| 1 | Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required. |
| 2 | Supplying, installation, testing & commissioning of smoke detector with built-in LED and mounting base complete with all connections etc. as required |
| 3 | Supplying, installation, testing & commissioning of Manual Call Box of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass & push button etc. as required |
| 4 | Supplying, installation, testing & commissioning response indicator on surface/recess MS box having two LEDs metallic cover complete with all connections etc.as required. |
| 5 | Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement,mounted in M.S.box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformeretc.complete as required. |
| 6 | Supplying, installation, testing & commissioning talk back slave station in surface/recess suitable for operation on simplex mode complete with P.T.T.knob & speaker/microphone enclosed in a MS (16 SWG)/ABS box with break glass in front etc. complete as reqd. |
| 7 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required2 x 1.5 sq. mm |
| 8 | Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required. |
| 9 | 6 Zone |
| 10 | Supplying, installation, testing & commissioning of ceiling/wall mounted loud speaker, 3/1.5 Watt in ABS enclosure complete as required |
| 11 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required |
| 12 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed copper conductor cable in the existing surface / recessed copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as require.speaker cable Single pair, 2-core, 1.5 sqmm |
| 13 | Speaker cable Single pair,2-core,1.5 sqmm |
| 14 | Speaker cable Two pair,2-core,1.5 sqmm |
| 15 | Supplying and fixing of following size of steel conduit along with accessories in surface/recess including painting in case of surface conduit,or cutting the wall andand making good the same in case of recessed conduit as required. |
| 16 | 20 mm |
| 17 | 25 mm |
| 18 | S/I/T/C of main control and indicating panel made out of 16 SWG MS sheet to accommodate the following items duly powder coated in approved colour with louvers for ventilation,locking arrangement,audio and visual indicatiion for fire alarm and public address system,monitoring system including connections,interconnections etc.complete as required.10 zone panel for fire alarm system.250 watt amplifire racks suitable for operation on 220V AC/24V DC supply conforming to IEC-268-3 complete with all accessories as required-2 Nos.( one to act as standby)station with LED PTT (press to talk) push button for operation on 230V AC/24V DC supply conforming to IEC-268 for simplex mode of operation/communication suitable for 20 Nos.talk back unit-1 Set. Annoucement control desk suitable for selection of different zones selectively and ON ALL CALL switch with visual indication etc.,complete as required- 1 Set. Amplifier change over switch for inter changing amplifier- 1 No. Monitor Panel for loudspeaker complete output selector ON/OFF switch,fuse visual indications etc.complete as required- 1 No.Gooseneck microphone with stand and ON/OFF switch- 1 No.Main ON/OFF switch,fuse indication lamp,DC and AC voltmeters & ammeter terminal blocks etc.complete as required- 1 Set Battery charger trickle cum boost to take complete load of fire alarm & PA system complete with all accessories including providing & fixing of 2 nos.12 volt, 60 AH each sealed maintenance free batteries -1 set |
| 19 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 20 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. |
| 21 | Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. |
| 22 | Supplying, installation, testing & commisssioning of addressable fire control module complete as required. |
| 23 | Supplying, installation, testing & commisssioning of addressable phone control module complete as required. |
| 24 | Supplying, installation, testing & commissioning of Adressable manual call point complete as required. |
| 25 | Supply and fixing of Energy Saving display Sign Board Glass type specially designed for classic décor with excellent quality high efficiency and long life for display, well ventilated, powder coated having nominal size LED Lamp, battery backup 6 hours to be installed on wall/ceiling etc complete as reqd. |
| 26 | (a) Single Sided |
| 27 | (b) Double Sided |
| 28 | Supply & Fixing of Signages on Aluminium Sheet 2.0 mm (±10%) fixing on wall/ceiling complete in all respect. |