| 1 | Note:-1. Please refer schedule \"A\" notesbefore quoting the tender. 2. Amount of schedudle of credit shall be deducted offline by department . |
| 2 | GENERAL SUMMARY |
| 3 | Schedule \"A\" Part-I ( Building Works )Design andM&L for construction of Pre-engineered building for block of Simulator room sheds with entrance lobby, toilet, platform, ramps, brick steps, 900mm wide plinth protection all around without drain including internal services with height of 6.06m at location specified on plan and as per parameters/ specification provided in DBR & Particular Specification (PS)Note:- The complete design of the buildings mentioned under sch \"A\" Part-I shall be carried out and design and drawings shall be got vetted from any IIT & also refer scope of mentioned in Sch \"A\" Notes and details of scope under Phase-I, Phase-II and Phase-III. The contarctor shall also submit detail estimate alongwith with yard stick for approval of CWE as per Annex \"B\" to Sch \"A\" Notes & the cost of these provision shall be deemed to be included in qouted rate against this item. |
| 4 | Lump sum price worked out by the contractor for BUILDING WORKS as listed in Schedule ‘A’Part-II (Ref prepriced schedule attached seperately) |
| 5 | Lump sum price worked out by the contractor for SCHEDULE ‘A’ PART- III (INTERNAL WATER SUPPLY WORKS) as listed in Schedule ‘A’Part- III (Ref prepriced schedule attached seperately) |
| 6 | Lump sum price worked out by the contractor for SCHEDULE ‘A’ PART-IV (INTERNAL ELECTRIFICATION WORKS ) as listed in Schedule ‘A’Part -IV (Ref prepriced schedule attached seperately) |
| 7 | Lump sum price worked out by the contractor forSCHEDULE ‘A’ PART-V (EXTERNAL WATER SUPPLY WORKS) as listed in Schedule ‘A’ Part-V (Ref prepriced schedule attached seperately) |
| 8 | Lump sum price worked out by the contractor forSCHEDULE \"A\" PART-VI (SEWAGE DISPOSAL WORKS) as listed in Schedule ‘A’Part-VI (Ref prepriced schedule attached seperately) |
| 9 | Lump sum price worked out by the contractor for SCHEDULE ‘A’ PART-VII(AREA DRAINAGE WORKS) as listed in Schedule ‘A’Part-VII(Ref prepriced schedule attached seperately) |
| 10 | Lump sum price worked out by the contractor for SCHEDULE \"A\" PART- VIII (COMPOUND WALL, FENCING AND GATE WORKS) as listed in Schedule ‘A’Part-VIII(Ref prepriced schedule attached seperately) |
| 11 | Lump sum price worked out by the contractor for SCHEDULE \"A\" PART- IX (ROAD, PATH AND CULVERT WORKS) as listed in Schedule ‘A’Part-IX(Ref prepriced schedule attached seperately) |
| 12 | Lump sum price worked out by the contractor forSCHEDULE \"A\" PART-X (EXTERNAL ELECTRIFICATION AND DG SET WORKS) as listed in Schedule ‘A’Part-X(Ref prepriced schedule attached seperately) |
| 13 | Lump sum price worked out by the contractor for SCHEDULE ‘A’ PART-XI(EXCAVATION, EARTH WORK & SITE CLEARANCE AND DEVELOPMENT WORKS) as listed in Schedule ‘A’Part- XI (Ref prepriced schedule attached seperately) |
| 14 | SCH \"A\" Pt - XII (MISCELLANEOUS ITEMS) |
| 15 | INTERNAL ELECTRIFICATION WORKS NOTE:- For items of Internal Electrification Works notes given at the beginning of Sch ‘A’ Part-IV ( Internal Electrification Works) shall also be applicable. |
| 16 | Supply and fixing highbay LED light fittings 80 watt energy saving environment friendly & robust highbay LED with PDC housing suitable for ceiling (surface/suspended) mounting with system efficiency not less than 120 lm/watt complete all as specified and directed. |
| 17 | S&F Wall mounted air circulator copper wound, double ball bearing of size 600 mm, 220-240 volts, air delivery not less than 250 CMM & power consumption not more than 200 watt, metal body painted with metallic powder coated anti corrosion paint alongwith necessary fixing arrangement and connecting cable from ceiling rose complete all as specified and directed. |
| 18 | EXTERNAL WATER SUPPLYWORKSNOTE:- For items of EXT WATER SUPPLYWORKS notes given at the beginning of Sch ‘A’ Part-V (EXTERNAL WATER SUPPLYWORKS) shall also be applicable. |
| 19 | Supply & laying Pipe DI socket and spigot including class K-9 supplied laid complete normal dia 250 mm. |
| 20 | Construction of stone masonry valve pit for sluice valve all as specified and as per drawing including plastering, PCC in foundation, Excavation and earth work in any type of soil, MS sheet cover 3mm thick sheet with locking arrangement painted with two coat of anti corossive paint over one coat of zinc chrome primer of450x450x600 (type \"B\"). |
| 21 | Refixing CI pipe including fittings with spigot and socketed end/ flanged end,centrifugally cast laid in trenches after cleaning internally and externally, drawing out forigen material /rust complete up to satisfaction of Engr in Charge of 250mm sizes with and including new titon joint for fixing of pipe:-Note :- (i)Earth work , joints and CI Specials/fittings of the pipes shall be measured andpaid separately under appropriate item. |
| 22 | SEWAGE DISPOSAL WORKS NOTE:- For items of SEWAGE DISPOSAL WORKS notes given at the beginning of Sch ‘A’ Part-VI ( SEWAGE DISPOSAL WORKS ) shall also be applicable. |
| 23 | M&L for RCC conventional septic tank designed to carry sewage and sullage water, excavation in any type of soil and earth work, PCC 1:4:8 below foundation, RCC M-30 Design Mix in Walls, Base Slab, Baffle walls and Roof Slab including beams etc with vent shaft, manhole openings with cover connection etc. complete with effective depth of 1.5 meter and overall depth of 3 meter for 100 users complete all as specified and directed. |
| 24 | M&L for soakage well excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size 1.2m x 3.00m complete all as specified and directed. |
| 25 | M&L for RCC 150 mmdiameter pipes laid on 150 mm thick PCC cradlebedfor the depth of 0.70 m to 1.65m with excavation in any type of soil, including manholes/drop manhole of standard size made of brick masonry/ RCC/Precast RCC with SFRC ventilating cover and frame including all items and activities to execute and make sewer line functional complete all as specified and directed. |
| 26 | EXTERNAL ELECTRIFICATION AND DG SET WORKS NOTE:- For items of EXTERNAL ELECTRIFICATION AND DG SET WORKS notes given at the beginning of Sch ‘A’ Part-X (EXTERNAL ELECTRIFICATION AND DG SET WORKS) shall also be applicable. |
| 27 | Supply, installation, testing and commissioning floor mounted transformer of capacity 33KV/433V, 630/.433 KVA stepdown outdoor type, 3 phase, 50 Hz, AC, oil immersed, air naturally cooled (ONAN Type), with external cooling tubes / radiators, cooper double wound core type copper wound having no load voltage ratio 33KV/433V corresponding to principal tapping, delta connected primary side (HV side) and star connected on secondary side (LV side) in accordance with vector symbol DYN 11 (vector group 04) with neutral brought out on LV side and having tapping on HV side for constant out put so as to alter / vary secondary voltage +-7.5% in steps of by means of manual off load tap changing arrangements complete and confirming to IS 1180 Part-I 2014,EEL-2.TOTAL LOSSES @ 50% LOAD 613W AND TOTAL LOAD @ 100% LOAD 1828W complete all as specified..The transformer should be fitted with the following standard fitting and accessories :-(a)Name , Rating and Diagram plate.(b) Earthing terminals - 2 Nos(c)Removable inspection opening on top cover.(d) Air release hole with plug explosion vent.(e) Dehydrating silica gel Breather. |
| 28 | (f)Oil Level Guage.(g) Oil filling hole with plug on conservator.(h) Oil Conservator with drain plug.(j)Jacking legs.(k)Bottom drain cum filter valve.(l) Top filter valve.(m) Pressure release device.(n)Silica Gel breather(o)4\" dial type thermometer(p) Off Circiut tap changer switch(q) HT side open type / LT side cable termination box type.Note:-1. The Transformer shall be complete with standard fittings all as specified conforming to IS: 1180 (part-I) 2014and manufacturer shall hold licence / certificate from BIS to this effect.2. The Transformer will have its initial oil filling to appropriate level ( Cost of oil including testing with desired dielectric strength is included)3.Cost of Tfr foundation/plinth as per manufacture drawing/Specification or as per approved by GE is deemed to be included in quoted rate. |
| 29 | S&F vertical type air break switch, gang operated, tripple pole, mechanically operated, outdoor type, with all fittings and accessories, mounted on and including HT 33 KVporcelain insulators 12 Nosand steel channel frame, GI Operating rod 25 mm dia of suitable length to worked from ground, including locking arrangements and with 7 lever Navtal brass lock, suitable for 1000 Amps current rating etc complete |
| 30 | S&F drop out fuse unit, explusion type for out door air break gang oprated switch, single pole mounted on and including insulators and jumpers for 33 KV working pressure fixed to and includingMS channel with nuts, bolts and washer etc, synthetic bounded fuse tube complete with line cap suitable for current carrying capcity upto 1000 Amps all as directed. |
| 31 | Supply and fix cable jointing kit for 33 KV grade cable for out doortermination heat shrink type joint complete with jointing material and accessories suitable for3 core XLPE armoured Al conductor cable of size 120 sq mm all as specfied and directed. |
| 32 | Supply, laying, testing & commissioning ofHT 33 KV (earthed) XLPE insulated screened PVC bedded, electric power cable, galvanized steel strip or wire armoured (heavy duty) with aluminium conductor 33000 volts grade conforming to IS 7098 Part II, 1985amended upto date, of size 3 core 120 Sqmm, ISI marked, laid in trenches or passing through pipes/ducts all as specified. Note:-1. Excavation and earthwork, sand cushioning, GI pipe, cable protection will be measured and paid for separately2.Cable shall be tested at high voltage testbefore & after laying. |
| 33 | Supply and fix, testing, commissioning of LT weather proof panel board powder coated outdoor type double door shutter, made out of CRCA 3.15 mm thickouter and 1.6 mm thick for inner door confirming to IS 8623 with angle iron 50 x 50 x 6mm outoor, floor mounting type with closed bus bar , chamber and with Aluminium bus barwith necessary insulator suitable for 3 phase, 4 wire 50 Hz AC supplyas per CPRI approved including provn of digital ammeter 0-1500A,digital voltemeter 0-500 Volts, CT\"s of suitable ratio,indicator lamps R-Y-B, selector switches and internal wiring including making PCC block type 0.6 Mtr above ground level grouting etc all as specified and directed with the following Work alsoincludes provision of suitable size of cable glands, cable lugs, nut, bolts, washers etc. The bottom portion of enclosure shall be minimum 60 cm above ground level of legs of angle iron )(Main panel)a) Aluminium bus bar capacity not less than1.5 times of incommerb) ACB 4 pole with Microprocesser Release type 1000 Amp 50 KA - 1 Nos c) MCCB 4 pole adjustable type 400 Amp 36 KA - 2 Nosd) MCCB 4 pole adjustable type 63 Amp 16 KA - 1 Nos e) MCB SPN 6-32 Amps 10 KA-2 Nos |
| 34 | All as per the description of serial item No 32.00 above but Digital Ameter of 0-1000A & consisting of followings :- (FP-1/FP-2)a) Aluminium bus bar capacity not less than 1.5 times of Incommerb)MCCB 4 pole adjustable type 400 Amp 36 KA - 1 No c) MCCB 4 pole adjustable type 200 Amp 25 KA - 2 No d)MCB SPN 6-32 Amps 10 KA- 2 Nos |
| 35 | All as per the description of serial item No 32.00 above but Digital Ameter of 0-1000A & consisting of followings :- (FP-3)a) Aluminium bus bar capacity not less than1.5 times of Incommerb)MCCB 4 pole adjustable type 63 Amp 16 KA - 1 No c) MCCB 4 pole adjustable type 63 Amp 16 KA - 1 No d)MCB SPN 6-32 Amps 10 KA- 2 Nos |
| 36 | Supply & fix juction box of size 155X210X92 mm IP 66 thermoplastic PC -GFS polycarbonate weather proof with degree of protection against mechanical load IK09 with plain walls of cables entries to be drilled individually .The juction box internally embedded polyurethane material gaskit.colour-black,RAL 9011.Fixed on pole with the help of MS nuts bolts & MS clamps - 2 Nos of size 40mm x 4mm thick with one No MCB SP 6 amp capacity mounted on din rail inside box.Work also includes making suitable hole in pole to take out connections to fitting if required at site. |
| 37 | Supplyand fixing street light bracket made out of 40 mm light grade GI tubing minimum 1.2 mtr ling with suitable adapter to suit the opening of street light on one end alongwith integrated fabricated adapter round cup type with 4 Nos studs on outer side to fix the bracket on top ofexisting steel tubularpoletwoway,with necessary MS clamps with one coat of red oxide and two coats of aluminium paint upon fabricated adapter including nut, bolt, washers complete as specified and directed by Engineer-in-charge. |
| 38 | Supply and fixing Automatic operation street light timing switch having lighting control (ON-OFF) through Astronomical Calculation of Sun rise/sun set by setting date, time and degree of longitude and latitude without separate light sensors and pre-wired with suitable size copper conductor single core PVC sheathed cable and all mechanism fitted into LT feeder pillar box (KIOSK) outdoor type, pole mounted. The panel shall be dust and vernin proof, made ofCRCA MS sheet fixed with 25mm X 4mm thick MS flate iron strip complete with nuts, bolts & washwers, duly powder coated finish. Front opening type with locking arrangement complete all as specified and directed suitable for three phase and neutral with under and over voltage protection relay, contactor 65A/63A TP, MCB 63A TPN, 415 volts, 50 Hz, AC supply system complete as specified and directed |
| 39 | M&L for precast cable route Indicator made out of cement concrete1:2:4, type B1, using(20mm graded stone aggregate) having 10cm square shape at top and 20cm square shape at bottom and total height of 90cm casted as per direction of Engineer-in-Charge and grouted into PCC 1:2:4, type B-1, 35cm below ground level as per site requirement including embossed with \"HT 33000 V Cable\" and also painting in synthetic enamel Paint and necessary excavation and earth work in any type of soil as directed by Engr-in-Charge. |
| 40 | Supply and fix heavy duty industrial type air circulator fans 230 volts single phase oscillating 600 mm sweep suitable for wall mounting.(for Sml room) |
| 41 | Supply and fix 63 amp 3 phase wall mounted socket with MCB and enclosure all as specfied and directed. |
| 42 | Supply, installation testing and commissioning of OEM manufactured, static silent (sound proof enclosure), Disel engine driven generating set capable of delivering 200 KVA(in case of non availablity next higher capacity shall be provided without any price adjustment), water cooled, 415 volts (AC, 3 phase, 4 wire system of supply) 50 Hz at power factor 0.8 minimum. The DG set shall consists of diesel engine coupled to a matching alternator through flexible coupling and mounted on common base frame with control panel standardised by manufacturer, fuel tank with mounting arrangements and inlet outlet return inlet oil arrangemnet, exhaust pipe complete and suitable for conditions prevelant at site location, (the capacity of engine & alternator shall be worked out taking all derating factors into consideration of the location of site)including PCC foundation of suitable size (leaving atleast 0.5m all round space for easy of movement and 0.5m height) anti vibration pads, including emission control devices to make it compliant of emission limits as brought out in the GSR issued by Min. of Enviornment and all features with latest CPCB guidelines and comprising of following complete all as specified and directed:- |
| 43 | (i) ENGINE (Prime Mover ) : Diesel Engine 1500 RPM, direct injection six cylinders, type four stroke, confirming to ISO 3046 /BS 5514, water cooled, naturally turbo charged, capable of giving adequate BHP to drive alternator capable of delivering 200 KVA at outdoor atmospheric conditions of site location, (taking all derating factor into consideration), 12/24 Volt (as permanufacturer recommendations) electric battery start, complete with fly wheel all standardwithfittings/fixtures as per manufacturer and including suitable panel with tachometer, lubtemperature, pressure guage and frequency meters and also including self starter system, dynamo, fuel electric control panel with electronic governor (ECPG) and engine protection system (shut down, High water temperature, low lub oil, oil pressure, over speed etc) fuel tank and first fill of lub oil and other consumables etc. |
| 44 | (ii) ALTERNATOR :Brushless AC alternator, 3 phase, 415 volt , 4 wire, rated for suitable output to drive the engine, Minimum power factor 0.8, 1500 RPM, IP 23 protection class enclosure, insulation class “H” salient pole, revolving field singlebearing automatic voltage regulator coupledthroughflexible coupling with and to match the above engine.Note: Alternator Capacity shall be calculated as per ambient temperature of the site location.(iii) BASE PLATE :- Made out of structural steel as per manufactures recommended design/specifications.(iv) IN BUILT AMF CONTROL PANAL : Factory made, cubical type, in-built AMF panel borad,indoor type made out of MS angle not less than 25 x 25 x 5 mm and 2 mm thick MS CRCA sheet,front opening type, protection class IP-54, duly powder coated after seven tank process, withelectrolytic grade copper bus bar of 200 Amps capacity for four poles, with all standardswitchgear and protection, internal wiring of adequate size PVC insulated multistranded copperconductor cable etc and also consisting of following :- (a) MCCB, 320 Amp, 415 Volts rating, 4 pole, 35 kA rupturing capacity, specially fixed for incoming supply with over load relay, short circuit and fault protection – 01 No with suitable rating HRC back up fuses.(b) AMF logic panel including wiring, power contractor with MCCB suitable capacity for DG Set of main supply, single phase preventor, digital multifunction meter (showing Amps, Volts, Hz, KWH etc.) Emergency stop Button, DGSet over load, High water temp, Low lub oil pressure, Auto charging unit and failure to start, Phase indication lamp LED type RYB including all relays, circuit and protection required for automatic operation of DG Set. |
| 45 | (c) Change over switchof bus bar capacity 400 Amp, 440 volt, 50 Hz including all copper lugs, nut, bolt and connected accessories - 03 Nos(v) ACCOUSTICENCLOSURE :Sheet metal fabricated cope type, silent enclosure, manufactured on CNC machines as per CPCB norms and powder coated after seven tank process; the enclosure shall be designed for reducing the sound level to 75 DB (A) at a distanceof 1 M at 75% load under field condition and OX, 70 DB at 3 M from Gen set when DG set is working at full load alongwith testing conformance, lebelling certification etc as laid down in GSR No. 371 (E) dt 17 May 2002.(vi) Foundation / Plinth / Base : shallbe provided as per manufacturers recommendations with atleast 0.5m all round space for easy of movement and 0.5m height (minimum).(vii) Diesel storage tank : shall be as per manufacturers specifications.(viii) MISC: Tool kit, operation & maintenance catalogue, spare part list, overhauling manuals, gurantee card, etc shall be provided as per manufacturers standard practices without any extra cost to the department. |