement concrete 1:4:8 type D-2 nominal mix using 40mm graded stone aggregate in foundation chain link fence with gate complete are included in same quoted rate all as specified and as directed by Engr-in-Charge.Note:- Platform for transformer shall be designed as per manufacturer of transformer requirement. However Minimum Size of platform shall be 3.0mx2.5mx1.0m. |
| 47 | Supply and fixing for cable jointing kit for 11 KV (earthed) grade cable for outdoor termination, cold shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size95 sqmm complete all as specified and as directed. |
| 48 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 95 sqmm,Indoor/Outdoor type completeall asspecified and as directed. |
| 49 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size120sqmm,Indoor/Outdoor type completeall asspecified and as directed by Engr-in- charge. |
| 50 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size150 sqmm,Indoor/Outdoor type completeall asspecified and as directed by Engr-in- charge. |
| 51 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 185 sqmm,Indoor/Outdoor type completeall asspecified and as directed by Engr-in- charge. |
| 52 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 400 sqmm,Indoor/Outdoor type completeall asspecified and as directed by Engr-in- charge. |
| 53 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 500 sqmm,Indoor/Outdoor type completeall asspecified & directed. |
| 54 | Supply and errects steel tubular. Swaged pole. 410-SP-55 of 11 meters long conforming to IS-2713 completet with cast iron base plate 400X 400X 5 mm thicks, finial taper bolts nuts and screws complete including painting with two coasts of aluminnimum paintsover a coat of red oxide primer including painting up to 1.50m high from ground level in black & white strips & duly marking/ numberning, completeall as specified &directed by Engineer-in-Charge. |
| 55 | M & L cross arms of M.S channel or angle section etc complete of different sizes brancings, supports,clamps and back plates febricated from structural steel sections incluiding nuts, bolts, washers, wellding, bending cold or hot drilling for bolts in any size or shape as indicated or directed and inclusive of one primer coat , on under coat and one finishing coat of paint complete all as specified and directed by Engr-in-charge. |
| 56 | Supplying and fixing out door, triple pole, gang operated switch single bank, 15 insulators, 11KV tilting type suitable to vertical/horizontal mounting consisting of hot dipped electro plated galvanised channel iron base11 KV, copper/copper alloy tinned contacts, copper or chromium plated MS arcing chains capable of making and breakign the magnetising current complete with horizonatal bar, GI pipe as down level coupling and operating handle with locking arrangements and drop out fuzes working voltage 11000 volts 400 Amps including testing complete all as specified and directed by EIC. |
| 57 | S& F Lighting Arrestor non-lineartype for out door use complete with all fittings transmission class discharge capacity 65 kilo Amps suitable for 11000 V including bracket, clamps, nuts and washers and connecting to earth wire complete all as specified and directed by EIC. |
| 58 | S & F Danger Notice plate of 1.6 mm thick ,mild steel sheet, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with MS Clamp, bolts and nuts of approved size for HT 25X20 cm complete, all specified and directed |
| 59 | S & F Stay assembly complete with accessories as shown in electrical plate No. 1 (loop type insulator, stay clamps, excavation and concrete measured separately) of size 16 mm dia. |
| 60 | S & F Loop type insulator, vitreous porcelain, white, brown or green: Small size, with overall dimensions65 x 90mm, clearance of hole 16mm complete, all specified and directed. |
| 61 | S & F Galvanised stay strand, 7/4mm complete, all specified and directed. |
| 62 | S & F Cable route indicator for HT Cables include PCC Work complete, all as specified and directed.Note:- The cable route indicator shall be with circular minimum dia 150 mm and minimum 6 mm thick cast iron plate embossed with \"HT cable\" riveted to angle iron of (25mm x 25mm x 5mm) of length minimum 60 cm and embedded in PCC 1:2:4 foundation of 30 cm x 30cm x 30cm. completeall as specified &directed by Engineer-in-Charge. |
| 63 | S & F Cable route indicator for LT Cables include PCC Work complete, all as specified and directed.Note:- The cable route indicator shall be with circular minimum dia 150 mm and minimum 6 mm thick cast iron plate embossed with \"LT cable\" riveted to angle iron of (25mm x 25mm x 5mm) of length minimum 60 cm and embedded in PCC 1:2:4 foundation of 30 cm x 30cm x 30cm. completeall as specified . |
| 64 | M & L for surface excavation n. exc 30 cm deep and avg 15 cm deep and out in hard rock and soft and loose soil all asas specified and directed. |
| 65 | M & L for for 75mm thick PCC 1:5:10 , Nominal mix, type E-2 (using 40 mm graded crushed stione aggregate) as in foundations, filling and mass concrete, complete all asas specified and directed . |
| 66 | M & L for for 25mm thick sandfilling as cushoining for laying of paver block, under floors or in foundations including watering and consolidation all as spcified and directed directed.Note : Punned thickness of sand shall be measured and paid. |
| 67 | M & L formachine pressed precast concrete interlocking paver block any shape and size confirming to IS 15658-2006 of 60mm thickness, M-35 Grade with grey cement and pigment as approved by GE and as manufracture instruction complete all as specified. (Shape, size & colour will be approved by GE) |
| 68 | Excavating in post holes in Hard soil each n.exc 0.5 cum getting out hard/dense soil, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25cm. |
| 69 | M&L cement concrete 1:2:4 type B-2 nominal mix (using 40mm graded crushed stone aggregate) in foundation , footing, post holes etc complete all as specified. |
| 70 | S&F mild steel section and embedding in concrete, posts or struts in fencing including cutting tops to shape as directed drilling holes notching for wire etc. flat iron fillets (for securing wire mesh) including all necessary drilling , bolting etc and similar work conforming to Fe-410-0). |
| 71 | M&L Mild steel roundbars 10mm dia and over cut of legnth, bent to shape required, including ranking bending to chanin link fencing and binding with and inlcuding mild steel wire (annealed ) not less than 0.9 mm dia or securing with clips quality (Fe-W (Gde.E-250) quality A or Fe-290 (Gde-E-165). |
| 72 | S&F mild steel screw bolt (machine made) with hexagonal or square heads at one end and screwed the other each screwed end to be fitted with washersand one hexagonal nut but length of bolt exc. 5cm and n. exc. 10cm long and bolt one side embedded in concrete posts etc complete to fix fencing wire dia of shank11 to15mm complete. |
| 73 | Supply only MS galvanised chain link fencing, 3.8mm diaand pitch of fencing 50mm (Weight not more than 4 Kg/Sqm) including line wire any mesh, size as directed as in fencing complete all as specified and as directed. |
| 74 | Fixing only Chain link fencing including line wires,any mesh, size and type to any standards,rails straining bolts, etc. including provision of binding wire. |
| 75 | S&F for Galvanised 2 strand, steel barbed wire 2.24mm dia barbed with 2mm dia barbs at 75mm spacings and straining and fixing to any type of standard rails straining bolts, including, securing or tying at crossings with and provision of galvanised mild steel wire, staples or steel pins, etc. as directed (each line wire to be measured) |
| 76 | M&L painting new steel surface of any description over 10cm width or grith not otherwise described including preparation, priming with zinc chromateand two coats of synthetic enamel paint complete. Note:- Painting on steel work to be done before execution. |
| 77 | S & F steel work of Fe-410-W(Gde- E-250) quality-B Mild steel plates, plain or chequered, 5mm thick or over in thickness in available sizes complete all as specified and as directed by Engineer-in-charge. |
| 78 | S & F for Steel work in tubular pipes (vertical poles / trusses / purlins / Rafter) including welding etc. complete using ERW or induction butt welded tubes conforming to I.S.1161-1979 grade St.-240 complete all as specified and directed |
| 79 | S & F for Framed work Fe-410-W(Gde-E-250) quality B as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing incl sliding door bolt, steel handles..etc, complete, all as specified and directed by Engineer-in-charge. |
| 80 | S & F for Framed work such as grills, gratings, etc.. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe.290.Gde-E-165 complete, all as specified and directed by Engineer-in-charge. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail