| 1 | Supply, installation, testing and commissioning of power distribution panels as per the detailed specification. (Refer Sec. V Part A & B) |
| 2 | 415V Class - IV MAIN Panel RCL PUMP HOUSE as per dwg no IGC/ES/EL/RCL-213 SHEET 01 OF 04 |
| 3 | 415V Class - IV MCCB WALL MOUNTEDPanel as per dwg no.IGC/ES/EL/RCL-213 SHEET 02 OF 04 |
| 4 | 415V Class - IV MCC Panel RCL PUMP HOUSEas per dwg no.IGC/ES/EL/RCL-213 SHEET 03 OF 04 |
| 5 | 415V/20 kW wall mounted Star-Delta Starter panel as per dwg no.IGC/ES/EL/RCL-213 SHEET 04 OF 04 |
| 6 | 415V/250A Power distribution panel as per Dwng no.IGC/ES/EL/CWCP-118 |
| 7 | Supply, transportation, installation, testing and Commissioning of the following types of Suspended luminaires. (Refer Sec VI, Clause No.16.1). - Catalogue No : CANE STD LINEAR PENDANT 40W, 5700K-4FTItem code LPC0104057NDWEP0DL4C01 with downrod replacement fixing accessories or Equivalent and Lamp Type LED |
| 8 | Supply, transportation, installation, testing and Commissioning of the following type of Surface mounted luminaires. (Refer Sec VI, Clause No.16.1).- Catalogue No : WAND K 30W 5700Kcode SLWKY03057NDWEP04C22 -SURFACE LIGHTS NONDIM WITH CUSTOMIZED CLAMP OF 30 DEG. TILT WHITE (PC) 4FEET- PRIME or equivalent and Lamp Type LED |
| 9 | Supply, Installation, Testing and Commissioning of following Flood light luminaries on RCC/Metalic poles of height from 7 M to 12 M as per per the detailed specification. (Refer Sec VI, Clause No.16.1). - Catalogue No : BVP282 LED120 CW FG SY5WB 100W PSU or equivalent and Lamp Type LED |
| 10 | Supply, Installation, Testing and Commissioning of following Flood light luminaries on RCC/Metalic poles of height from 7 M to 12 M as per per the detailed specification. (Refer Sec VI, Clause No.16.1). - Catalogue No : BVP283 LED240 CW FG SY5WB PSU or equivalent and Lamp Type LED |
| 11 | Supply, transportation, installation, testing and Commissioning of the following types of High bay luminaires. (Refer Sec VI, Clause No.16.1). - Catalogue No : BY515 LED 200 or equivalent and Lamp Type LED |
| 12 | Supply, transportation, installation, testing and Commissioning of the following type of Recess mounted luminaires. (Refer Sec VI, Clause No.16.1). - Catalogue No : FULLLIT SQ STD 30W 5700K Item code PRF0003057NDWEP or equivalent and Lamp Type LED |
| 13 | Supply and Installation of MS Brackets, Supports, Frame work, Clamps, Base Channels, etc. fabricated out of angle / Channel / Rods etc. The rate quoted shall include the cost of fabrication / welding, cleaning and painting/ galvanising as follows including supply of required, fasteners, nuts, washers, etc.(Refer Sec VI, Clause No.11) |
| 14 | MS fabrication 1 coat primer & 2 coats synthetic enamel paint |
| 15 | GI: MS fabrication With hot dipped galvanising. |
| 16 | Supply and open installation of following sizes of flush mounting POWDER COATED TPN/SPN DB Enclosures with Double Door and per Phase isolation DBs consisting of Phase, Neutral and Earth Bus and interconnecting wires etc. at suitable depth in brick work as per the detailed specification and as directed by the Engineer-in-charge.(Refer Sec VI, Clause No.15.2). |
| 17 | 6 WAY Cat No:DETPI006DD (Vertical) or equivalent make TPN TIER Per Phase Isolation (PPI) DB |
| 18 | Supply, open installation testing and commissioning of the following sizes of cable end termination box on MS frame work (MS frame will be measured separately) as per the scope of work. (Refer Sec VI, Clause No.15.1.15). |
| 19 | TPN,6 way Cable end box, Cat No:DBTPI006CB or equivalent suitable for TPN, 6 way TPN TIER Per Phase Isolation Distribution Board Cat No:DBTPI006DD |
| 20 | Assembling, installation, testing and commissioning of MCB DB enclosure already embedded in the wall including supply of Per phase isolation conversion kit as per the detailed specification for the following size of MCB DBs. (Refer Sec VI, Clause No.15.3). |
| 21 | TPN, 6 Way Distribution Board |
| 22 | Supply fixing testing and commissioning of the following RCBOs on Distribution Boards as per the detailed specification. (Refer Sec VI, Clause No.14.2) |
| 23 | RCBO DP 32A sensitivity 30mA TYPE AC, 2Module |
| 24 | Supply Installation testing and commissioning of the following MCB on Distribution Boards as per the detailed specification. (Refer Sec VI, Clause No.14.2). |
| 25 | 6-32 Amps SP MCB (Type-C) |
| 26 | 40-63Amps, FP MCB (TYPE-C) |
| 27 | Supply, fabrication and installation of the following size of Copper Flats in Built in trenches on walls, poles, RCC Concrete and through embedded pipes as per the detailed specification. (Refer Sec VI, Clause No.12.7). |
| 28 | 25X3 mm Copper flat |
| 29 | Supply and installation of the following sizes of copper wires in built in trench as per the detailed specification.(Refer Sec VI, Clause No.12.8) |
| 30 | 8SWG copper wire |
| 31 | Maintenance of Earth Pits including supply of Sodium Bentonite, and measurement of Earth Pit Resistance as per the specification.(Refer Sec VI (MNC), Clause No.2). |
| 32 | Supply, cleaning the floor, proper pasting and installation of following insulating mat as per specification. (Refer Sec VI, Clause No.25). |
| 33 | 2.0 mm thickness, Max useable voltage 3.3kV, AC Proof voltage 10kVfor 3 minutes, AC dielectric strength 30kVRMS Insulating Mat confirming to IS:15652 |
| 34 | Supply and Installation of following sizes of Surface Mounting Plastic Boxes as per the detailed specification. (Refer Sec VI, Clause No.15.6). |
| 35 | Surface Mounting Plastic Boxes 6 Module |
| 36 | Supply and Installation of 16A modular switch, 6/16 Amps combined shuttered type Socket and 10A modular switch & 3 pin, 6A shuttered type Socket, 6Modular Plate as directed by Engineer-in-charge. |
| 37 | Supply and external installation of following sizes ofHeavy Duty, Hot Dip Galvanised MS ERW Conduitsfor Electrical & Communication System with all the required accessories like round JBs, Solid Long Bends, Check Nuts, Nipples, Couplings, Reducers, Copper Clips, Copper Conductor, GI Wire etc. as per the detailed specification. .(Refer Sec VI, Clause No.27) |
| 38 | 25mm dia 1.8mm wall thickness Heavy Duty, Hot Dip Galvanised/ ERW Conduits with 50mm deep junction boxes. |
| 39 | Supply and Installation of following sizes of PVC trunking (casing & capping) on walls/Ceiling for routing of Power, Lighting and Telephone wires including all the required accessories like JBs, Coupling, External & Internal Bends, Elbows and end cap as per the detailed specification.(Refer Sec VI, Clause No.29) |
| 40 | 25 X 12 mm size of PVC Mini trunking |
| 41 | Identification and rectification of shunt or series fault in main or sub distribution panel in labs / building. |
| 42 | Major fault |
| 43 | Wiring for lights / fans /sensors/ Timer /Power point with 1100V grade FRLS insulated copper conductor wires in existing concealed/ ExposedPVC / ERW / Flo-coated Metal conduitsas per the detailed scope of work, includingsupply of Wires, switches/ sockets, termination of copper wires at either end by crimping including supply of PVC Sleeves/Ferrules, Copper Crimping Lugs and connecting the wires to various switches, sockets, etc. including testing and commissioning as per the detailed specification.(Refer Sec VI, Clause No.18) |
| 44 | Wiring for Light/Sensor/Fan Points with 2 Runs of 1.5 Sq.mm copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm copper wire for Earth from MCB Distribution Board to Primary light/sensor/fan point through Control Switch Box including 6Amps modular switch. |
| 45 | Wiring for Power point with 3 Runs of 2.5 Sq.mm Copper wires for Phase & Neutral and Earth from MCB Distribution Board to Power point through Control Switch Box including 16A modular switch, 6/16 Amps combined shuttered type Socket and 6A modular switch & 3 pin, 6A shuttered type Socket, Modular Plate. |
| 46 | Wiring for lights / fans /sensors/ Power pointwith1100V grade FRPVC insulated copper conductor wires in existing concealed/ ExposedPVC / ERW/Flo-coated Metal conduitsas per the detailed scope of work, includingsupply of Wires, switches/ sockets, termination of copper wires at either end by crimping including supply of PVC Sleeves/Ferrules, Copper Crimping Lugs and connecting the wires to various switches, sockets, etc. including testing and commissioning as per the detailed specification.(Refer Sec VI, Clause No.18) |
| 47 | Wiring for Light point with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm Copper wire for Earth from Light point toLight point /sensor/contactor |
| 48 | Wiring for Light point with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5Sq.mm Copper wire for Earth from Switch boxto Light point/Ceiling fan including 1 No 6A modular switch |
| 49 | Wiring for fan point with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5Sq.mm Copper wire for Earth from Switch boxto Fan point including 1 No 6A modular switch and 1 No step type Fan regulator |
| 50 | Wiring for Power point with 3 Runs of 2.5 Sq.mm Copper wires for Phase & Neutral and Earth from Control Switch Box to control switch box including supply of 16A modular switch, 3 pin 6/16A combined shuttered type Socket, Modular plate. |
| 51 | Removal of light fixtures (Refer Sec VI (MNC), Clause No.21). |
| 52 | Removal of light fixtures in labs and low bay areas |
| 53 | Removal of the following from 415Volts switch boards (Refer Sec VI (MNC), Clause No.19). |
| 54 | 63A/100A/125A, 500V, TP/TPN/SFU/ Combination SFU or 4/6/8/12 Way SPN DB or 4/8 WAY TPN DBs |
| 55 | Removal of old LT power distribution/Motor control centre panels consisting ACBs, SDFU\"s feeders, starter cubicles and its associated LT armoured cable from various buildings and safe transporting of the same panels up to 5 Kilometers as directed by EIC. |
| 56 | 415V/400A, MCC Panels(5 Vertical)-consists ofSDFUs-05 nos andSTAR-DELTA Starters-3 nos (15 HP) ,Ground floor RCL PUMP HOUSE building |
| 57 | 415V/250A, PDB Panel (3 Vertical)-consists ofSDFUs-12 nos ,Ground floor ESG ANNEX building |
| 58 | Removal of 1.5 or 2.5 or 4 sq.mm aluminium wire from concealed/ ExposedPVC / ERW / Flo-coated Metal conduits on roof or wall conduitsas per the detailed scope of work.(Refer Sec V Part A) |
| 59 | Loading, Transportation, Unloading at site, installation, Testing and Commissioning of1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables of following sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification (Note: Cable will be issued free of cost by the department).(Refer Sec VI, Clause No.3) |
| 60 | 3/3.5/4core X Upto 25 sqmm |
| 61 | 3/3.5/4Core X above 120 & up to 240 sqmm |
| 62 | 3/3.5/4Core X above 240 & up to 400 sqmm |
| 63 | Loading, Transportation, Unloading at site, Laying, Testing and Commissioning of one number PVC/HRPVC/XLPE insulated and PVC sheathed Stranded Aluminium/copper conductor power cable of 1.1 KV grade of following sizes direct in ground including excavation, sand cushioning, protective covering with chamber burnt/cement bricks on sides & top, refilling the trench and providing RCC route indicator etc as required (Note: Cable will be issued free of cost by the department).(Refer Sec VI, Clause No.3) |
| 64 | 3/3.5/4 Core X upto 25 Sqmm |
| 65 | End Termination of the following sizes of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable usingSingle Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland. (Refer Sec VI, Clause No.10.1). |
| 66 | 3.5 x 185 sq.mm |
| 67 | 3.5 x 400 sq.mm |
| 68 | End Termination of the following sizeCopper Conductor PVC/XLPE Insulated and FRLS sheathed armoured UG Cable usingSingle Compression, Heavy Duty,Siemens type Brass Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Copper crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland. (Refer Sec VI, Clause No.10.1). |
| 69 | 4C x 10 Sq.mm including cable gland earthing |
| 70 | 4C x 16 Sq.mm including cable gland earthing |
| 71 | Supply, installation, testing and commissioning of the following Raychem make Heat Shrinkable CableStraight Through Jointing Kits (Crimping type) for 3.5 Core Aluminium Conductor, 1.1 kV (E), PVC/XLPE insulated cables of following sizes as specified. Excavation will be measured separately (Refer Sec VI, Clause No.10.6). |
| 72 | Straight Through Joint (Crimping type)for 3.5 Core x 400 Sq. Mm |
| 73 | Retrieval of the already laid one number1100 Volts Grade XLPE/HRPVC insulated, Stranded Aluminium conductor cables of following sizes in built-in trenches, on walls, poles and from embedded pipes including removal of GI spacer, clamps etc and relaying the same cable in built-in trenches, on walls, poles and through embedded pipes using the retrieved spacer & clamp & supplying the shortage spacer & clamp if any as per the detailed specification. (Refer Sec VI, Clause No.7) |
| 74 | 3/3.5/4 CoreAbove 240 & Upto400 Sqmm |
| 75 | 3/3.5/4 Core Above 120 & Upto 240 Sqmm |
| 76 | 3/3.5/4 CoreAbove 25 & Upto 120 Sqmm |
| 77 | upto 3/3.5/4 C X 25Sqmm |
| 78 | Retrieval of the already laid one number PVC/HRPVC/XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following sizes laid direct in ground including removal of end termination, excavation of trenches, retrieving of bricks, back filling and Re - laying the same cable direct in ground by using retrieved bricks including transportation of cables, excavationand backfilling of soil, supply of sand & shortage bricks etc as per the detailed specification. (Refer Sec VI, Clause No.7) |
| 79 | 3/3.5/4 Core Above 240sqmm & upto 400 sqmm |
| 80 | Retrieval of the already laidone number1100 Volts Grade XLPE/HRPVC insulated, Stranded Aluminium conductor cables of following sizes in built-in trenches, on walls, poles and from embedded pipes including removal of end termination GI spacer, clamps etcas per the detailed specification. (Refer Sec VI, Clause No.5) |
| 81 | 3/3.5/4 Core upto 25 Sqmm |
| 82 | Wiring for lights / fans /sensors/ Power point with 1100V grade FRLS insulated copper conductor wires in existing concealed/ Exposed PVC / ERW / Flo-coated Metal conduits as per the detailed scope of work, including supply of Wires, termination of copper wires at either end by crimping including supply of PVC Sleeves/Ferrules, Copper Crimping Lugs and connecting the wires to various switches, sockets, etc. including testing and commissioning as per the detailed specification.(Refer Sec VI, Clause No.18) |
| 83 | Wiring with 1 Run of 1.5 Sq.mm Copper wire |
| 84 | Wiring with 1 Run of 2.5 Sq.mm Copper wire |
| 85 | Temporary installation of Power distribution panel as directed by Engineer-in-charge.(Refer Sec V Part A) |
| 86 | Supply and pasting of water proof stickers of 250 x 50 mm size with messages as directed by Engineer in charge as per the detailed specification. (Refer Sec V Part A ) |
| 87 | Supply and Fixing of Powder coated MS Danger / Warning Boards of different Voltage levels as per the detailed specification. Make: Thadhani or equivalent. ( (Refer Sec V Part A ). |
| 88 | Excavation of soil including refilling with excavated earth and disposing surplus earth at places as directed with in a lead of 10 Mtrs. and initial lift upto 1.5 Mtrs. including neat banking as per detailed specification. (Refer Sec VI, Clause No.2) |
| 89 | Supply and Installation of laminated Hylam sheet of 3mm thickness over the boxes and as per the detailed specification. |
| 90 | Collecting of scrap items and shifting more than 1 km and up to a distance of 5 kms. Measurement will be done on volume basis (Refer Sec VI (MNC), Clause No.28). |