| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | (i) Group B |
| 3 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 4 | (i) 2 x 1.5 sqmm + 1 x 1.5 sqmm earth wire |
| 5 | (ii) 2 x 2.5 sqmm + 1 x 2.5 sqmm earth wire |
| 6 | (iii) 2 x 6 sqmm + 1 x 6 sqmm earth wire |
| 7 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 8 | (i) 5/6 A switch |
| 9 | (ii) 3 pin 5/6 A socket outlet |
| 10 | (iii) Telephone socket outlet |
| 11 | Supplying and fixingtwo module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 12 | Supplying and fixing following size/modules, GI box along with modular base & cover plate for modular switches in recess etc as required. (i) 1 or 2 module (75 mm x 75 mm) |
| 13 | 12 module (200 mm x 150 mm) |
| 14 | Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required |
| 15 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. |
| 16 | supplying and fixing following way double door single pole andnatural MCB distribution board 240 volton surface/recess complete with tinned copper busbarm neutral busbar, earth bar, din bar, detachable gland plate, interconnections , phosphatized and powder painted including earthing etc as required (But without MCB/RCCB/Isolator) |
| 17 | (i) 12 way, Double door |
| 18 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of connections, testing and commissioning etc. as required. |
| 19 | (i) Single Pole |
| 20 | (ii) Single pole and neutral |
| 21 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 22 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation andre-filling as required |
| 23 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthingas required. |
| 24 | Supplying and fixing of 32 mm size of PVC pipeon wall surfsce/recess/under ground trench for protection of cable as per direction of engg in charge as required. |
| 25 | Supplying & fixing of 20/22 watt 4 feet energy effiecient LED tube light fitting directly on wall suitable for single phase AC 230 V complete with accessories connection etc as required. |
| 26 | Supplying, Installation, testing and commissioning of ceiling fan 1200mm sweep ISI mark single phase 230v 50HZ and wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
| 27 | Supplying and fixing of 50 wattenergy saving and environmental freindly LED flood light, 6500 K robust heat sink with long lifeincludingconnection, testing etc. as required. |