| 1 | Surface dressing n exc 15 cm deep including site clearance of any type of soil complete all as specified and as directed. |
| 2 | Excavation in trenches, n.exc 1.5m wide and n.exc 1.5m depth for foundation etc. or for shafts, wells, cesspits, manholes, pier holes, taking up/ laying of underground cableand getting out in any type of soil complete all as specified and as directed. |
| 3 | Returning, filling in trenches of any type of soil including spreading, leveling watering and well ramming in layers not exceeding 25 cm thick complete all as specified and as directed. |
| 4 | Removing of excavated soil not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as specified and directed. |
| 5 | M&L for PCC (1:4:8), type D-2 using 40mm graded stone aggregates as in foundation, filling and mass concretecomplete all as specified and directed. |
| 6 | M&L for brick work with fly ash bricks, straight or curved on plan exc 6 m mean radius, built in cement mortar (1:6) complete all as specified and directed. |
| 7 | M&L for rendering 15 mm thickon concrete/brick surface on wallin cement mortar (1:6) other than fair face of brick work, finished even and smooth without using extra cementcomplete all as specified and directed. |
| 8 | M & Lfor moorum/red bajri filling in floors or pavings, laid in layers n exc. 15 cm thick, spread, levelled and rammed including watering complete all as specified and directed. |
| 9 | M&L for hard core of broken stone or boulders of gauge not exc 63mm deposited spread and leveled in layers not exceeding 15cm thick watered and rammed to a true surface complete all as specified and directed. |
| 10 | M & L for sand filling under floors or in foundations including watering and consolidation complete all as specified and directed. |
| 11 | S & F for polythene film, 150 micron thick, laidin floor complete all as specified and directed. |
| 12 | M&L for 100mm thickPCC (1:3:6), type C-2 (using 40mm graded stone aggregates) as in sub base of floorsincluding necessary form workeven and rough to receive the topping layer in DG shed complete all as specified and directed. |
| 13 | M&L for 75 mm thickPCC (1:2:4), type B-1 (using 20mm graded stone aggregates) as in path, hardstanding including necessary form work and even and smoth without using extra cement in DG shed complete all as specified and directed. |
| 14 | S & Ffor 3mm thick glass dividing strips and 38mm wide inserted in position and confirm to design complete all as specified and directed. |
| 15 | Excavating in post holes (or similar holes) each n exc 0.5 cu m, getting out in soft/ lose soil, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, including watering and removing surplus soil to a distance not exc. 50m and making good the surface omplete all as specified and directed. |
| 16 | S &F for structural steel work in tubular trusses including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to IS 1161-1979 grade St.-240 complete all as specified and directed. |
| 17 | M&L for plates Fe-410-W (Gde-E-250) quality-B (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment complete all as specified and directed. |
| 18 | M&L for preparation of new or previously untreated steel surfaces of any description, over 10cm in width or girth andapplying two coats of synthetic enamel paint over a coat of red oxide zic chrome primer complete all as specified and directed. |
| 19 | S&F for pre-painted galvalume aluminium zinc coated GI based corrugated steel sheet 0.50mmthick of approved colour having tensile strength 550 Mpa as in roof covering/cladding to wall fixed with self tapping screws including side and end lap as per manufacturer’s instructions complete all as specified and directed. |
| 20 | S&F for pre-painted galvalume aluminium zinc coated GI based plain steel sheet 0.50mmthick of approved colour having tensile strength 550 Mpa as in ridges, hips, valley gutters, fixed with self tapping screws including side and end lap as per manufacturer’s instructions complete all as specified and directed. |
| 21 | M & L for Hand rails, wind ties for roof including securing bolts posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for ecuring wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar workonforming to Fe-290 Gde E-165 complete all as specified and directed |
| 22 | M&L for applying two coats of cement based paint over a coat of cement primer on new wall surfaces complete all as specified and directed. |
| 23 | M&L for 75mm thick PCC type C-2 (1:3:6), (using 40 mm graded stone aggregates) as in sub base of path including necessary form workeven and rough to receive the topping layercomplete all as specified and directed. |
| 24 | M&L for chequered cement concrete tiles of size 30 cm x 30cmx22 mm thick set, jointed in neat cement slurry in floor and pointed in white or grey cement and no pigment of machine pressed to match the shade of tiles laid over and including 15 mm thick screed bed in cement mortar (1:6) complete all as specified and as directed. |
| 25 | Design, fabrication,supply, insallation, testing and commissioning LT panel board (outdoor type floor mounted)of size1000mm x 800mm x 400mm suitable for working on 3 phase, 4 wire, 415 volts, AC, 50 Hz outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation, factory fabricated made out of 3.2mm thick CRCA sheet duly powder coated (seven tank process) and as approved by GE.The panel shall have front and rear opening, locking arrangement, bus bar chamber and switch gear compartment, hinged door with rubber gasket, botton cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate, aluminium bus bar duly covered with heat shrink sleeves colour coded duly fixed on DMC/SMC insulators, aluminium strip connection from bus bar to outgoing MCCBs and copper conductor cable of adequte size of MCBs, housed in a separate bus bar chamber and control wiring adequate size and length,MCCBs shall have extended bus bar links and panel mounted on 50x50x5mm size MS angle iron frame duly painted in and including PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) in foundation design subject to approval of GE as per as site requirement.Minimum claerance from ground level is 450 mmcomplete all as specified and comprising :-(a)MCCB, 160 Amps, FP, 25 KA, 415 volts, 50 Hz- 01 No (in coming)(b) MCCB, 125 Amps, FP, 16 KA, 415 volts, 50 Hz- 01 No (outgoing) (c)MCCB, 63 Amps, FP, 16 KA, 415 volts, 50 Hz- 02 Nos (outgoing) (d) Digital multi-fuctional meters for measuring current, voltage and frequency including CTs of suitable rating and class- 01 No (as out going) (e) Digital voltmeter (0-500V) withCTs and VSS-01 set, Digital Ammeter (0-100A), with CTs & ASS-01 set (f)LED phase indication lamps RYB-01 set(g) Aluminium bus bar TPN 400 Amps rating - 01 set (Note: LT panel drawing to be approved by GE duly recommended by Engr-in-Charge). ( Make: C&S/ L&T/Legrand/Siemens/Schneider) |
| 26 | Design, fabrication,supply, insallation, testing and commissioning LT panel board (outdoor type floor mounted)of size1000mm x 800mm x 400mm suitable for working on 3 phase, 4 wire, 415 volts, AC, 50 Hz outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation, factory fabricated made out of 3.2mm thick CRCA sheet duly powder coated (seven tank process) and as approved by GE.The panel shall have front and rear opening, locking arrangement, bus bar chamber and switch gear compartment, hinged door with rubber gasket, botton cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate, aluminium bus bar duly covered with heat shrink sleeves colour coded duly fixed on DMC/SMC insulators, aluminium strip connection from bus bar to outgoing MCCBs and copper conductor cable of adequte size of MCBs, housed in a separate bus bar chamber and control wiring adequate size and length,MCCBs shall have extended bus bar links and panel mounted on 50x50x5mm size MS angle iron frame duly painted in and including PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) in foundation design subject to approval of GE as per as site requirement.Minimum claerance from ground level is 450 mmcomplete all as specified and comprising :-(a)MCCB, 100 Amps, FP, 25 KA, 415 volts, 50 Hz- 01 No (in coming)(b) MCCB, 63 Amps, FP, 16 KA, 415 volts, 50 Hz- 01 No (outgoing) (c)MCCB, 16 Amps, FP, 16 KA, 415 volts, 50 Hz- 03 Nos (outgoing) (d) Change over switch, 125Amps, FP-01 Nos (e) Digital multi-fuctional meters for measuring current, voltage and frequency including CTs of suitable rating and class- 01 No (as out going) (f) Digital voltmeter (0-500V) withCTs and VSS-01 set, Digital Ammeter (0-100A), with CTs & ASS-01 set (g)LED phase indication lamps RYB-01 set(h) Aluminium bus bar TPN 400 Amps rating - 01 set (Note: LT panel drawing to be approved by GE duly recommended by Engr-in-Charge). ( Make: C&S/ L&T/Legrand/Siemens/Schneider) |
| 27 | Design, fabrication,supply, insallation, testing and commissioning LT panel board (outdoor type floor mounted)of size1200mm x 900mm x 400mm suitable for working on 3 phase, 4 wire, 415 volts, AC, 50 Hz outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation, factory fabricated made out of 3.2mm thick CRCA sheet duly powder coated (seven tank process) and as approved by GE.The panel shall have front and rear opening, locking arrangement, bus bar chamber and switch gear compartment, hinged door with rubber gasket, botton cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate, aluminium bus bar duly covered with heat shrink sleeves colour coded duly fixed on DMC/SMC insulators, aluminium strip connection from bus bar to outgoing MCCBs and copper conductor cable of adequte size of MCBs, housed in a separate bus bar chamber and control wiring adequate size and length,MCCBs shall have extended bus bar links and panel mounted on 50x50x5mm size MS angle iron frame duly painted in and including PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) in foundation design subject to approval of GE as per as site requirement.Minimum claerance from ground level is 450 mmcomplete all as specified and comprising :-(a)MCCB, 100 Amps, FP, 25 KA, 415 volts, 50 Hz- 01 No (in coming)(b) MCCB, 63 Amps, FP, 16 KA, 415 volts, 50 Hz- 01 No (outgoing) (c)MCCB, 16 Amps, FP, 16 KA, 415 volts, 50 Hz- 03 Nos (outgoing) (d) Digital multi-fuctional meters for measuring current, voltage and frequency including CTs of suitable rating and class- 01 No (as out going) (e) Digital voltmeter (0-500V) withCTs and VSS-01 set, Digital Ammeter (0-100A), with CTs & ASS-01 set (f)LED phase indication lamps RYB-01 set(g) Aluminium bus bar TPN 400 Amps rating - 01 set (Note: LT panel drawing to be approved by GE duly recommended by Engr-in-Charge).( Make: C&S/ L&T/Legrand/Siemens/Schneider) |
| 28 | M & L for PCC 1:2:4 type C2 using 20mm graded for padestal coping incl necessary formwork finished fair using extra cement omplete all as specified and directed by Engineer-in-Charge |
| 29 | M&L for earthing complete with galvanised steel earth plate electrode 600x600x6mm thick burried directly in ground earth pit not less than 2.25m deep below ground level with top edge of the plate not less than 1.5m deep below normal ground levelconnected to and including 32/6mm thick galvanised iron strip as earthing lead by means ofbolts, nuts, checknuts and washers of galvanised iron or steel all as specified in electrical plate No 3 of SSR (2009) part-I including 50mm bore GI pipe (light grade) for protection of earth strip and PCC (1:3:6) type C-1 as in pit, Precast RCC earth pit cover 8 cm thick reinforced with 8mm dia TMT bars @150mmc/c and two handles made out of 8mm dia round mild steel bar, excavation and earth work in any type of soil and alternate layers of charcoal, common salt and 20mm bore galvanised medium grade steel tubing for watering with one end fixed with cast iron funnel and wire mesh and testing on completion after dismantling of old unserviceable earthing with all material etc all as specified and directed.(Note:- (i) Earth strip and protection pipe upto board 7.5 m and others mentioned in above are included in this item (ii) The earthing pit shall be provide with proper earth pit and pit cover (iii) pit cover shall be painted with two coats of cement base paint of approved colour and pit number to be marked on a GI plate above 45 cm from GL as per colour code followed by AF authority (iv) Purchase voucher of GI plate and strip having GST number shall be provided before the payment claim (v) Earthing test certificate from users shall be provided before the payment claim) |
| 30 | M&L for earthing complete with copper earth plate electrode 600x600x3.15 mm thick burried directly in ground earth pit not less than 2.25m deep below ground level with top edge of the plate not less than 1.5m deep below normal ground levelconnected to and including 20x3mm thick copper strip as earthing lead by means ofbolts, nuts, check nuts and washers of galvanised iron or steel all as specified in electrical plate No 3 of SSR (2009) part-I including 50mm bore GI pipe (light grade) for protection of earth strip and PCC (1:3:6) type C-1 as in pit, Precast RCC earth pit cover 8 cm thick reinforced with 8mm dia TMT bars @150mmc/c and two handles made out of 8mm dia round mild steel bar, excavation and earth work in any type of soil and alternate layers of charcoal, common salt and 20mm bore galvanised medium grade steel tubing for watering with one end fixed with cast iron funnel and wire mesh and testing on completion after dismantling of old unserviceable earthing with all material etc all as specified and directed.(Note:- (i) Earth strip and protection pipe upto board 7.5 m and others mentoned above are included in this item (ii) The earthing pit shall be provide with proper earth pit and pit cover (iii) pit cover shall be painted with two coats of cement base paint of approved colour and pit number to be marked on a GI plate above 45 cm from GL as per colour code followed by AF authority (iv) Purchase voucher of GI plate and strip having GST number shall be provided before the payment claim (v) Earthing test certificate from users shall be provided before the payment claim) |
| 31 | Material and labour for Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6.3 mm thick buried directly in ground( earth pit not less than 2.25 mtrs deep below normal ground level )with the top edges of plate not less than 1.5 mtrs below normal ground level connected to GI wire 4mmby means of GInuts, bolts check nuts and washers earth lead protected by 15mm dia GI pipe light grade and connected to main distribution board/earthing test pointall as shown in electrical plate No 3 of SSR part 1 and all as specified including taking down old unserviceable earthing and testing of earthing on completion. Notes:-The unit rate also including for excavation, earth work in any type of strata, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix , type B1 cover reinforced with 8mm dia TMT bars @150mm C/C both ways ,GI funnel with GIwatering pipe 20mm dia medium grade, wire mesh, protection pipe 15mm dia GI pipe light grade for earth lead upto 7.50m long complete all specified and directed.(Note:- (i) Earth wire and protection pipe upto board 7.5 m and others mentoned above are included in this item (ii) The earthing pit shall be provide with proper earth pit and pit cover (iii) pit cover shall be painted with two coats of cement base paint of approved colour and pit number to be marked on a GI plate above 45 cm from GL as per colour code followed by AF authority (iv) Purchase voucher of GI plate and strip having GST number shall be provided before the payment claim (v) Earthing test certificate from users shall be provided before the payment claim) |
| 32 | Design, fabrication,supply, insallation, testing and commissioning LT Junction box (outdoor type floor mounted)of size 800mm x 600mm x 400mm suitable for working on 3 phase, 4 wire, 415 volts, AC, 50 Hz outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation, factory fabricated made out of 3.2mm thick CRCA sheet duly powder coated (seven tank process) and as approved by GE.The panel shall have front and rear opening, locking arrangement, bus bar chamber and switch gear compartment, hinged door with rubber gasket, botton cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate, aluminium bus bar duly covered with heat shrink sleeves colour coded duly fixed on DMC/SMC insulators, aluminium strip connection from bus bar to outgoing MCCBs and copper conductor cable of adequte size of MCBs, housed in a separate bus bar chamber and control wiring adequate size and length,MCCBs shall have extended bus bar links and panel mounted on 50x50x5mm size MS angle iron frame duly painted in and including PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) in foundation design subject to approval of GE as per as site requirement.Minimum claerance from ground level is 450 mmcomplete all as specified and comprising :-(a)MCCB, 320 Amps, FP, 36 KA, 415 volts, 50 Hz- 01 No (in coming)(b) Digital multi-fuctional meters for measuring current, voltage and frequency including CTs of suitable rating and class- 01 No (as out going) (c) Digital voltmeter (0-500V) withCTs and VSS-01 set, Digital Ammeter (0-100A), with CTs & ASS-01 set (d)LED phase indication lamps RYB-01 set(e) Aluminium bus bar TPN 600 Amps rating - 01 set (Note: LT Junction boxdrawing to be approved by GE duly recommended by Engr-in-Charge). ( Make: C&S/ L&T/Legrand/Siemens/Schneider) |
| 33 | Supply,laying, jointing and testing,XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 300 sqmm 3.5 core laid in trenches/ on wall, ducts, pipes, on poles and connection with necessary cables lugs, glands, suitable for mild steel saddle clips (were cable laid in ceilings/wall without cable duct) nut bolts complete. all as specified and directed.(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). |
| 34 | Supply,laying, jointing and testing,XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 150 sqmm 3.5 core laid in trenches/ on wall, ducts, pipes, on poles and connection with necessary cables lugs, glands, suitable for mild steel saddle clips (were cable laid in ceilings/wall without cable duct) nut bolts complete. all as specified and directed.(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). |
| 35 | Supply,laying, jointing and testing,XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 95 sqmm 3.5 core laid in trenches/ on wall, ducts, pipes, on poles and connection with necessary cables lugs, glands, suitable for mild steel saddle clips (were cable laid in ceilings/wall without cable duct) nut bolts complete. all as specified and directed.(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). |
| 36 | Supply,laying, jointing and testing,XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 70 sqmm 3.5 core laid in trenches/ on wall, ducts, pipes, on poles and connection with necessary cables lugs, glands, suitable for mild steel saddle clips (were cable laid in ceilings/wall without cable duct) nut bolts complete. all as specified and directed.(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). |
| 37 | Supply,laying, jointing and testing,XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 16 sqmm 4.00 core laid in trenches/ on wall, ducts, pipes, on poles and connection with necessary cables lugs, glands, suitable for mild steel saddle clips (were cable laid in ceilings/wall without cable duct) nut bolts complete. all as specified and directed.(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). |
| 38 | M&L for dry sand cushioning to underground cable, provided with a layer 8 cm thick before and 15 cm deep after laying and stretching jointing and testing the cable complete all as specified and as directed.(Note: Punned thickness of sand shall be measured and paid). |
| 39 | M&L for 50mm dia galvanized steel tubing (light grade) with complete all fittings such as elbow, unions, nipples, tees, bends, short pieces, connections, check-nuts, caps, plugs, diminishing pieces and flanges etc as in pole, crossing of roads, laid in trenches, fixed on walls for cable protection complete all as specified and directed. |
| 40 | M&L for brick covering with width equal to length of brick as mechanical protection to cable using sub class ‘B’ bricks laid flat,size 230mm x 115mmx 75mm, complete all as specified and as directed. |
| 41 | M&L for boring of holes under road, pavement, hard standing by trenchless technology/manual excavation as necessary including machine, tools etc as per site requirement complete all as specified and directed. |
| 42 | M&L for 80mm dia galvanized steel tubing (light grade) with complete all fittings such as elbow, unions, nipples, tees, bends, short pieces, connections, check-nuts, caps, plugs, diminishing pieces and flanges etc as in pole, crossing of roads, laid in trenches, fixed on walls for cable protection complete all as specified and directed. |
| 43 | Taking down andcarring the exisiting DG Set of capacity 63KVA from 31 Wg HQ and shifting it to SRE buildingand refixing the same at new said location within the Air force area complete all as specified and as directedby GE. (Note : (a) The cost ofnecessary taking down & carring of DG set throughtransportation of any mechanical method within the Air force area from one place to another place shall deemed to be included in the quoted rate. (b) Any damage of DG set during taking down, carring through transportation and fixing in new location shall be borne to tha contractor . Cost of damage recovered from the payment. (c) All the labour cost required in this work shall be included in this job .) |
| 44 | Taking down andcarring the exisiting DG Set of capacity 63KVA from TMQ power house and shifting it to pump house No 02and refixing the same at new said location within the Air force area complete all as specified and as directedby GE. (Note : (a) The cost ofnecessary taking down & carring of DG set throughtransportation of any mechanical method within the Air force area from one place to another place shall deemed to be included in the quoted rate. (b) Any damage of DG set during taking down, carring through transportation and fixing in new location shall be borne to tha contractor . Cost of damage recovered from the payment. (c) All the labour cost required in this work shall be included in this job .) |
| 45 | Taking down andcarring the exisiting DG Set of capacity 63KVA from power houseNo 03 and shifting it to pump house No 04and refixing the same at new said location within the Air force areacomplete all as specified and as directedby GE. (Note : (a) The cost ofnecessary taking down & carring of DG set throughtransportation of any mechanical method within the Air force area from one place to another place shall deemed to be included in the quoted rate. (b) Any damage of DG set during taking down, carring through transportation and fixing in new location shall be borne to tha contractor . Cost of damage recovered from the payment. (c) All the labour cost required in this work shall be included in this job .) |
| 46 | Taking down andcarring the exisiting DG Set of capacity 750KVA from 87SQM and shifting it to HQ building CSSand refixing the same at new said location within the Air force areacomplete all as specified and as directedby GE. (Note : (a) The cost ofnecessary taking down & carring of DG set throughtransportation of any mechanical method within the Air force area from one place to another place shall deemed to be included in the quoted rate. (b) Any damage of DG set during taking down, carring through transportation and fixing in new location shall be borne to tha contractor . Cost of damage recovered from the payment. (c) All the labour cost required in this work shall be included in this job .) |
| 47 | S&F for BMS system of 750KVA DG set including control panel, control wiring, sensors, with all fixing accessories complete all as specified and as directed. Make Cummins (product No KIT3238752) |
| 48 | S & Ffor ATS panel of 62.5/63 KVA DG set incl control wiring, nuts and bolts, PCC foundation (1:2:4) of 20mm graded aggregate etccomplete all as specified and as directed. ( Make: C&S/ L&T/Legrand/Siemens/Schneider) |