| 1 | Supply, installation testing and commissioning of following ZonesUL listed Microprocessor based Fire Alarm Control Panel Made of16/18 SWG CRCA sheet powder coated, finish suitable for operation with 220V 50HZ AC mains power supply with standby battery backup 24Volt DC power supply and built in charger (without batteries) , normal operating voltage 24 v DC, compatible with all types of conventional detectors, manual call points and normally opened dry contact devices, 16X2 Dot matrix display, fully compatible with UL-864 and NFPA-72 etc. complete as required as per details specifications. (make- Agni Instruments Engineers (P) Ltd /GST / Honeywell / System sensor / Ravel) |
| 2 | 8 Zone Main Fire Alarm Control panel without PA system |
| 3 | 6 Zone Main Fire Alarm Control panel without PA system |
| 4 | SITC of sealed maintenance free battery of capacity not less than the following capacities with all accessories etc as reqd. (Exide /Amco/Superior) |
| 5 | 2X7AH 12Volts |
| 6 | 2X26AH 12Volts |
| 7 | Supply, installation, testing and commissioning of UL listed, CE certified 2 wire conventional Photo electric / Ionization type Smoke detector with base (Blinking LED type) made of ABS plastic with all accessories, suitable for operation on 24V DC, internal protection class: IP23, dual pulsing LED with 3600 visibility, relative humidity:≤95%; non-condensing and EN54 compliance of approved make etc. as required. (Make- Apollo / GST/ Honeywell / System sensor) |
| 8 | Supply, installation, testing and commissioning of UL listed, CE certified 2 wire conventional Multidetector(fixed cum rate of rise heat Detector using a thermistor, raises an alarm when the detector reaches 590C (Fixed) or when the change in temperature exceeds the rate of rise of 110C/min) withbase (Blinking LED type)made of ABS plasticand all accessories, suitable for operation on 24 v DC, internal protection class: IP23, dual pulsing LED with 3600 visibility, relative humidity:≤95%;non-condensing and EN54 compliance of approved make etc. as required.(Make- Apollo / GST / Honeywell / System sensor) |
| 9 | Supply, installation, testing and commissioning of electronic hooter cum speaker made of 16/18SWG CRCA sheet duly powder coated with PO red colour, output not less than 80db @25mtr, LMT with adjustable sound output of 2.5 watt,5 watt, suitable knock out for cable entry from top suitable for operation on 100/70 volt RMS AC supply etc. as required. (Make- Agni Instruments Engineers (P) Ltd/Apollo / Honeywell / GST/ system sensor/ Ravel ) |
| 10 | SITC of manual push button station (pill box) Manual Call Point in MS Housing for Conventional Fire Alarm System with glass for breaking up in case of fire and hammer with chain etc. (Make- Agni Instruments Engineers (P) Ltd/Apollo / Honeywell / GST/ system sensor/ Ravel ) |
| 11 | Supply and laying of following sizes FRLS PVC insulated and PVC sheathed cable on surface/recess for looping the fire alarm devices & providing power supply to sounder cum strobes etc. as required. (ISI) |
| 12 | 2core 1.5sqmm copper conductor Un Armoured Cable |
| 13 | 2core 1.0sqmm copper conductor Un-Armoured Cable |
| 14 | Supplying and making indoor end termination with brass compression gland and aluminium lugs for following size of PVC insulated and sheathed/XLPE aluminium conductor cable of 1.1 KV grade as required. a)2 core, 1.5 Sq. mm (19mm) |
| 15 | S/F ABS round box / MS Boxon ceiling for fixing the detectors etc as reqd. |
| 16 | Supplying & Fixing of wall mounted Auto glow Signage Fire Exit Sign Board 3mm PVC Sheet with high Glow intensity in total Darkness. (Red and Green colour with exit symbols as per requirements) |
| 17 | Testing, checking & fault finding of Automatic Fire Detection, Fire Alarm system comprising of Fire control panels, Fire Detectors, Manual call points, Electronic Hooters etc.assessing the faults and material required for repairing and rectification of faults i/c rectification of minor faults, testing for proper functioning etc. complete as required. |
| 18 | Gr., 1st, 2nd, 3rd Floor and MSC room Telephone Bhawan, Berhampur |
| 19 | Dismantling the existing Fire alarm panel in the 2nd floor i/c disconnection of all cables, marking the terminals etc. and extending the cables to new location with providing a14 pair 1.0sqmm copper conductor bunched cable approximately 3mtrs length, reconnection etc. complete as required. |