| 1 | Providing and fixing of 9 watt LED Decorative, wall mounting, brushed nickel finish fixture with acrylic diffuser with 9 W LED lamp B22 base with wire complete with connection, testing commissioning etc as required. |
| 2 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
| 3 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.(Upto 450 mm sweep) |
| 4 | Erection of wall bracket /ceiling fittings/Tube light fittings of all sizes and shapes containing upto two GLS lamps per fitting, complete with all accessories including connection etc. as required. |
| 5 | SITC of indoor type double door compartmentalized cubical panel of suitable size for 415 Volt, 3 phases, 50 Hz made out of 2mm thick CRCA sheet and depth up to 300 mm with required hardware duly painted with powder coated. The panel having separate detachable gland plate, hinged door, with locking arrangement, earth bar/stud, 400 A/415V 4 strip aluminum bus bar duly PVC sleeved, including electrical mechanical interlocking, connection inter–connection for incoming/Outgoing cables with the required current capacity bus bar links (as per direction of Engg in charge), space forMCCBs and change over. The panel should be mounted on MS Base frame 75 mm x 40 mm x 5mm of suitable size and should have the provision of following instruments mounted and includingprovision of outgoing cable connections bus bar links of required current carrying capacityetc as required. (Indoor Panel should be as per design &drawing approved by Engg in charge and comprising of)Instruments Panel )a) VAF Meter in each panel to be designb) LED Pilot light (22.5 MM dia) withprotection MCB’s-03Nos) |
| 6 | Providing and fixing of following accessories in the above/existing cubical panel as mentioned in the existing/new panels i/c connection inter-connection with aluminum bus bar of required size and current carrying capacity etc as required as per direction of Engg in charge. (In item No 5) i) 125 A TP MCCB 25KA with thermal magnetic releaseLV516332 Schneider |
| 7 | Providing and fixing of following accessories in the above/existing cubical panel as mentioned in the existing/new panels i/c connection inter-connection with aluminum bus bar of required size and current carrying capacity etc as required as per direction of Engg in charge. (In item No 5) ii) 100 A TP MCCB 16-18 KA with thermal magnetic releaseLV510938 Schneider |
| 8 | Providing and fixing of following accessories in the above/existing cubical panel as mentioned in the existing/new panels i/c connection inter-connection with aluminum bus bar of required size and current carrying capacity etc as required as per direction of Engg in charge. (In item No 5) iii) 63 A TP MCCB 16-18 KA with thermal magnetic release LV510934 Schneider |
| 9 | Providing and fixing of following accessories in the above/existing cubical panel as mentioned in the existing/new panels i/c connection inter-connection with aluminum bus bar of required size and current carrying capacity etc as required as per direction of Engg in charge. (In item No 5) i) Spreader Links for 125 Amp TP MCCB |
| 10 | Providing and fixing of following accessories in the above/existing cubical panel as mentioned in the existing/new panels i/c connection inter-connection with aluminum bus bar of required size and current carrying capacity etc as required as per direction of Engg in charge. (In item No 5) ii) Spreader Links for 100 Amp TP MCCB |
| 11 | Providing and fixing of following accessories in the above/existing cubical panel as mentioned in the existing/new panels i/c connection inter-connection with aluminum bus bar of required size and current carrying capacity etc as required as per direction of Engg in charge. (In item No 5)iii) Spreader Links for 63 Amp TP MCCB |
| 12 | Earthingwith G.I. earth pipe4.5mtr long x 40mm dia including accessories and providing masonary enclosure with cover platehaving locking arrangement and watering pipe etc. withcharcoalor coke and salt complete as required. |
| 13 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 14 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required |