| 1 | SCHEDULE A PART I (BUILDING WORK) |
| 2 | Design,fabrication,supply,erection,construction and executionof single storey trg sheds of size 15.30m x 8.30m (Plinth Area) using substructure RCC frame (RCC foundation, RCC column, RCC plinth beam) upto plinth level &in superstructureload bearing sections shall be made PEB structures and wall /panels other non-load bearing members of Light gauge steel frame (LGSF). TheTrg Shedshall be based on given tentative line plan Drg No HQ CWE No 2/RKE/05/2025-26 Sheet 1/1complete all as specified and directed. |
| 3 | Total amount of Sch \"A\" Part II(SITE CLEARANCE AND EARTH WORK) (For details see Sch \"A\"in PDF folder) |
| 4 | Total amount of Sch \"A\" Part III (Hard Standing) (For details see Sch \"A\"in PDF folder) |
| 5 | Total amount of Sch \"A\" Part IV (ROAD) (For details see Sch \"A\"in PDF folder) |
| 6 | Total amount of Sch \"A\" Part V (EXTERNAL ELECTRIC SUPPLY) (For details see Sch \"A\"in PDF folder) |
| 7 | Total amount of Sch \"A\" Part VI(INTERNAL ELECTRIC SUPPLY) (For details see Sch \"A\"in PDF folder) |
| 8 | SCHEDULE A PART VII (MISCELLANEOUS ITEMS OF B/R AND E/M) |
| 9 | Supply only soil outside def land for earth filling |
| 10 | M & L for applying termoplastic reflective paint as in road marking 02 mm thick single coat as in centerline or edge line road marking of n. exc 150 mm width using HOT MARK termoplastic paint (HOT application) white by indigenous modem propelled road marking method as directed incl all ingredient such as binder glass beads Titanium -dioxide calcium carbonate linter fillers themoplastic requirement for glass beads shall be per Table no 800-4 specifiation incl spraying of glass beads instruction , approved colour confirming to BS 3262-1989 with special applicator machine all as per manufacturers instruction complete all as specified and directed. |
| 11 | Supply and fix MCCB / MCB distribution board, Vertical TPN, 4 way, 415 V, 3 phase, AC with MCCB as incomer and MCBs as outgoing in sheet steel powder painted enclosure double door type with minimum IP 43 degree of protection with built in copper bus bar of suitable size, neutral link and earth link complete including cutting the wall surfaces for flush mounting of DB and making good with cement plaster, putty and paint to match with the existing surface complete all as specified and directed.Note: MCCB/MCBs shall be measured and paid separately. |
| 12 | Supply and fix LED 30 watt Building security light fitting having IP 65 or more protection mounting type made out of one piece in pressure die-cast aluminium housing with high efficient LED as lighting source and PC Cover separate compartment for driver,including making suitable size of bracket,clamp, washers, nuts, bolts and fixing accessories complete with electronic driver and all accessories duly prewired complete all as specified and directed. |
| 13 | Labour and T&P for horizontal boring of hole passing through pavement/road/hardstanding by manual or mechanical means suitable for 50 mm bore complete all as specified and directed. |
| 14 | Fabrication, supply, installation, testing and commissioning electrical cubical control panel board(KIOSK TYPE) of size 600x450x550mm Double door, CPRI approved an ISO 9001 factory assembled made out door pedestal type feeder pillar box weather and vermin proof fabricated of 3.0mm CRCA MS sheet of Suitable size,3 phase 4 wire 415 Volt ac 50 Hz complete duly painted, powder coated complete with locking arrangement, earthing terminals with suitable rating aluminium strips for incoming/outgoing MCCB\"s including and Mounting measuring instrument such as Volt meter, Ammeter, Selector switchs, CT\"s -03 Set, Phase indicator lamps with holder , toggle switches and backelite fuse cut outs etc including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 105 cm long angle iron size 50x50x6mm welded on all four corner embedded in PCC (1:2:4) using 20mm graded upto 45cm complete all as specified and directed by the Engg-in-charge( Feeder pillar box shall be consisting the following) (a)4 Nos electrolytic aluminium bus bars high conductivity aluminium alloy proper insulated of 1 ½ times of the incoming capacity with provision of extension and mounting on porcelain support(b) MCCBFP 100 amps, 15/16 KA , 415 volts, 50Hz(fixed and thermal type) = 01 No (Incoming)(c) 08 Nos, holes in bottomfor inlet and outlet cable with suitable size of copper cable gland(d)Electric connection between MCCB and Busbar shall be done with aluminium strip links duly colour coded.(e) Digital Panel mounted Amp meter 96 mm square type complete with selector switch complete with suitable size of CT\"s - 01 Set(f) Digital Panel mounted Volt meter 96 mm square type complete with selector switch - 01 NosNote: (i) For all incoming and outgoing cable should be provided suitable size of gland.(ii) Before placing the order drawing of the panel should be approved by the GE. |
| 15 | Note:-(a) Specifications of all items should not be less than the above mentioned specification and quantity.(b) The work to be carried out as per NBC2016 norms and necessary firefighting eqpt also be provided as per Building norms NBC 2016.(c) Specifications of all items should not be less than the above mentioned specification and quantity, if additional quantity and higher specification are required at site the contractor shall be provided the same without any extra cost with the approval of accepting officer. |