| 1 | Taking down carefully existing points wiring on surface conduit/concealed conduit forlight/ fan/socket /power/bell from wall & roof along with fitting and fixtures such as switches, sockets, ceiling roses, batten holders, unserviceable light fittings, piece of wires,gutties, conduit, wooden boards etc and making good the disturbed portion ofwalls, ceiling etc all as specified and directed Engr-in-charge. |
| 2 | M & L for Point wiring with 1.5 sqmm PVC insulated and unsheathed FRLSH single core multi-stranded copper conductor for one light/fan in new PVC conduit to be terminated in pressed steel terminal boxes with top cover plateincluding 1.5 sqmm PVC insulated and unsheathed FRLSH single core multi-stranded copper earth continuity conductor connected to cmmon earth dolly controlled by one switch and/or one regulator complete including repairing the surfaces in CM 1:3 and finishing the surface as per existing treatment all as specified and directedby Engineer in-charge Note-I-(Switches and regulators shall be measured and paid for separately). Note-II- ( Wiring shall be done as per colour code in IS for phase, neutral and earth). Note-III- (The cost of modular cover plate, blank plate and metal flush boxes is deemed to be included in the unit rate quoted for this item).Note -IV - cost of Eye/bottle thimblesused for connection in switches/sockets & MCBs in DBs is deemed to be included in the unit rate quoted for this item. Note:- V- Rate of cutting chasing included in the unit rate quoted for this item |
| 3 | M & L for point wiring with 1.5 sqmm PVC insulated and unsheathed FRLSH single core multi-stranded copper conductor for one light point controlled by 2 way and including PVC rigid concealed conduit medium grade 19/20 mm dia to be terminated in pressed steel terminal boxes with top cover plateincluding 1.5 sqmmPVC insulated and unsheathed FRLSH single core multi-stranded copper earth continuity conductor connected to cmmon earth dollycontrolled by one switch and/or one regulator complete including repairing the surfaces in CM 1:3 and finishing the surface as per existing treatment all as specified and directed.Note-I- ( Wiring shall be done as per colour code in IS for phase, neutral and earth). Note-II- (The cost of modular cover plate, blank plate and metal flush boxes is deemed to be included in the unit rate quoted for this item). Note -III - cost of Eye/bottle thimblesused for connection for 2 way switch is deemed to be included in the unit rate quoted for this item. Note:-III- Rate of cutting chasing included in the unit rate quoted for this item |
| 4 | All as per Sl item No 2.00 above herein before but one socket out let 5 pins 5 Amp on the same board with other switches complete all as specified and directed. |
| 5 | All as per Sl item No 2.00 above herein before but for one socket out let 5 pins 5 Amp on independent board complete all as specified and directed. |
| 6 | All as per item No.2.00 herein beforebut 2.5 Sqmm PVC insulated and unsheathed FRLSH single core multistranded copper conductor incl 2.5 Sqmm PVC insulated and unsheathed FRLSH single core muilti-stranded copperearth wire for switch socket combination 3 pin 15 amps on independent board. |
| 7 | M & L for Point wiring with 1.5 sqmm PVC insulated and unsheathed FRLSH single core multi-stranded copper conductor for one light/fan in existing conduit to be terminated in pressed steel terminal boxes with top cover plateincluding 1.5 sqmm PVC insulated and unsheathed FRLSH single core multi-stranded copper earth continuity conductor connected to cmmon earth dollycontrolled by one switch and/or one regulator complete including repairing the surfaces in CM 1:3 and finishing the surface as per existing treatment all as specified and directedby Engineer iin-charge Note-I-(Switches and regulators shall be measured and paid for separately). Note-II- ( Wiring shall be done as per colour code in IS for phase, neutral and earth). Note-III- (The cost ofmodular cover plate and metal flush boxes is deemed to be included in the unit rate quoted for this item). Note -IV - cost of Eye/bottle thimblesused for connection in switches/sockets & MCBs in DBs is deemed to be included in the unit rate quoted for this item. |
| 8 | All as per Sl item No 7.00 above herein before but one socket out let 5 pins 5 Amp on the same board with other switches complete all as specified and directed. |
| 9 | All as per Sl item No 7.00 above herein before but for one socket out let 5 pins 5 Amp on independent board complete all as specified and directed. |
| 10 | All as per item No 7.00 herein beforebut 2.5 Sqmm PVC insulated and unsheathed FRLSH single core multistranded copper conductor incl 2.5 Sqmm PVC insulated and unsheathed FRLSH single core muilti-strandedcopper earth wire for switch socket combination 3 pin 15 amps on independent board. |
| 11 | Supply and fix in replacement of Modularswitch1 way, 6 Amps, 1 module complete all as specified and directed by Engr-in-charge. |
| 12 | Supply and fix in replacement of Modularswitch1 way, 16 Amps, 1 module complete all as specified and directed by Engr-in-charge. |
| 13 | Supply and fix in replacement of Modularswitch2 way, 6 Amps, 1 module complete all as specified and directed. |
| 14 | Supply and fix in replacement of ModularBell switch1 way, 6 Amps, 1 module complete all as specified.and directed by Engr-in-charge. |
| 15 | S & F Bell ding dong electronic complete all as specified and directed by Engineer-in-charge. |
| 16 | Supply and fix in replacement of Modular socket 5 pin 6 Amps, 2 module complete all as specified and directed by Engr-in-charge. |
| 17 | Supply and fix in replacement of Modularsocket 5 pin 6/16 Amps, combination type2 module complete all as specified and directed by Engr-in-charge. |
| 18 | Supply and fix in replacement of Fan regulator modular type 2 module complete all as specified and directed by Engr-in-charge. |
| 19 | Ceiling rose surface bakelite surface 65 x 50mm3 terminals all as specified & directed by Engr-in-charge. |
| 20 | Material and labour for in replacement angular typelamp holder, PVC/ polycarbonate type with back plate suitable for 7 to 23 watts for batten fitting, including plastic square board of required size, complete all as specified and directed. |
| 21 | S&F Ceiling/surface mounted Slim design LEDround Downlight with Superior light output and internal driver 9/10 Watts 230 volts with internally pre-wired and including connecting up with two core twisted flexible copper conductor cable with suitable size compelte all as specified and directed by Engineer-in-Charge. |
| 22 | S & F LED high bay/medium bay luminaire 80 watt with external electronic driver , IP-65,indoor type input voltage range 120-270 volts with provision of 3 core copperconductor cable 1.5 Sqmm size from connector/ceiling rose to fitting with fixing arrangement as per site requirement/conditions and including removing old unserviceable fittingcomplete all as specified and as directed by the Engr-in-charge. |
| 23 | S & F LED high bay/medium bay luminaire 120 watt with external electronic driver , IP-65,indoor type input voltage range 120-270 volts with provision of 3 core copperconductor cable 1.5 Sqmm size from connector/ceiling rose to fitting with fixing arrangement as per site requirement/conditions and including removing old unserviceable fittingcomplete all as specified and as directed by the Engr-in-charge. |
| 24 | S & F in replacement of MCB, TRIPLE pole & neutral (TPN) 10 KA 240 volts 40 to 63 Amp capacity fixing in DB’s complete all as specified and directed. (Note: MCB should be B or C curve as directed by engineer in charge) |
| 25 | S & F in replacement of Sheet metal enclosureDB TPN 4 ways double door 415 volts with 200 Amps standard bus bar of suitable size and common neutral link flush mounting type, drilling holes for incoming and out going cables complete with IP-43 protection complete all as specified and directedby Engr-in-charge |
| 26 | Supply and fixing LED batten fitting 18-20 watt, 4 feet, PVC housing with electronic driver cool/warm type completeconnecting with copper conductor flexible cablefrom ceiling rose to connector of the lightas in repaircomplete all as specified and as directed by the Engineer-in-Charge. |
| 27 | Supply and fixing LED batten fitting 10-12 watt, 2 feet, PVC housing with electronic driver, including LED luminaire 10/12 watt cool/warm type connecting with copper conductor flexible cablefrom ceiling rose to connector of the lightas in repair complete all as specified and as directed by the Engineer-in-Charge. |
| 28 | S&F asin repair 9/12 watt LED light fitting wall mounting fixture wooden finish (sketch type) including LED lamp 9 watt compact and energy efficient epoxy powder coated luminaire and connecting with copper conductor flexible cablefrom ceiling rose to connector of the light complete including removing unserviceable light fittings all as specified and as directed by the Engineer-in-Charge. |
| 29 | Cutting of hardstanding floor/wall for laying of cable including matching with suface by using cement concrete all as specified and directed.Note:- Necessary concrete work to be measured and paid separately. |
| 30 | Supply and fix Modularswitch in repair 1 way, 6 Amps, 1 module, 230 voltsmake and fitment as per gound requirement complete all as specified.NOTE-contractor shall visit the site to check make and size of item. |
| 31 | Supply and fix Modularswitch in repair1 way, 16 Amps, 1 module, 230 volts complete all as specified. NOTE-contractor shall visit the site to check make and size of item. |
| 32 | Supply and fix Modular socket in repair 5 pin 6 Amps, 2 module 230 volts complete all as specified. NOTE-contractor shall visit the site to check make and size of item. |
| 33 | Supply and fix Modularsocket in repair 5 pin 6 &16 Amps, combination type2 module complete all as specified. NOTE-contractor shall visit the site to check make and size of item. |
| 34 | Supply and fix in replacement of metal flush box of 2 modulein MAP qtrs complete all as specified and directed. |
| 35 | Supply and fix in replacement of metal flush box of 3 modulein MAP qtrscomplete all as specified and directed. |
| 36 | Supply and fix in replacement of metal flush box of 4 modulein MAP qtrscomplete all as specified and directed. |
| 37 | Supply and fix in replacement of metal flush box of 6 modulein MAP qtrscomplete all as specified and directed. |
| 38 | Supply and fix in replacement of metal flush box of 8 modulein MAP qtrscomplete all as specified and directed. |
| 39 | Supply and fix in replacement of modular cover plate of 2 module in MAP qtrscomplete all as specified and directed. |
| 40 | Supply and fix in replacement of modular cover plate of 3 module in MAP qtrscomplete all as specified and directed. |
| 41 | Supply and fix in replacement of modular cover plate of 4 module in MAP qtrscomplete all as specified and directed. |
| 42 | Supply and fix in replacement of modular cover plate of 6 module in MAP qtrscomplete all as specified and directed. |
| 43 | Supply and fix in replacement of modular cover plate of 8 module in MAP qtrscomplete all as specified and directed. |
| 44 | Material and labour for PCC 1:3:6 type C-2 using 20 mm graded stone aggregate for certain works (filling tha gap around DB VTPN) including neccassory form work and finishing the surface fair and even without using extra cement all as directed and specified. |
| 45 | Supply and fix epoxy power coated MCCB distribution distribution box double door VTPN 6 way vertical type AC 415 V with IP 43 protection for MCCBs alongwith provision of MCCB as incomer with common bus-bar rated 300 Amp at incoming end of outgoing MCCBs grouted/ flush to wall, complete all as specified by Engineer-in-charge. (Note : (i) Cost of Eye/bottle thimbles used MCCBs in VTPN 6 way shall deemed to be included in unit rate quoted for this items, (ii) Electric wiring should be done in proper colour coding i.e. Red for phase, Black for neutral and Green for Earth (iii) Connection of cable with VTPN shall be done through appropriate size of Al thimble incl disconnecting and taking down old unsv MCCB DB VTPN of any description.INCOMING:- (a) MCCB 200 Amps, adjustable thermal and magnetic type 4 pole, 415 Volts, 25 KA-01 Nos (Ultimate breaking capacity ICs -Icu = 100 %) .OUT GOING:- (a) MCCB 63 amps, adjustable thermal and magnetic type 4 pole, 415 Volts, 16 KA --- 06 Nos. |
| 46 | M & L for Sub main wiring with 04 (Four) single core 10.0 Sqmm PVC insulated and unsheathed FRLSH,stranded copper conductor cable drawn throughpvc concealed conduit of suitable dia including 6.0 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note1:- 4 Runsof 10.00 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Runof 6.00 Sqmm Copper conductor Earth wire shall be measured as one unit) Note2 : Rate quoted for this item shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of suitable size dia with tees, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc.(ii) Cutting chases, pinning in and making good to facing where requiredpointing in cement mortar 1:3 to match theexisting surfaces and cutting not exc. 10 cm girth. (iii) Taking down/out existing unserviceable sub main wiring.(iv) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB. |
| 47 | Material and labour for new rotor assembly complete of any size with super enameled copper wire of existing gauge incuding varnishing and drying complete reassembling & testing complete of size 1200mm sweep complete all as specified and directed.NOTE foritem ser No 1 to 6 : -(i) Fans to be repaired will be handed over to contractor at MES store yard after cutting the burnt winding in presence of Engineer-in-charge and cost of cutting of winding shall be included in the quoted rate.(ii) The cost of shifting the fan from MES store yard to contractors workshop andback shall be included in the item.(iii) Fans will be issued to the contractor in lots of 10 Nos and more for which, contractor shall ensure that minimum lot of 10 number each be returned to the department on every fifth day from the issue of fans after carried out rewinding and other repair,in failing so, the amount @ Rs. 20/- per fan per day shall be deductedfrom the contractor due till the returning of fan duly tested. |
| 48 | Material and labour for new rotor assembly complete of ceiling fan of any size with super enameled copper wire of existing gauge incuding varnishing and drying complete reassembling & testing complete of size 1400mm sweep complete all as specified and directed. |
| 49 | Dismantling of wall mounting/Cabin fan 380/400mm sweep, (any make and type , taking out rotor, removing all coils (burnt and alive), rewinding all the coils with suitable size super enamelled copper wire (ISI Marked) including all packing materials, insulating materials, varnishing, greasing, oil, re-assembling, split pins,body/blade screws and testing on full speed,. as per the direction of Engineer-in-Charge complete all as specified and directed. |
| 50 | Dismantling of industrial wall mounting air circulator fan 450/600mm sweep, (any make and type , taking out rotor, removing all coils (burnt and alive), rewinding all the coils with suitable size super enamelled copper wire (ISI Marked) including all packing materials, insulating materials, varnishing, greasing, oil, re-assembling, split pins,body/blade screws and testing on full speed,. as per the direction of Engineer-in-Charge complete all as specified and directed. |
| 51 | Supply and replacement ofindustrial wall mounted fan motor suitable for 450/600mm sweep complete including necessary fitting & connection. (Make:Khaitan/Cool home/Crompton Greaves |
| 52 | Opening up ceiling fan, exhaust fans, wall mounting (any sweep, size or make) as kept unserviceable in E/M store yard for detection of defect and reassembling after cleaning, greasing and overhauling including replacement of split pins, body/blade screws and testing before depositing in store yard complete all as specified and directed. Note: Other spares necessary to be replaced shall be measured and paid for separately under following items of this schedule. |
| 53 | Supply and fix in replacement of Capacitor 2.5/3.15 mfd 230 Volts (+) 5 % dry type complete all as specified and directed. Make- TIBCON/ELCAP/\"AD/TORCON) |
| 54 | Supply and fixing PVC capacitor assy two ways with fixing screwsany type all as specified and directed |
| 55 | Supply and fix in replacement of capacitor suitable for PVC Exhaust fan motor 1.5 mfd 230 volts (+) 5 % dry complete all as specified and directed. Make- TIBCON/ELCAP/\"AD/TORCON) |
| 56 | Supply and replacement of ball bearing for ceiling fans of any sweep/size/ any make complete all as specified and directed. Size of 6200,6201,6202,6203,6204 & size S-7/S-8 (Make of bearing : Make ABC/SKF/NBC.Note : Ball bearing shall be replaced in the store yard of E/M or in the civil workshop on lathe machine if required and cost thereof shall be included under this item. |
| 57 | Replacement of gun metal bush for ceiling fans, exhaust fans and cabinsfans of any makes/size complete all as of specified and directed.Note : Bush shall be replaced in the store yard of E/M or in the civil workshop on lathe machine if required and cost thereof shall be included under this item.Note:- Cost of replacement of UNSV Shaft for exhaust fan of capacity 200/300mm sweep shall be included under this item. |
| 58 | Taking down and refixing of ceiling fan after supply and replacement of hanging assembly set comprising of rubber reels , mild steel clamps, nuts, bolts with one lock hole and lock pins suitable for any types of fans and rodscomplete all as specifiedand directed by Engr-in-charge.Note:-Contractor has to submit the certificateregarding serviceable condition of rubber reel, fan hook, clamp hook and split pin of ceiling fan. |
| 59 | Replacement of ceiling fan blade (multipurpose type) suitable for 1200 mm sweep ceiling fan including nuts, washers etc complete all as specified and directed suitable for any make of fan. (white/Browm colour/as per site requirement). |
| 60 | Supplyand connecting flexible Cable of copper wire 2 core of size 23/0.0076, 0.5 sq mm (white colour)complete. |
| 61 | Supplyand connecting flexible Cable of copper wire 2 core of size 40/0.0076, 0.5 sq mm (white colour)complete. |
| 62 | Supply & fixing as in old/damaged body ofwall mounted Fan including exhaust fan blade made of steel properly painted with all fixtures make as same of motor andsize upto 450/600 mm all as directed by Engineer-in-Charge. |
| 63 | S&F in replacement louver shutter made out of 0.63 mm galvanised iron sheet for exhaust fan of 300/250 mm sweep size round or square as per site condition including fixing arrangement with fixing material complete all as specifed and directed. |
| 64 | Replacement ofPVC canopy (upper/bottom) for ceiling fan of any make andsize all as directed by Engineer-in-Charge. |
| 65 | Supply & fixing down rodfor ceiling fans made out of MS pipe 15mm bore medium grade 60 cm long duly threaded, holes drilled and spray painted with synthetic enamel paint all as directed by Engr-in-Charge |
| 66 | Supply & fixing down rodfor ceiling fans made out of MS pipe 15mm bore medium grade 1.2 m long duly threaded, holes drilled and spray painted with synthetic enamel paint all as directed by Engr-in-Charge |
| 67 | Material and labour for painting of ceiling fan using synthetic enamel paint in two coats over a coat of primer of any make/sweep/model etc after cleaning/washing and fill up cavities using filler including writing MES NO Black Colour complete all as specified and directed. |
| 68 | Spray painting on outside body of the exhaustfan incl blades any size with synthetic enamel paint(smoke gray colour) including scrapping existing paint and incl writing MES Number with black paint all as directed. |
| 69 | Supply and fix ceiling fan box round cover plate size 6 inch complete all as specified and directed by Engr-in-chrge. |
| 70 | Supply and fixing in replacement by cutting sizes water proof plywood ISI Marked, 12mm thick,of required size incl necessary provisions for mounting in walls, openings and securing using fasteners 10 cms long and 8 mm dia for mounting of exhaust fans in various locations and sizes as directed. |
| 71 | S&F MS screw for fixing of ceiling fan blade of any size and type complete all as specified and directed. |
| 72 | Supply & fixing in replacement of NEW PCB unit of suitable size of existing make and description of make (Bajaj) for BLDC ceiling fan of 1200 mm sweep, single phase 240 V complete all as specified and directed by the Eng-in-charge. Note : PCB will be replaced by concerned OEM only and OEM bill will be submit at the time of payment |
| 73 | Supply & fixing in replacement of NEW PCB unit of suitable size of existing make and description of make Khaitan for BLDC ceiling fan of 1200 mm sweep, single phase 240 V complete all as specified and directed by the Eng-in-charge. Note : PCB will be replaced by concerned OEM only and OEM bill will be submit at the time of payment |
| 74 | Supply & fixing in replacement of NEW PCB unit of suitable size of existing make and description of make (Halonix ) for BLDC ceiling fan of 1200 mm sweep, single phase 240 V complete all as specified and directed by the Eng-in-charge. Note : PCB will be replaced by concerned OEM only and OEM bill will be submit at the time of payment |
| 75 | S&F45W 3000K Ring Type decorative Post Top Light, Pressure Cast aluminium PU Painted housing with casted aluminium heat sink, having Optical grade PC diffuser with Symmetrical arrangement of LED\"s. Suitable for upto 076mm OD pole.Light fixture should be protected by in-Built Surge protection of 4kV and External Surge protection of 10kV. Light should be rated with IP65 and IK08. Operating temperature range of light should be -10°C to +50°C.Make: BAJAJ (BGCPNP 45W LED WW-ARCHNER PLUS POST TOP),Havells, Phillipsand S&F3 Mtr Clear height Decorative Ornamental Pole duly PU (Poly Urethane) Painted (RAL color code as per client choice), made of high tensile Steel Pipe, Galvanised before PU Painting. Pole shall be in minimum 2 Sections, where Bottom section dia-114mm minimum upto 1200mm height from base plate. Top section dia-60mm minimum.The Top section of pole must have Cast Aluminium Embleshments throughout the length.Base Plate size 200x200x10mm with PCD of 200mm. Foundation bolts set of M16x450mmx 4 Nos made of EN8 grade steel should be used only for erection. A lockable door of suitabe size should be provided at bottom section for termination and connection with provision of mounting backelite sheet and connector, MCB SP, 10 amps,240 Volts, 10 KA, \"C\" curve rating including RCC base etc.Similar to Bajaj Model No- BJPL ECO 3M PT Pole or equivalent in halonixNote: Manufacturer should have their own manufacturing and galvanising plant ,the certificate for the same should be submitted by contractor prior to purchase. Poles and post top lights should be of same make Make: Bajaj,Havells, Phillips |
| 76 | Supply and fixing of inverter LED security light luminaire 30 watt , pressure die cast aluminum housing, toughened heat resistant glass, IP66 protection, better optics for uniform distribution with multiplte LEDshaving optical grade polycarbonate lens with 4 hours battery back up all accessories internally pre wired and including connecting up with two core 1.5 sq mmcopper conductor cable from connector to ceiling rose to connection of lightwith GI bracket of suitable size and clamps with fixing accessories including disconnecting and taking down oldunserviceable security light fitting of any description and in any position complete all as specified and directed.Make: Halonix cat ref no LED SL 30W HLSLD-ML04-30-CWL-INV-RTC-R or as equivalent IN PHILIPHS/HAVELLS/BAJAJ |
| 77 | Supply and fix in replacement of recessedaccentSpot COB downlight of capacity 30 watt aluminium die cast housing & heat sink for durable performance, long life with 30,000 burning hours , Lumen- 2250lm, cut out 120 mm , CRI> 80, PF>0.9, Beam angle 36 degree, height 81 mm, Dia 135 mm having surge protection 2 kv incl electrically connection complete all as specified and directed by Engr-in-charge. Make: Philips (SKU: LT01329-1) or as equivalent IN PHILIPHS/HAVELLS/BAJAJ |
| 78 | Supply and fixing warm white 20 meter Mini marathon rope light with connector, IP 65 protection water proof strip light with 72 LEDs/meter offers 400 lumens/meter consuming 6 watt power incl electrically connectioncomplete all as specified and directed. Make: PHILIPHS/HAVELLS/BAJAJ |
| 79 | Supply and fixing of Inverter LED tube light fitting 1x20 Watt with minimum 04 hours battery back integrated aluminium batten with diffuser and including 20 Watt LED hight efficient, AC 220-240 V, 50 Hz and connecting with copper conductor flexible cable of size 0.50 Sqmm from ceiling rose to connectorof the light including disconnecting and taking down old existing light fitting of any description and in any position complete all as specified and directed. |
| 80 | S & F LED lamp invertor technology 9 watt with 4 hour power back up with efficiency more than 100 lumen per watt, Lithium ion battery including removing of unserviceable lamp complete all as specified and directed by Engr-in-charge. |
| 81 | S & F modern energy efficient bedroom Muziris wall decorative light of capacity 20 watt single headed 240 volt, IP20 rating, controller type (push button), product weight 1.04 kg, body material (metal), power source (corded electric),Lamp base E27, Colour(bronze) incl electrically connection , including removing of unserviceable decorative light fittings of any description complete all as specified and directed by Engr-in-charge. Make: Philips model No 31425 or as equivalent. |
| 82 | S & F modern energy efficient Muziris picture/mirror light of capacity 12 watt 240 volt, Colour (bronze), material (Aluminium), dimensions(mm) 500x80x95, lamp base (LED), CCT 3000K, Lumen 420 lm, CRI>80 incl electrically connection , including removing of unserviceable mirror light fittings of any description complete all as specified and directed by Engr-in-charge. Make: Philips model No 31403 or as equivalent IN HAVELLS/BAJAJ/HALONIX |
| 83 | S & F modern energy efficient Bed side light of capacity 2 watt 220-240 volt, Colour (Grey), material (Metal), dimensions(mm) 470x67x28, lamp base (LED), CCT 3000K, Lumen 50 lm,controller type (push button), power source (corded electric) incl electrically connection , including removing of unserviceable bed side light fittings of any descriptioncomplete all as specified and directed by Engr-in-charge. Make: Philips model No 30975or as equivalent IN /HAVELLS/BAJAJ/HALONIX |
| 84 | S & F modern energy efficient Track light of capacity 20 watt 220-240 volt, Colour (Black), material (Aluminium), dimensions(mm) 158x65x125, lamp base (LED), CCT 3000K, Lumen 1500 lm,controller type (push button), power source ( electric) incl electrically connection , including removing of unserviceable track light fittings of any description complete all as specified and directed by Engr-in-charge. Make: Philips model No 31446 or as equivalent HALONIX/HAVELLS/BAJAJ |
| 85 | S & F well designed modern energy garden spike light of capacity 12 watt 220-240 volt, Colour (Anthracite), material (Aluminium), dimensions(mm) 100x75x75, lamp base (LED COB Integrated), CCT 4000K, Lumen 360 lm, IP 65 protection against dust & jet of water from any direction ,controller type (push button), power source (corded electric) incl electrically connection complete all as specified and directed by Engr-in-charge. Make: Philips model No 31385 or as equivalent HALONIX/HAVELLS/BAJAJ |
| 86 | S & F Solar LED post top luminaire 20 W of high efficiency poly crystalline Solar Module with maintenance free Lithium battery of having 3 days backup with 2 PIR Sensor with 360 degree coverage , 5700K, IP-65 made of pressure die cast aluminium housing & clear glass complete with all accessories internally prewired wire including electronic driver, connecting with fitting and including disconnecting and taking down existing unsv light fitting complete all as specified and directed by Engr-in-charge. |
| 87 | Material & labour for replacement of unsvearthing complete with galvanised steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5mtr below the normal ground level connected to galvanised earthwire 4mm dia by means of bolts, nuts, check nuts and washers of galvanised iron.Earth strip protected by GI pipe 15mm bore(medium grade) and connected to earthing test pointas directed and as specified and shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 40 cm x 40cm x 5cm reinforced with 8mm dia TMT bars @ 15cm c/cboth ways with one handle for liftingmade out of 8mm dia bar, funnel, wire mesh, 20mm dia GI pipe medium grade for watering, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil and testingcomplete all as directed by Engineer-in-Charge and earth testing on completion . |
| 88 | Taking down existing LT panel board (Meter Box) located at Map blockand supply and fixing sheet metal enclosure board made of 1.6 mm thick metal sheet and painting 2 coats with synthic enamel paint over a coat of red oxide primer including Aluminium bus bar of suitable rating and fixed with wall for fixing MCCB 4P 125 amp and electric meters complete with wiring, fitting and accessories, locking arrangements with handle (adequate size and adequate depth for the following equipments, internal wiring and termination of external cable, lugs and glands and conduits as required) comprising of following. (a) Incoming 125 Amp 4 pole MCCB 25 KA-01 Nos.(Main incomer) (b) Aluminium Bus bar rated 200 Amp capacity. (c) 10Amp DP/SPN MCB-01 No (Outgoing for stair case and garrage) (d) 63 Amp DP/SPN MCB-06 Nos(Outgoing for Qtr meters) (e) Taking down and Refixing of electric meterenergy meterssingle phase 240Volt 40Amps 50HZ -06 Nos. |
| 89 | Supply and fix in replacement ofLED post top fitting 40 W powder coated aluminium die cast and spun aluminium with clear/diffused PC cover suitable for landscape lighting 240V, 50 Hz ,ACsupply complete with all accessories internally pre wired including provision of 3 corePVC flexible copper conductor from electric supply source to connector of light with degree of protection IP 65,CCT 6500K complete all as specified and directed by Engr-in-charge.Note: Cost of GI pipe of suitable dia of length 4 feet, grouting holes into piller and cement work has beenincluded in the rate quoted by contractor |
| 90 | Supply and fix in replacement ofLED post top fitting 20-25 W powder coated aluminium die cast and spun aluminium with clear/diffused PC cover suitable for landscape lighting 240V, 50 Hz ,ACsupply complete with all accessories internally pre wired including provision of 3 corePVC flexible copper conductor from electric supply source to connector of light with degree of protection IP 65,CCT 6500K complete all as specified and directed by Engr-in-charge.Note: Cost of GI pipe of suitable dia of length 4 feet, grouting holes into piller and cement work has beenincluded in the rate quoted by contractor |
| 91 | Supply and fix new generation, energy saving, environment friendly, long life aesthetically designed aluminium landscape IP 65 of luminaire for diffused lighting with high power LED as light source LED Bollard pathway lightsof capacity 10 watt warm whitemade up of aluminium pipe UV protected pure polyester powder coated having colour temperature(CCT) 3000K warm white fixed to concrete foundation by means of 3 nos M10 bolts complete all as specified and directed by Engr-in-charge.Note:- Cost of PCC foundation of suitable height , PVC conduit25 mm of suitable length, all electrical connection and all other items whichever required for fixing is deemed to be included in the unit rate quoted for this item. |
| 92 | Supply and fixincl taking down LED garden light fitting cool/warm white with LED bulb upto 20 watt E27/B22 base cap fitted on the piller with the help of GI pipe of 1 mtr length and PCC up to 250 mm height nut bolts and in stainless steel housing with clear acrylic cover in top section with IP 65 protection class ,connection with 1.5 sqmm 3 core copper cableincluding making suitable PCCfoundation and all electrical connection complete all as directed by Engr-in-charge. |
| 93 | Supply and laying or fixing or passing through pipe 1100 volts grade heavy duty, 2 core, 6 sq mm nominal cross section cable with PVC insulated aluminium conductormultistrand served with an inner sheathing of PVC tapeand overall PVC sheathed in service connection, including disconnecting and taking down oldunserviceable existingcable complete all as specified and as directed by the Engineer-in-Charge. |
| 94 | Supply and laying or fixing or passing through pipe 1100 volts grade heavy duty, 2 core, 10 sq mm nominal cross section cable with PVC insulated aluminium conductormultistrand served with an inner sheathing of PVC tapeand overall PVC sheathed in service connection, including disconnecting and taking down oldunserviceable existingcable complete all as specified and as directed by the Engineer-in-Charge. |
| 95 | Supply and fixing 36W , 2’X2’ recessed Luminaire with housing made up ofCRCA powder coatedmade up ofHigh transmittancediffuser for glare free symmetric light distribution., Powered by Isolated, SELV output Electronic Driver with Output Short-circuit protection, Surge Voltage protection and other safety & performance test as per IS:15885 Part 2/Sec 13.Power Consumption should not greater than 36W and System Efficacy notless than 100 Lumens/Watt, CCT 5700K PF>0.95, CRI>80 ,THD<10%. Operating temperature: -10 °C to +35 °C , Operating voltage range: 140 V - 270 V. Built in PIR Sensor.Luminaire Should conform to IP20 Classification. Test report to be submitted; photo biological safety norms: IS16108, test certificate to be submitted; certification: LM 79 for luminaire andLM80 for led source, Driver and Fixture to be BIS certified as in repair complete all as specified and as directed by the Engr-in-charge. |
| 96 | Supply and fixing concrete pit in PCC (1:3:6) type C1 of size 40x40x40 cm having hollow inner space 30 cm, pre-cast RCC (1:2:4) type B1 cover slab 40 cm x 40cm x 5cm reinforced with 8mm dia TMT bars @ 15cm c/cboth ways with one handle for liftingmade out of 8mm dia bar complete all as specified and directed by Engr-in-Charge. |
| 97 | Material and labour for servicing of earthing on site including filling water, GI funnel, minor plaster work if necessary, white wash complete all as specified and directed. |
| 98 | Checking of earthing results of various type of earthing installed in bldgs/Sub station through earth test meter and submission of earthing report complete all as specified and directed by Engr-in-charge. |
| 99 | Supply only PVC rigid casing caping 20 mm dia icl fixing clamps complete all as specified and directed by Engr-in-Charge. |
| 100 | Supply and fixing hot pressed module SMC meter junction boxes SMC base and SMC door, concealed hinges, veiwing glass, earth bolt, plugged off white colour suitable for single phase energy meter complete all as specified and directed. |
| 101 | Supply and fix recess mounted LED luminaire 36 watt cool white 5700K suitable for gridd ceIling cutout dimensions: 2x2 Ft. incl connecting with twin core copper wire from ceiling rose to fitting, Fixture size: (LxWxH) in (595x595x65) mm incl lamp and driver all as specified & directed. |
| 102 | Supply and fix surface mounted LED luminaire 36 watt warm white 3000 K suitable for surface ceiling cutout dimensions: 2x2 Ft. incl connecting with twin core copper wire from ceiling rose to fitting, Fixture size: (LxWxH) in (595x595x65) mm incl lamp and driver all as specified & directed. |
| 103 | Supply and fixingRound surface mounting LED Panel 18 watt warm/cool type circular down lighterwith PDC aluminium housing and high translucent frosted plastic diffuser, 240 volt, 50HZ, AC supply, efficiency 100lm/w completewithall accessories internally pre wiredincluding connecting with 2 coreflexible wirecopper conductor from ceiling rose to connector of the light, including disconnecting and taking down existing old unserviceable fittingcomplete all as specified and as directed by the Engr-in-charge. |
| 104 | Supply and fix in replacement epoxy power coated MCCB distribution distribution box double door VTPN 4 way vertical type AC 415 V with IP 43 protection for MCBs alongwith provision of MCCB as incomer with common bus-bar rated 200 Amp at incoming end of outgoing MCBs grouted/ flush to wall, complete all as specified by Engineer-in-charge. (Note :- MCCB will be measured and paid under seperate item) (i) Cost of Eye/bottle thimbles used MCBs in DBs shall deemed to be included in unit rate quoted for this items, (ii) Electric wiring should be done in proper colour coding i.e. Red for phase, Black for neutral and Green for Earth (iii) Connection of cable with VTPN shall be done through appropriate size of Al thimble. |
| 105 | Supply and fix in replacement of MCCB, 4 Pole, 63 A, 16 KA for fixing in DB including proper thimble connection, thermal and magnetic release protectioncomplete all as specified and directed by Engineer-in-charge. |
| 106 | Supply and fix in replacement of MCCB, 4 Pole, 100 A, 25 KA for fixing in DB including proper thimble connection, thermal and magnetic release protectioncomplete all as specified and directed by Engineer-in-charge. |
| 107 | Supply and fix in replacement of Sheet metal enclosure 8 ways double door for DBs when MCBs areto be used 240,volts including 200 Amps standard bus bar of suitable size and common neutral link allflush mounting type, drilling holes for incoming and out going cables with IP43 protection complete all as specified & directed byEngr-in-charge. |
| 108 | Supply and fix in replacement of Sheet metal enclosure 4 ways double door for DBs when MCBs areto be used 240,volts including 200 Amps standard bus bar of suitable size and common neutral link allflush mounting type, drilling holes for incoming and out going cables with IP43 protection complete all as specified & directed byEngr-in-charge. |
| 109 | Supply and fix in replacement of Sheet metal enclosure 12 ways double door for DBs when MCBs areto be used 240,volts including 200 Amps standard bus bar of suitable size and common neutral link allflush mounting type, drilling holes for incoming and out going cables with IP43 protection complete all as specified & directed byEngr-in-charge. |
| 110 | S & F in replacement of MCB , SPN,240 Volts ,63 amp for fixing in DBs ofincluding proper thimble connections complete all as specified and directed by Engineer-in-Charge. (Note: MCB should be B or C curve as directed by engineer in charge) |
| 111 | S & F in replacement of MCB , SPN,240 Volts ,40 amp for fixing in DBs ofincluding proper thimble connections complete all as specified and directed by Engineer-in-Charge. (Note: MCB should be B or C curve as directed by engineer in charge) |
| 112 | S & F in replacement ofMCB, single pole 240 volts 6 to 32 Amp capacity for fixing in DB’s including proper thimble connections complete all as specified and directed by Engineer-in-Charge. (Note: MCB should be B or C curve as directed by engineer in charge) |
| 113 | S & F in replacement ofMCB, single pole 240 volts 63 Amp capacity for fixing in DB’s including proper thimble connections complete all as specified and directed by Engineer-in-Charge. (Note: MCB should be B or C curve as directed by engineer in charge) |
| 114 | S&F single pole and neutral enclosure with a two pin and earth plug and socket 20 Amp complete with and including one single pole MCB.20 Amp, 10 KA \"B\" curve including removing old unserviceable enclosure complete all as specified and as directed by the Engr-in-charge. |
| 115 | M & L for Sub main wiring with two single core 6.0 Sqmm PVC insulated and unsheathed FRLSH,stranded copper conductor cable drawn through PVC concealed conduit 25 mm dia medium grade including 6.0 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note 1:- 2(two) Runs of 6.00 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Run of 6.00 Sqmm Copper conductor Earth wire shall be measured as one unit)Note 2 :(i) Rate quoted for this items shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of 25 mm dia medium grade with tees, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc.(ii) Cutting chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to match the existing surfaces and cutting not exc.10 cm girth . (iii) Including taking out/down existing unserviceable sub main wiring (iv) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB. |
| 116 | M & L for Sub main wiring with two single core 4.0 Sqmm PVC insulated and unsheathed FRLSH,stranded copper conductor cable drawn through PVC concealed conduit 25 mm dia including 4.0 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note 1:- 2 Runsof 4.00 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Runof 4.0 Sqmm Copper conductor Earth wire shall be measured as one unit) Note2 : Rate quoted for this items shall be inclusive of the cost of(i) Rigid non-metallic PVC conduit of 25 mm dia withtees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc.(ii) Cutting chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to match the existing surfaces, cutting not exc.10 cm girth . (iii) Taking out/down existing unserviceable sub main wiring.(iv) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB. |
| 117 | M & L for Sub main wiring with two single core 10.0 Sqmm PVC insulated and unsheathed FRLSH,stranded copper conductor cable drawn through PVC concealed conduit 25 mm dia including 6 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note 1:- 2 Runsof 10.00 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Runof 6.00 Sqmm Copper conductor Earth wire shall be measured as one unit) Note2 : Rate quoted for this items shall be inclusive of the cost of(i) Rigid non-metallic PVC conduit of 25 mm dia withtees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc.(ii) Cutting chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to match the existing surfaces, cutting not exc.10 cm girth . (iii) Taking out/down existing unserviceable sub main wiring.(iv) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB. |
| 118 | M & L for Sub main wiring with 04 (Four) single core 16.0 Sqmm PVC insulated and unsheathed FRLSH,stranded copper conductor cable drawn throughpvc concealed conduit of suitable dia including 10.0 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note1:- 4 Runsof 16.00 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Runof 10.00 Sqmm Copper conductor Earth wire shall be measured as one unit) Note2 : Rate quoted for this item shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of suitable size dia with tees, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc.(ii) Cutting chases, pinning in and making good to facing where requiredpointing in cement mortar 1:3 to match theexisting surfaces and cutting not exc. 10 cm girth. (iii) Taking down/out existing unserviceable sub main wiring.(iv) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB. |
| 119 | M & L for Sub main wiring (with approved colour coding as per IS)with single core FRLSH PVC insulatedmultistranded copper conductor1.1 KV grade (main cable : number of runs indicated below) along with one run of single core FRLSH PVC insulatedmultistranded copper conductor 1.1 KV grade for earthing in and including PVC conduits of suitable size, for 2 runs of 1.5 sq. mm main cable + 1 run of 1.5 Sq. mm earth cable as in replacement of old unserviceable wiring complete all as specified and directed. Note:(i) Two different color wires shall be used for phase andneutral . (ii)Connections of cables with MCBs or bus bars shall be done through appropriate size brass/copper thimbles. (iii) If Necessary cutting chasing shall be included in this item. |
| 120 | M & L for Sub main wiring (with approved colour coding as per IS)with single core FRLSH PVC insulatedmultistranded copper conductor1.1 KV grade (main cable : number of runs indicated below) along with one run of single core FRLSH PVC insulated multistranded copper conductor 1.1 KV grade for earthing in and including PVC conduits of suitable size, for 2 runs of 2.5 sq. mm main cable + 1 run of 2.5 Sq. mm earth cable as in replacement of old unserviceable wiring complete all as specified and directed. Note:(i) Two different color wires shall be used for phase andneutral . (ii)Connections of cables with MCBs or bus bars shall be done through appropriate size brass/copper thimbles. (iii) If Necessary cutting chasing shall be included in this item. |
| 121 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of cables including getting out in any kind of soil complete all as specified and directed. |
| 122 | Returning filling in including spreading, levelling, and well ramming, in layers not exceeding 25 cm each layer of any kind of soil. |
| 123 | Removing surplus excavated material from site not exceeding 50 mtrs from starting point and depositing where directed at level not exceeding1.5 mtr above the starting point. |
| 124 | Material and labour for sand cushioning for cables 8 cm below the cable and 15 cm abovewith dry river sand in trenches for cushioningof underground cable line including spreading, leveling, well ramming completed all as specified and directed. |
| 125 | Supplying & laying factory made unreinforced Precast concrete cable coversclass LV type 1, flat, Size 250x150x40mm laid in trenches as protection to cables completeall as directed by Engr-in-Charge |
| 126 | Material and labour for replacement of GI tubing light grade 40 mm borefor passing through cables under the floor ,along the wall or along the pole complete all as specified and directed. |
| 127 | Material and labour for replacement of GI tubing light grade 80 mm borefor passing through cables under the floor ,along the wall or along the pole complete all as specified and directed. |
| 128 | XLPE Insulated ,screened, PVC bedded, galvanized steel wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 2 core supplied& laid in replacement complete all as specified& directedby Engineer-in-Charge. |
| 129 | XLPE Insulated ,screened, PVC bedded, galvanized steel wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core supplied& laid in replacement complete all as specified& directedby Engineer-in-Charge. |
| 130 | Supply and fix in replacement of New generation energy saving and environmental friendly long life LED building security light 1x25 watts made up of pressure die cast alluminium housing with high power LED as light source and lense embedded PC cover having TOP OPENING separate driver compartment with IP66 protection and impact resistance of IK07,with all accessories including suitable bracket with 32 mm bore light grade GI pipe bend to shape, including MS clamp of size of required size and PVC cable 1.5 Sqmm twin core from ceiling rose to light fittings complete all as specified and directed by Engineer-in-charge. |
| 131 | Supply and fixing in replacement ofLED surface mounted bulk head luminaries 8-10 watt with min 800 lumen,IP 66, PVC housing, surge protection including driver & LED lampetc complete with all accessories, connecting with copper conductor flexible cablefrom ceiling rose to connector of the light as in repair complete all as specified and as directed by the Engineer-in-Charge. |
| 132 | Supply and fix inof PVC Gang Boxof 5 Ampcomplete all as specified and directed. |
| 133 | Supply and fix inof PVC Gang Boxof 15 Ampcomplete all as specified and directed. |
| 134 | Supply & fix in replacement of existing unserviceable Sheet metal enclosure with new DB’s suitable for MCBs of single pole and neutral 2 way single door type with 200 amp rated bus bar. Note: i) Connnections of the MCB\"S shall be done with appropriate size of brass/Cooperthimble. ii) The DB shall be fiush fixed and making good the disturbed surface shall be part of job at no extra cost. |
| 135 | Supply and laying or fixing or passing through pipe 1100 volts grade heavy duty, 2 core, 2.5 sq mm nominal cross section cable with PVC insulated aluminium conductormultistrand served with an inner sheathing of PVC tapeand overall PVC sheathed in service connection, including disconnecting and taking down oldunserviceable existingcable complete all as specified and as directed by the Engineer-in-Charge. |
| 136 | Supply and Fix MCB DP 63 Amp, Superior Air Circulation , hammer trip mechanism all as specified and directed by Engr in charge. |
| 137 | Supply and Fix MCB DP 40 Amp, Superior Air Circulation , hammer trip mechanism all as specified and directed by Engr in charge. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail