| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group B |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 3 | Wiringfor circuit / submain wiring alongwith earth wire with following size ofFRLSPVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit as required.a) 2 X 1.5 sq.mm +1 X 1.5 sq.mm Earth wire |
| 4 | Wiringfor circuit / submain wiring alongwith earth wire with following size ofFRLSPVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit as required.a) 2 X 2.5 sq.mm +1 X 2.5 sq.mm Earth wire |
| 5 | Wiringfor circuit / submain wiring alongwith earth wire with following size ofFRLSPVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit as required.a) 2 X 4.0 sq.mm +1 X 4.0 sq.mm Earth wire |
| 6 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.a) 3 x 1.5 sq. mm |
| 7 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. a) 3 x 2.5 sq. mm |
| 8 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. a) 3 x 4 sq. mm |
| 9 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.a) 20 mm |
| 10 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. a) 25 mm |
| 11 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular base plate i/c connection etc as reqd. |
| 12 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 02 Nos 3 pin 5/6 A modular socket outlet and 02 Nos 5/6 A modular switch, connections etc. as required. |
| 13 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 14 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 15 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc.as required.a) 4 Module (125mmX75mm) |
| 16 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc.as required. a) 8 Module (125mmX125mm) |
| 17 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc.as required. a) 12 Module (200mmX150mm) |
| 18 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 19 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.a) 5/6 Amp switch |
| 20 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) 3 pin 5/6 Amp socket outlet |
| 21 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) 15/16 Amp switch |
| 22 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) 6 pin 5/6 Amp socket outlet |
| 23 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) Bell push |
| 24 | Supplying and fixing following piano type switch/ socket on the existingswitch box/coverincluding connections etc.as required.a) 5/6 amps switch |
| 25 | Supplying and fixing following piano type switch/ socket on the existingswitch box/coverincluding connections etc.as required. a) 3 pin 5/6 A socket outlet |
| 26 | Supplying and fixing following piano type switch/ socket on the existingswitch box/coverincluding connections etc.as required. a)15/16 A switch |
| 27 | Supplying and fixing following piano type switch/ socket on the existingswitch box/coverincluding connections etc.as required. a) 6 pin 15/16 A socket outlet |
| 28 | Supplying and fixing brass batten / angle holder including connection etc. as required. |
| 29 | Supplying and fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator) .8 way , Double door |
| 30 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\"curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.a) Single pole |
| 31 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc as required. a) 63 Amp |
| 32 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \"C\" curve including connections, painting etc. as required. |
| 33 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc.with charcoal/ coke and salt as required. |
| 34 | Supplying and Installation of ceiling fan 1200 MM sweep with canopy down rod 2ft long & MS fan hooks etc. complete set with connections, testing and commissioning as required. (Crompton/Orient/Havells/Usha/Bajaj/Khaitan or Eqvt). |
| 35 | Supplying and Installationof 400 mm sweepwall fansuitable for single phase,240 volt,50 Hzetc. complete set with connections, testing and commissioning as required. (Crompton/Orient/Havells/Usha/Bajaj/Khaitan or Eqvt). |
| 36 | SITC of 200/225/250 mm PVC body fresh air fan in the existing opening including making good the damage i/c providing and fixing suitable lower/shutters & conn. Etc as req. compatible to havells make model No Ventil air DX FHVVEDXWHT08 Acceptable toCrompton/ Havells /Bajaj/ Usha or equivalent. |
| 37 | SITC of 300 mm sweep double ball bearing metal exhaust fan suitable for single phase, 230 vlolt, 50 Hz, fixing of suitable lower/shutters & conn. Etc as req. compatible to havells make model No Ventil air DB FHVVEMTDBB12 Acceptable toCrompton/ Havells /Bajaj/ Usha or equivalent. |
| 38 | SITC of 380 mm sweep heavy duty metal exhaust fan suitable for single phase, 230 vlolt, 50 Hz, fixing of suitable lower/shutters & conn. Etc as req. compatible to havells make model No Turbo ForceAcceptable toCrompton/ Havells /Bajaj/ Usha or equivalent. |
| 39 | Supplying and installation of20 watt LED batten with polycorbonate housing & integrated electronic driver ,box type etc as required iucluding making connection etc as required Make CG / Bajaj / Havells / Philips/HPL/Syska/C&S. directly on ceiling/wall, including connection with 1.5 sqmmFRLS PVC insulated, copper conductor, single core cable and earthing etc as required. |
| 40 | Supplying, installation , testing and commissioning of 10 watt LED batten 2 feet long with decorative ultra slim square profile extruded polycorbonate, environmental friendly, energy efficient with 1.5 sq mm FRLS PVC insulated copper conductor single core cable and earthing etc as required. compatible to Jaquar make model No kubic plus LKBP4KV010XCAcceptable Make- Havells/ CG /Bajaj/ Philips/Jaquar /Syska. |
| 41 | Supplying and fixing of6 watt round shape surface type slim LED light panel suitable for 240 volt,single phase,50 Hz .compatible toHavells make model No.LHEAAHP5IL1W006Acceptablemake- Bajaj/Philips/Crompton/Jaquar/Syska . |
| 42 | Supplying and fixing of12 watt round shape surface type slim LED light panel suitable for 240 volt,single phase,50 Hz .compatible toHavells make model No.LHEAAHP5IL1W012Acceptablemake- Bajaj /Philips/ Crompton/ Jaquar/ Syska . |
| 43 | Providing of 36 watt LED ultra slim recess mounting luminarie with high performence LEDs 2x2 voltage 100 V-300 V AC CRCA housing,luminous efficiency not less then 100 Lm/watt with make of Havells/ Polycab /Crompton/ Wipro/Phillips/Bajaj/ Jaguar. |
| 44 | Supplying and fixing of70 watt LED street light fitting on existing pole suitable for single phase,230 volt, 50 Hz with IP- 66 protection etc as required. Make Bajaj/ Havells/ Polycab /Crompton/ Wipro/Phillips/ Jaguar. |
| 45 | Add GST Difference @6.33% on DSR itemson Rs. 794163.00/- |
| 46 | Add 1% labour cess on DSR items on Rs. 794163.00/- |