| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 2 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C |
| 3 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 4 | 3 x 1.5 sq. mm |
| 5 | 3 x 2.5 sq. mm |
| 6 | 3 x 4 sq. mm |
| 7 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 8 | 20 mm |
| 9 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 10 | 63 A |
| 11 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 12 | 8 way , Double door |
| 13 | 16 way , Double door |
| 14 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 15 | Single pole |
| 16 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 17 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 18 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. |
| 19 | 3 Module |
| 20 | 12 Module |
| 21 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 22 | 5/6 amp switch |
| 23 | 3 pin 5/6 amp socket outlet |
| 24 | 15/16 amps switch |
| 25 | 6 pin 15/16 amps socket outlet |
| 26 | Laying of one number pvc insulated and PVC sheathed/ XLPE power cable of 1.1 kv grade of following size on the wall surface as required Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 27 | Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required. 150 mm X 75 mm X 60 mm deep |
| 28 | Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required. 180 mm X 100 mm X 60 mm deep |
| 29 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 30 | Supplying, installation, Testing & Commissioning of LED surface mountedBatten light of following body materialand construction as per IS : 10322 withdriver (Replaceable)as per the requirement with Driver efficiency >85% ,Operating voltage AC140-270 Volt,freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20,CRI>80, Flicker free, (flickershould be below 5 %), life time (LED,Driver & electrical circuitary), ofminimum 50000BurningHourswith,70%ofinitial Lumenmaintained tilllife ends, CCT3000°K/ 4000°K/5700°K /6000°K/6500°K(AsperANSIBin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BISstandard andtrade markcertificate(T.C.).Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. completeinallrespecti/cconnectionswith1.5sqmmFRLS,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy≥105 <120lm/Watt output . LM79 & LM80 Test reportfromNABLlab foralltestingrequiredforLED fixtures as per BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement:heatsinkofaluminumhousing such that LED junction temperature shall not rise above 90°C). |
| 31 | 18- 22 watt |
| 32 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req |
| 33 | 1400mm, service value ≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum) |
| 34 | Supply of 250mm (10inch) sweep 1250 rpm exhaust fan Fresh Air Type complete with shutter blades etc. as required. |
| 35 | Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-45, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP66,IK-10, CRI >80 , under voltage and over voltage protection, EMI EMCas per CISPR -15 , lenses for beam angle 30 deg-120deg as per the application and the project requirement deg., suitable tilt able fitting, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy 105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). |
| 36 | 70 watt |
| 37 | P/F of 4.5 Kg CO2 Type Fire Extinguisher Squeeze Grip Type Trolly Wheel as well Mounting Type Complite in All Respectwith isi mark i/c fixing arragement etc as required. |
| 38 | Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS) system suitable for Single Phase input, Single Phase output AC Supply. The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. The UPS systems shall be Microprocessor based Digital Control, using Insulated Gate Bipolar Transistor (IGBT)\"s both for the rectifier & inverter with PWM (Pulse Width Modulation) Technology. The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >95% at 100% non-linear loads. Current total harmonic distortion (ITHD)/ total demand distortion (TDD) on the input grid shall be < 5% at 100 %load. (The required LC filters shall be included in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ) however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC single phase 160-270V 50 Hz and delivering output AC supply true sine wave single phase 220/230/240 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins and 150% for 1 minute. Operating temperature 0 to 40 deg C, Relative humidity 0-95% non condensing, noise level less than 60db at 1 meter distance, Protection for Under voltage, over voltage, abnormal output voltage, battery over charging, output over current, short circuit, battery deep discharge , 10 KV surge. Display for watt/VA,Amp and Voltage power parameters etc. UPS shall comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI) type UPS (as per standard IEC 62040-1, 2 & 3) . The UPS should be with IGBT Based Inverter Technology, Communication RS232/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge. Required battery racks, DC breaker of suitable rating and interconnecting copper conductor cable of suitable size and connectors and all required accoseries are inclusive in the cost. The UPS should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc |
| 39 | 2KVA |
| 40 | Supply , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R 407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply: Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). |
| 41 | 1.5 TR with 5 Star BEE Rating |
| 42 | S/I/T/C of stand for split AC |
| 43 | S/I/T/C of copper pipe for split AC |
| 44 | S/I/T/C of Drain Pipe |
| 45 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \"C\" curve including connections, painting etc. as required. |
| 46 | Supply of wall mountingfollowing KVA voltage stabilizersuitable for 230 volt 50 Hz s/ phase AC supply etc. as reqd.4 KVA |
| 47 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \"C\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 48 | SITC of full HD LED Monitor,55 INCHES complying with the following specifications: Resolution : Full HD : 1920 x 1080 or better Backlight : LED Brightness : 300 NITS min. Contrast : 1200 : 1 or better Power supply : 230v + / - 10%, 50 Hz at site with connections and along with all accessories etc. complete as required. |
| 49 | Supply & Installation of wall mounted RO plus UV plus UF water purifier with up to 20 L/hr purification capacity and storage tank up to 09 liter capacity. |
| 50 | Supplying and fixing of full stainless steel body self-contained drinking water cooler with cooling capacity 150ltr per hr, storage capacity 150ltr and suitable for 230V supply as required. |
| 51 | Supply of XLPE insulated PVC sheathed Al. conductor armoured cable for working voltage up to 1.1 kv confirming to IS 7098(part-1) of following size :- 2C x 10 sq mm |
| 52 | S/I/T/C of 2MP fixed lensDOME IP Camera with following specifications:-Image Sensor: 1/32MP CMOS or better**Minimum Illumination: 0.08 lux color, 0 lux with IR or better ** Shutter Speed:1/3 – 1/100,000 sFrame Rate:1-25 fps or better **Lens: 2.8 Fixed Video Compression: H.265 or better ** S/N Ratio: >45dB Resolution: (1920x1080) or better Protocol: should comply to IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNS, IEEE802.1XIR Range: Minimum 25mOperating Temperature: -20 to 55 deg CentWeatherproof Standard:IP66 or better **Safety standard: UL. |
| 53 | SITC of 2MP fixed lens Bullet IP Camera with following specifications:-Image Sensor: 1/3 2MP CMOS or better**Minimum Illumination: 0.08 lux color, 0 lux with IR or better **Shutter Speed:1/3 – 1/100,000 sFrame Rate: 1-25/30 fps or better **Lens: 2.8mm fixedVideo Compression: H.265 or better **S/N Ratio: >45dBResolution: (1920x1080) or better **Protocol: should comply to IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNS, IEEE802.1XIR Range: Minimum 30mOperating Temperature: -30 to 50 deg CentWeatherproof Standard:IP66 or better **Safety standard: UL |
| 54 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable . |
| 55 | SITC of IP65 box(without PoE switches)of dimention 310mmX160mmX140 mm onpole or wall with suitable arrangement for support/installation of 8 port Giga PoE switch and 1 nos. 15/16 amp modular switch socket set. |
| 56 | SITC of metal clad, powder coated, compartmentalized cubical panel board as per CPWD electrical specifications including insulated aluminum bus bars, supports,interconnection, erection of switch gears with depth 30 cm to 60 cm and making provisions for termination of incoming/ outgoing cables/ bus ducting and making foundation etc as required. (Suitable for 400 Amp TPN) |
| 57 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 125A 36KA,FPMCCB |
| 58 | P/FHot press sheet mouldedcompound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof polebox of innerdimension 200x160x98mm (NS) complete with suitable arrangement for fixing of 2 nosof 6 to 32 amp single pole MCB & 63 Amp. Doublepole isolator (MCB/Isolator excluded) withneutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plateofsuitable size with danger monogram property printed on the coveretc asreqd. |
| 59 | Comprehensive AMC of stainless steel body self-contained drinking water cooler with cooling capacity 150 ltr hr, storage capacity 150 ltr and suitable for 230V supply as required for one year after completion of 1 year warranty i.e.repair of compresser defective part including condenser coil/ condenser motor/discharge coil/running capacitor/Thermostate switch/float valve/motor capacitor/condenser fan blade/gas charging/as per requirement complete as required including material and servicing for proper functioning of water cooler. |
| 60 | Comrehensive AMC of wall mounted reverse osmosis (R.O.) plus UV plus UF water purifier with up to 50lt/hr purification capacity and storage tank up to 9 litres capacity for one year after completion of 1 year warranty with replacement of defective parts including carbon candle/ RO membrane /span filter or solenoid valve /CTO/SMPS/UV tube/choke/RO pump/circuit board etc. |
| 61 | SITC of Single phase Monoblock Pump SetComplite With all accsories Workable on 240/415 V,50 Hz AC supply (a)1 Hp (0.75 kw) single phase pump set,head fro 12-30 meter Suction and Delivery 25X25mm. |