| 1 | Taking down/ dismantling steel/PCC poles/struts of any size and any height complete all as specified and directed. |
| 2 | Taking down/ dismantling Cross arms of MS chanel or angle sections etc. from HT pole complete of any size complete all as specified and directed. |
| 3 | Taking down/ dismantling Insulators complete of any size and type complete all as specified and directed. |
| 4 | Taking down/ dismantling Stay assembly complete of any size complete all as specified and directed. |
| 5 | Taking down/ dismantling Earth wire span complete all as specified and directed. |
| 6 | Taking down/ dismantling ACSR conductors of any size complete all as specified and directed. |
| 7 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm incl taking down old cable where required complete all as specified and directed. |
| 8 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 3 core 120 sq mm incl taking down old cable complete all as specified and directed. |
| 9 | Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 sqmm to 95 sqmm incl taking down old joint complete all as specified and directed. |
| 10 | Supply and fix cable jointing kit for 11 KV grade cable for in door termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 sqmm to 95 sqmm incl taking down old joint complete all as specified and directed. |
| 11 | Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 120 sqmm to 185 sqmm incl taking down old joint complete all as specified and directed. |
| 12 | Supply and fix cable jointing kit for 11 KV grade cable for in door termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 120 sqmm to 185 sqmm incl taking down old joint complete all as specified and directed. |
| 13 | Supply, fabricating, installation, testing , commissioning and electrically connecting HT Bus Bar feeder pillar boxfor 95 Sq.mm Cable and Panel of size 100cm x 110cm x 65 cm,11KV ,factory made , machine pressed , dust and vermin proof ,out door type made with CRCA sheet 3.15 mm thick , HT Feeder Pillar internally and externallyshall bepainted with expoxy powder coating red paint with 7 tank process for treatment of degreasing, pickling & two coats primer, IP65, before being given the stove epoxy finish both side opening in two halves with rubber beading , including Aluminium bus bar of 250 Amp (Each Strip Size 50 x 6mm x Length 800mm ) capacity, 3 strip mounted on HT porcelain insulators, HT Danger Plate Provided on Both Side of bus bar chamber.Cubical switch shall have the independent opening panel and shall be mounted on angle iron frame and legs made from angle ironof size 50mm x 50mm x 6mm frame including lifting arrangement and legs duly spray paintedwith two coats of synthetic enamelpaint over a coat of redoxide primer , embeding and grouting in PCC (1:2:4) type B1using 20 mm graded crushed stone aggregate in foundationincluding necessay earth work, including all connections incoming and outgoing cable with suitable size aluminium lugs and glands etc.including providing security fence XPM jally type of 2 mtr height from ground level square type all rounded 2.5 mtr length with 9 nos angle iron of 25 x 25 x 5 mm of height 2.25 mtr ( 2 mtr above ground and 0.25 mtr under ground including necessary location gate of same XPM jally complete all as specified and directed. |
| 14 | M&L for excavation in trenches soft loose soil ,for laying under ground cable, errection of poles and stays in any type of soilnot exc 1.5 Mtr wide and not exc. 1.5 m in depth for foundation and getting out complete all as specified and as directed. |
| 15 | M & L for excavation in trenches,for laying under ground cable,pipe lines, errection of poles and stays in any type of soilnot exc 3.0 Mtr wide and not exc. 3.0 m in depth for foundation and getting out complete all as specified and as directed. |
| 16 | M & L for returning filling in including spreading, levelling, watering and ramming in layers not exceeding 25 cm thick with earth obtained from excavation all as specified and as directed. |
| 17 | M & L for removal of surplus soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 mtr above the starting point all as specified and as directed. |
| 18 | M & L for unwashed sand cushioning below and around cable in trenches with river sand all as specified and as directed. |
| 19 | Supplying and laying un-reinforced precast concrete cable cover HV, Type 1, flat, size 300mmx l80mm x 40mm complete all as specified and directed. |
| 20 | S & F 80mm bores of tubes \"light grade\" galvanised with all fittings and fixed complete with electric pole, laid in trenches for passing of XLPE cable all as specified and as directed. |
| 21 | M&L for Earthing complete with steel earth plate electrode 60 cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1,5 metres below normal ground level,connecting to the Galvanised iron earthStrip 25x4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron and steel earthwire protected by provision of GI Medium grade pipe 15 mm bore including provision of concrete pit made from PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 17mmthick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4 Kg / Sqm) and frame of angle iron 25 x 25 x 6 mm with lugs 02 No and with 6 mm dia MS bar handle made to shape GI medium grade 20 mm bore pipe for watering perforated at bottom, 1.75 metere long placed on top edge of earth plate, common salt and charcoal fittings, test point made out of 17 mm x 8 mm FI with fixing arrangement, funnel wire mesh and earth work in hard / dense soil, returning filling in and removal of surplus soil to a distance notexceeding 50 M all as per electrical plate No 5 of SSR Part- I connected to earth test point incl taking down old earthing complete all as specified and directed. |
| 22 | M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit /pipe or fixed to poles or any other indicated situation for loop earthing etc. as required25 x 4 mm galvanised iron strip for earthing complete all as specified and directed. |
| 23 | M&L forgalvanised cross arms,bracings,supports,clamps, angles,hellowbars square/round,flat irons etc and back plates fabricated in structural steel sections including nuts, bolts,washers, welding, bending, fabrication, cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coatand anti corrosive silver paint one undre coat and one finishing coatand including removing old unserviceable item complete all as specified and directed |
| 24 | M&L for steel tubular swaged type poles 11 metrs long,pole weight approximately 227 kgs, pole should be in one piece only and smooth finishing and smooth finishing of pole,ISI marked complete with all accessories such as cast iron base plate, finial taper plug,bolts, nuts, screws,washers and drilling of holes for continious GI earth wire as specifiedtype 410 SP-55 including applying two coats of aluminium paint over one coat of red oxide zinc chrome primer and embedded portion shall be painted with two coats of black paint after preparation of surfacecomplete all as specified and directed. |
| 25 | M & L PCC 1:4:8, type D-2 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete complete all as specified and direcetd. |
| 26 | M & L for Cement concrete1:3:6 type C 1 (using 20 mm graded stone aggregate) as in roof kerbs or pole coupling of size 300x300 mm or chamfered on edges all as specified and directed. |
| 27 | M&L Lightening arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp, 11000 volts complete all as specified and direcetd. |
| 28 | Supply and fix HT 11 KV, out door type gang operated air-break switch suitable for horizontal or vertical mounting fixed type complete with 15 insulators of rating upto 400 Amps incl taking down old GOD set from existing two pole structure complete all as specified and directed. |
| 29 | Supply and fix HT 11 KV, out door type gang operated air-break switch suitable for horizontal or vertical mounting fixed type complete with 15 insulators of rating upto 200 Amps incl taking down old GOD set from existing two pole structure complete all as specified and directed. |
| 30 | Supply and fixing Danger notice plate of 1.6 mm thick MS sheet,vitreous enamelled white with letters, figures and conventional skull and bones with MS clamp, bolts and nuts of approved size for HT, 25x20 cm,11 KV mark complete all as specified and directed. |
| 31 | M & L forStay assembly complete 20 mm dia stay road with accessories as shown in electrical plate No. 1 complete all as specified and directed.Note- loop type insulator, stay clamps, excavation and concrete measured separately. |
| 32 | M & L forLoop type insulator, vitreous porcelain, white, brown or green large size, with overall dimensions 90mmx140mm, clearance of hole 25.5mm complete all as specified and directed |
| 33 | Note : Deduction of Schedule of Credit (Sch A Part II) to be made of Rs 123328.00 form the total quoted amount of BOQ while accepting the bid. Details of Schedule of credit is given in Tender Documents. |