| 1 | Supply , installing, testing& commission of LT Paneloutdoor type, Cubicle type, as per IEC-61439-1 & 2 for 415 V ,50Hz,rated fault current : 50KA for 0.5 sec with internal arc containment dust, vermin proof, weather proof, IP-54 Grade of protection,providing Aluminium bus bar of capacity 700 Amps ratingincluding internal wiring using suitable size not less than 1.5 sqmm FRLS copper conductor cable along with ferouls. The panel shall be painted with anticorrosive coating and finally powder coated of flint gray shade (RAL -7032). the panel should be provided with multifunction meters, voltmeter, 3 phase indicators lamps and the panel should be mounted on \"C\" channel base of required size duly coated with anti corrosive paint. the circuit distribution lines to be marked over the panel using poly venylreflective stickering (Where necessary)complete with following in Pump House DRDL.INCOMING(a) MCCB 630 Amps 4 pole 50 KA with microprocessor release, Icu=50 KA Ics=100% of Icu with adjustable overload setting (minimum 70% to 100%) -01(b) Digital Multi function meter with V A PF Hz KVA KVAR with class -1 Accuracy 0-500 Amp-01(c) Indicator set ,SELECTOR SWITCH-01 setOUT GOING(a) MCCB FP 400 A, 36 KA- 01Nos along with Star delta starter (for 200 HP pump) -01 No(b) MCCB FP 63 A, 25 KA- 01 Nos along with Star delta starter (for 10 HP pump) -01 No(c) Spare space for MCCB FP 63 A, 25 KA -01No. |
| 2 | Supply , installing, testing& commission of LT Paneloutdoor type, Cubicle type, as per IEC-61439-1 & 2 for 415 V ,50Hz,rated fault current : 50KA for 0.5 sec with internal arc containment dust, vermin proof, weather proof, IP-54 Grade of protection,providing Aluminium bus bar of capacity 500 Amps ratingincluding internal wiring using suitable size not less than 1.5 sqmm FRLS copper conductor cable along with ferouls. The panel shall be painted with anticorrosive coating and finally powder coated of flint gray shade (RAL -7032). the panel should be provided with multifunction meters, voltmeter, 3 phase indicators lamps and the panel should be mounted on \"C\" channel base of required size duly coated with anti corrosive paint. the circuit distribution lines to be marked over the panel using poly venylreflective stickering (Where necessary)complete with following in Pump House DRDO Township.INCOMING(a) MCCB 400 Amps 4 pole 36 KA with microprocessor release, Icu=50 KA Ics=100% of Icu with adjustable overload setting (minimum 70% to 100%) -01(b) Digital Multi function meter with V A PF Hz KVA KVAR with class -1 Accuracy 0-500 Amp-01(c) Indicator set ,SELECTOR SWITCH-01 setOUT GOING(a) MCCB FP 250 A, 36 KA- 02Nos along with Star delta starter (for 60 HP pump -02 Nos)(b) MCCB FP 63 A, 25 KA- 04 Nos along with Star delta starter (for 15 HP booster pump & centrifugal pump-04 Nos)(c) Spare space for MCCB FP 63 A, 25 KA -01No. |
| 3 | Supply , installing, testing& commission of LT Paneloutdoor type, Cubicle type, as per IEC-61439-1 & 2 for 415 V ,50Hz,rated fault current : 50KA for 0.5 sec with internal arc containment dust, vermin proof, weather proof, IP-54 Grade of protection,providing Aluminium bus bar of capacity 400 Amps ratingincluding internal wiring using suitable size not less than 1.5 sqmm FRLS copper conductor cable along with ferouls. The panel shall be painted with anticorrosive coating and finally powder coated of flint gray shade (RAL -7032). the panel should be provided with multifunction meters, voltmeter, 3 phase indicators lamps and the panel should be mounted on \"C\" channel base of required size duly coated with anti corrosive paint. the circuit distribution lines to be marked over the panel using poly venylreflective stickering (Where necessary)complete with following in DSC Manjeer pump house .INCOMING(a) MCCB 250 Amps 4 pole 36 KA with microprocessor release, Icu=50 KA Ics=100% of Icu with adjustable overload setting (minimum 70% to 100%) -01(b) Digital Multi function meter with V A PF Hz KVA KVAR with class -1 Accuracy 0-500 Amp-01(c) Indicator set ,SELECTOR SWITCH-01 setOUT GOING(a) MCCB FP 125 A, 25 KA- 02Nos along with Star delta starter (for 12.5 HP pump -02 Nos)(b) Spare space for MCCB FP 63 A, 25 KA -02No. |
| 4 | M&L for Scrapping of old existing paint of pipe lines for Fire fighting system of 100 sizes and applying two coats of enemel paint to match with the existing shade complete all as directed.Note - Rate quoted shall be deemed to include cost of Paint & tools. Make - ASIAN/SHALIMAR/BERGER OR ITS EQUIVALENT |
| 5 | All as per item no 4 above but of size 150 mm dia |
| 6 | All as per item no 4 above but of size 200 mm dia |
| 7 | Material and labour for earthing complete with galvanised iron strip electrode 60x60cmx6mm thick, burried directly in ground(earth pit not less than 2.25metres deep below ground level) with top edge of the plate not less than 1.5metres below normal ground level, connected to galvanised earth lead strip of size 25x4 mmby means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.3 connected to switchgear equipments/motors protected by 40mm dia light grade GI pipe upto a length of 7.5mtr including necessary excavation earth work, charcoal and salt PCC 1:3:6 type C1 for chamber 40mm thick RCC cover slab 1:2:4 type B1 with 8 mm dia TMT bars @ 100mm c/c both ways, 20mm dia GI watering pipe medium grade with funnel complete and testing complete all asdirected. |
| 8 | Taking down old unserviceable hydrant valve and Supply, Installation, Testing and Commissioning of Single Headed Hydrant valve confirming to IS 5290 with ISI mark of size 63 mm dia oblique type with instantaneous hose coupling adaptor etc. with all neceesary fittng materials complete required. |
| 9 | Taking down old unserviceable hydrant valve and Supply, Installation, Testing and Commissioning of Double Headed Hydrant valve confirming to IS 5290 with ISI mark of size 63 mm dia oblique type with instantaneous hose coupling adaptor etc. with all neceesary fittng materials complete required. |
| 10 | Taking down old unserviceable hydrant hose pipe and Supply, Installation, Testing and Commissioningof Hydrant hose pipe, 63 mm dia and 1x15 mtrs long RRL type with Gunmetal 63 mm size male coupling at one end andfemale coupling at the other end.It should with stand a burtsting pressure of 450 psi, rot proofed, with ISI mark. Hose shall comply to IS 636 |
| 11 | Replacement of Hose box made of 18 gauge MS Sheet 800mm X 600mm X 250mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside yardall as specfied and directed. |
| 12 | Replacement of Fire hydrant stand post both ends flanged 1.5 Mtr long 80 mm dia with one end bent to 90 degrees suitable for long single fire hydrant valves including duck foot bend double end flanged and sluice valve all as specfied and directed. |
| 13 | Dismantling the Monoblock/Centrifugal pump set of 7.5 HP capacity 3 ph, 415V, AC, 50Hz after disconnection of electric/ pipe connections andproviding dummy plates to suction and delivery lines, Shifting to the reputed workshop for repairs andreplacing of minor spare parts like gaskets, packings, nuts, bolts and washers etc, and greasing, reassembling and replacement of other major parts as required and factory testing the rated flow discharge of the pump shifting to the original location and reconnecting of pipes/ electric connections at site andtesting to the entire satisfaction of the Engr-in-charge complete.Note : Parts like impellars, shafts , bearings, seal and lantern rings will measured and paid seperately under relevant items of Sch A |
| 14 | Supply only following spare parts suitable for Centrifugal pumpset of 7.5 HP |
| 15 | Impellar (Bronze) |
| 16 | Casing Wearing Rings |
| 17 | Inlet Flange |
| 18 | locking sleeve |
| 19 | Flinger |
| 20 | Seal retainer |
| 21 | Oil seal |
| 22 | Bearings as per existing model. Make: SKF/NBC or its equivalent |
| 23 | Bearing Retianer |
| 24 | Shaft |
| 25 | Material and Labour for Rewinding of centrifugal pump Motor of capacity 7.5 HP, 3Ph, 415V, AC, 50Hz with super enamelled copper wire of same gauge and same number of turns and applying insulating varnish including removing the burnt out winding with out damaging to other parts and cleaning the slots etc and testing complete all asdirected. |
| 26 | Taking out unserviceable DOL Starter from panel board after disconnecting electric connection and Supply and Fix DOL Starter suitable for 3 to 7.5 HP, 3Phase, 415Volts, AC, 50Hz and reconnection to existing system and testing complete all as as directed |
| 27 | Supply and fixCI sluice valve 80 mm diaclass PN 1.6 flanged type with grey cast iron body, bonnet dome, wedge, stuffing box, gland thrust plate cap, SS spindle stem, carbon steel bolts, nuts etc complete complying to IS 14846withnecessary fixing arrangement as required at site by providing rubber/ fibre gaskets inclduing taking out old unserviceable valve of any typecomplete all as directed.Make :- KIRLOSKAR//KARTAR/ Zoloto/Audco or its equivalent |
| 28 | All as per item No.17 above but of size 100 mm dia complete all as directed |
| 29 | All as per item No.17 above but of size 150 mm dia complete all as directed |
| 30 | All as per item No.17 above but of size 200 mm dia complete all as directed |
| 31 | Material and labour for construction of valve chamber of size 900x900x600mm internal size including necessary earth work and excavation, PCC 1:4:8 type D2 for foundation, brick work in cement mortar 1:4, PCC 1:2:4 type B1 for coping, 15mm thick rendering in cement mortar 1:4including provision of mild steel cover 3mm thick on 40x40x6 mm angle iron frame work with 2 coats of synthetic enamel paint over a coat of zinc chorme primer and locking arrangements complete all as directed. |
| 32 | Material and labour for construction of valve chamber of size 6000x1000x2000mm internal size including necessary earth work and excavation, PCC 1:4:8 type D2 for foundation, brick work in cement mortar 1:4, PCC 1:2:4 type B1 for coping, 15mm thick rendering in cement mortar 1:4including provision of mild steel cover 3mm thick on 40x40x6 mm angle iron frame work with 2 coats of synthetic enamel paint over a coat of zinc chorme primer and locking arrangements complete all as directed. |
| 33 | Supply and laying in on ground GI tubing \"Medium grade\" 100 mm bore, with all fittings complete all as specified and as directed. |
| 34 | All as per item No 23 above but of size 80 mm |
| 35 | All as per item No 23 above but of size 50 mm |
| 36 | All as per item No 23above but of size 40 mm |
| 37 | All as per item No 23above but of size 25 mm |
| 38 | Excavation in trenches in Hard/dense soil not exceeding 1.5 metre wide and not exc 1.5 metre in depth and getting out for taking out / laying of pipes and making bottom surfaces of excavationleveled. |
| 39 | Returning, filling in trenches with excavated soil including spreading, levelling, watering and well ramming in layers not exceeding 25 cm complete all as directed by the Engineer-in-Charge. |
| 40 | Removing surplus soil / spoil to a distance not exceeding 50 metre away and depositing where directed at a level not exceeding 1.5 metre above the starting point all as directed by the Engineer-in-Charge. |
| 41 | Material and labour for servicing ofcentrifugal pump with capacity of 200 HP including dismantling, refixing, greasing, spare parts. NOTE:- The pump should be functional satisfactorily as per Engr-in-charge. All the required items included in the quotated rate. |
| 42 | Repair & Servicing of Diesel Engine by adjusting the fan belt with proper tension, cleaning the sulphated material deposited on battery terminals and refixing duly applying petroleum jelly and supply & fixing of Lubrication oil filter, Preline filter cartridge, Fuel filter cartridge, Air cleaner primary element, Air cleaner safety element, Filter coolant, Water separator, gaskets, Washers and leaking pipes/hoses including taking down unserviceable item complete all as directed for the following capacity Diesel engine :-Note:(i) Servicing of Diesel engine shall be done by the technician from generator make and the cost shall be included in the quoted rate. (ii) The required transportation, repairing tools shall be arranged by the contractor and the cost shall be included in the quoted rate. |
| 43 | Supply and laying 150 mm diamild steel pipe including weldingconforming to IS : 1239/3589 . |
| 44 | All as per item no 33 above, but of size 100 mm dia. |
| 45 | Material and Labour for cutting of existing MS pipe line of any dia for alterations andadditions including welding of pipe lines to arrest leakagesas required at site of work including necessary excavation and earth work complete all as directed |
| 46 | Supply, fixing in replacementof water CO2/stored pressure type Fire Extinguisher 9 Ltrs Capacity complete fully charged gunmetal cap heavy inner container with wall mounting brackets etc. confirming to IS: 933. |
| 47 | Supply, fixing in replacementof Dry Chemical Powder type Fire Extinguisher 6 Kg Capacity complete fully charged gunmetal cap heavy inner container with wall mounting brackets etc. confirming to to IS: 15683. |
| 48 | Supply, fixing in replacementof CO2 type Fire Extinguisher 5 Kg Capacity complete fully charged gunmetal cap heavy inner container with wall mounting brackets etc. confirming to to IS: 15683. |
| 49 | Supply, fixing in replacementof Mechanical foam type Fire Extinguisher 9 Ltr Capacity complete fully charged gunmetal cap heavy inner container with wall mounting brackets etc. confirming to to IS: 15683. |
| 50 | Supply & Fixing LED flood lights 100 watts230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection with impact and corrosion resistant complete with driver and unique lens system for enhanced illumination and lamp including removal of existing & complete all as directedMake:-Havells/Bajaj/Philips/Crompton/FortuneArrt or its equivalent |
| 51 | Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete |
| 52 | S&F in repairsIntegral LED bollards 8 watt with opal acrylic diffuser made of extruded aluminium housing and IP65 protection including PCC foundation with suitablephospher bronze/GI nuts and bolts for fixing the bollard as per site requirement complete all asdirected Note:-Rate quoted shall be inclusive of necessary excavation and concrete required.Make:-Havells/Bajaj/Philips/Crompton/FortuneArrt or its equivalent |
| 53 | PVC insulated copper conductor FRLS grade2.5 sqmm,three core cable, ISI marked. |
| 54 | M&L for cutting existing road incl black top surfaces of required width and depthfor laying of pipe line, refilling and making good after laying of pipe with removed soii and finally sealed with cement concrete of thickness not less than 100mm to match with the top surface of Road.(Cement concrete shall be measured and paid seperately under appropriate item) |
| 55 | M & L for cement concrete 1 : 2 :4 type C2 using 40mm stone aggregate, as in repairs to RCC pipe line/ Valve pits / disturbed hard standing or any other repair as required at site at any situationall as specifiedas directed. |
| 56 | Supply, fabricate and fixing MS framed equal angle grills,gratings, framed guard bars,ladder,framework of Valve pit cover, water tanks, shallow wells etc, or similar work as ordered and fabricated from MS rolled section of any size and shape as directed and fixed at position with all fixing accessories complete. |
| 57 | M & L for making of fire point platform with fondation and brick work of staging of size 1.2m x 0.7 m at height 0.5 mtr for placing the 4 Nos of buckets of steel filled with sand and water. Making shed with angle iron frame of size 1 meter height, angle iron frane size 50 x 50 x 5 mm. Shed to be made by iron sheet of not less than 22 guage. Painting the shed and buckets with quality red paint and marking of fire point. |
| 58 | Repair/Maintenance including rectification of any faults of various Fire Alarm Systems installed at DRDL &ASL area including checking, testing, cleaning of Smoke Detectors, Heat Detectors, Beam Masters, Hooters, Manual Call Points, spirit bulbs etc. by carrying out preventive Maintenance and Corrective Maintenance rectifying defects in existing system and making the entire system trouble free and efficient functioning with all accessories connected to the Fire Alarm systems complete all as directed. Note: (i)Spares if any required shall be measured and paid under the relevant items of schedule and cost of labour/Fire fighting Technician/ Engineer, element like Tools/Eqpt, cleaning agents etc are deemed to be included in the quoted rate.(ii)Service report is to be generated andsubmitting to Engr-in- Charge. |
| 59 | Supply and Installation of the followingconventional/Addressabletype Zone microprocessor based fire alarm control panel suitable to the existing system including dismantling of old un serviceable control panel and rewiring the connections as required complete all as directed. |
| 60 | 2 Zone control panel Adressable |
| 61 | 4 Zone control panel conventional type |
| 62 | 8 Zone control panel conventional type |
| 63 | Supply of the following spares required for the efficient functioning of the Conventional/Addressable Fire Alarm Systems for item Nos.68 & 69 here-in-before. |
| 64 | Ionisation / Photo Electric (Optical) Smoke Detector |
| 65 | Heat Detector. |
| 66 | Electronic Hooter. |
| 67 | Manual call point. |
| 68 | Response Indicator. |
| 69 | Transformer 5 Amp, 24 – 0 – 24 Volt. |
| 70 | Maintenance Free Battery 12 V, 7 AH. |
| 71 | Maintenance Free Battery 12 V, 12/18 AH. |
| 72 | Supply of the following spares required for the efficient functioning of the Conventional Fire Alarm Systems for item Nos.68 & 69 here-in-before. |
| 73 | Addressable Ionisation / Photo Electric (Optical) Smoke Detector |
| 74 | Addressable Heat Detector. |
| 75 | Addressable dual tone Electronic Hooter. |
| 76 | Addressable loop Card. |
| 77 | Addressable Mannual pull station. |
| 78 | Programming of Loop card any zone (Addressable/conventional). |