| 1 | Supplying Installation Testing Commissioning of Central Control Server System comprising of Intel® Xeon® CPU E5-2640 x64 (or better) compatible with dual and quad core processors, Windows 11 (Professional, Enterprise, Ultimate, 64 bit), Windows Server 2013 R2 (Standard, Enterprise, 64 bit) 16 GB or more, Video card and monitor capable of displaying at 1024 x 768 resolution or better, Latest Microsoft Licence Version Operating System Loaded with MS OFFICE 2019 Professional, Word, EXCEL, Power Point, Outlook Express, Microsoft Team official version lifetime licences suitable for running BMS software complete etc. as required. |
| 2 | Supplying Installation Testing Commissioning of Client PC System comprising of PC Hardware withminimum11th Gen Intel® I7 processor CPU E5-2640x64 (or better), compatible with dual and quad core processors minimum 3.1 Ghz and 8GB or higher RAM, Hard Drive Space of 256 GB SSD or better, Video card and monitor capable of 1920 x 1080 pixel resolution or better with Ethernet adapter (10/100/1000 Mbps with RJ-45 connector) with 2 GBor higher Graphics card suitable for BMS System complete etc. as required. |
| 3 | Supplying, Installation, Testing and Commissioning of following size LED display (LED monitor) industrial grade with 3840x2160 resolution or better, USB playback, bluetooth and miracast connectivity, 4X HDMI 2.0, DP 1.2, HDR 10/10+, brightness: 500-nits or better, Video wall mode should be available, contrast ratio: 1200:1, OPS slot, viewing angle (H/V): 170°/ 170°, response time less than 12ms, Display control shall be on monitor screen and programmable with remote (remote shall be supplied with system), Key Board, Optical Mouse, etc. as required32 inch or larger |
| 4 | Supplying Installation Testing Commissioning of Necessary Software (UL listed) Packages containing Building Management with Capability of Collection, Storage, Processing and Controlling all the Data. Software shall support Open Standard Protocols like XML, BACnet, Modbus, Lon works etc. and without the use of Proprietary Protocols, with Enterprise Level Database Like MS SQL complete Lifetime Licenced & capable to collect, store & access all points from Fire Alarm Systems, IT Systems, Lighting Automation Systems, HVAC System, Lift, Energy management, Water Management System, etc. to create & monitor historical & event data, event management data, alarm management data & reporting data, Email Alerts for Critical alarms for all the systems. The scope includes additional software required by BMS software (to enable a standard Web browser) to be resident on the DDC/client machine (manufacture-specific browsers shall not be acceptable). User log-on identification and password shall be required & a minimum three-layered security system(User interface Level, Application Level and Data Base Level) to be deployed for safety. The supplied computer software shall employ objectoriented technology (OOT) for representation of all data and control devices within the system. This data shall reside on a server for all database access (Systems requiring proprietary database and user interface programs shall not be acceptable). All components and controllers supplied under this contract shall be true “peer-to-peer” communicating devices (Components or controllers requiring “polling” by a Master / Global / Host to pass data shall NOT be acceptable). Physical connection of BACnet/MOD BUS devices shall be via Ethernet at all levels. The License must be provided by default. The BMS software shall be complete in all respect to cater the following different numbers of points managed in the installation. Upto 2500 Points included. |
| 5 | Supplying Installation Testing Commissioning of IP Based DDC controller capable of fully “stand- alone” operation i.e. In the event of loss of communication with other DDC’s or Control Station, they shall be able to function on their own. The controllers shall consist of dual/quad core 32 bit microprocessors with EPROM based operating system on BACNET. The network Topology shall not allow single point failure. Each DDC on field level shall have embedded TCP/IP (10/100Mbps) connectivity so that it can be hooked into the Local Area Network (LAN) provided by the client or on dedicated network . Each DDC can be accessed from the Graphical User Interface (GUI) or from a standard Web browser (WBI) by connecting the server alongwith inbuilt web browser. All controllers shall accept 230V+/- 10%, 50Hz Uninterrupted power supply provided by end user. Controller shall support DHCP addressing over Local Area Network (LAN) so that the static IP requirements get reduced however a single static IP shall be provided for system so that it can be hosted on to internet in consultation with end user. The microprocessor based DDC’s shall be provided with power supply, analoge to Digital and Digital to analoge converters with memory and capacity to accommodate input/output (I/O) hardware points (with or without an expansion board). Each DDC should have own board and shall accept 0-10 V / 4-20mA input signal having Minimum 20% spare capacity considered for expansion. Each DDC on field level should have minimum 128MB RAM & 64MB Flash memory. Following type of All controllers should be mandatorily BTL approved with B-BC profile complete etc. as required (Using of existing enclouser for DDC Controller) Type-IV (Support upto 128 Points) |
| 6 | Supplying Installation Testing Commissioning of following type of input output (IO) expansion module complete etc. as required. |
| 7 | I/O Module with 4 UIO channels |
| 8 | I/O Module with 8 UIO channels |
| 9 | I/O Module with 8 UI channels |
| 10 | I/O Module with 8 DI channels |
| 11 | I/O Module with 16 DI channels |
| 12 | I/O Module with 8 DO channels |
| 13 | I/O Module with 4 DO channels |
| 14 | Supplying Installation Testing Commissioning following type 3rd party Integration unit to provide the interface between Ethernet LAN and the 3rd party field control devices or any other devices which need to be integrated. These shall also provide supervisory capability of functions over the devices connected to it. The purpose of using these units should be limited to integrate the devices only. The Unit must have two onboard Ethernet port, minimum 2/3 on board RS485 ports. The Integration unit should have inbuilt 4GB memory for program storage. The Unit must communicate over TCP/IP with communication speed of 10/100MBPS. The Integration unit should be capable of handling multiple protocol simultaneously such as Bacnet, Modbus, SNMP restricted to single protocol. All integrators should be mandatorily BTL listed. The integration unit shall be housed in suitable size sheet steel enclosure made of 1.6mm thick CRCA sheet, lockable front door with glass, arrangement for cable entry and duly powder coated complete etc as required.Integrator for 1250 Points |
| 15 | Supplying Installation Testing Commissioning of following Field Devices including connection etc. as required |
| 16 | Differential pressure switch for filters & Blowers |
| 17 | Duct type temperature sensor Measuring range: -30 to 110 Deg.C, Accuracy: +/- 1.3 Deg.C |
| 18 | Supplying & laying of 2x1.5 sqmm armoured cable,600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required. |
| 19 | 4 Port network switch |
| 20 | Armoured CAT 6 cable outer dia.10 mm |
| 21 | Duct mounted Temperature andRH sensor for montoring of return air |
| 22 | Supply, installation,testingandcommissioningof Duct mounted electrical heater packagewithall necessary controls (Thermostat,Humidstat etc.) asrequiredas perstandardspecification and Folowing capacities |
| 23 | 4KW |
| 24 | 6 KW |
| 25 | Communication,cabling contiunuity checking,connections,laying with proper arrangements etc as required in complete shape for the existing Honeywell makes BMS without replacing of DDC,field devices, Comunication canbles,port etc as instructed by the Engineers- In-Charge |