| Sl. No. | Item Description |
| 1 | Schedule \"A\" Section-I to XVIunder Ser No. 2.00 to 17.00 are prepriced by MES on SSR (Pt-II)-2020 |
| 2 | Lump sum price worked out by the Contractor for \"BUILDING WORK\" as listed in Schedule \"A\" Section-I. |
| 3 | Lump sum price worked out by the Contractor for“SITE CLEARANCE, EXCAVATION AND EARTH WORK” as listed in Schedule ‘A’Section-II. |
| 4 | Lump sum price worked out by the Contractor for“INTERNAL WATER SUPPLY” as listed in Schedule ‘A’Section-III. |
| 5 | Lump sum price worked out by the Contractor for“INTERNAL ELECTRIFICATION” as listed in Schedule ‘A’Section-IV. |
| 6 | Lump sum price worked out by the Contractor for“INTERLOCKING PATH & CEMENT CONCRETE ROAD” as listed in Schedule ‘A’Section-V. |
| 7 | Lump sum price worked out by the Contractor for“SEWAGE DISPOSAL” as listed in Schedule ‘A’Section-VI. |
| 8 | Lump sum price worked out by the Contractor for“AREA DRAINAGE” as listed in Schedule ‘A’Section-VII. |
| 9 | Lump sum price worked out by the Contractor for“RAIN WATER HARVESTING” as listed in Schedule ‘A’Section-VIII. |
| 10 | Lump sum price worked out by the Contractor for“EXTERNAL WATER SUPPLY” as listed in Schedule ‘A’Section-IX. |
| 11 | Lump sum price worked out by the Contractor for“EXTERNAL ELECTRIFICATION” as listed in Schedule ‘A’Section-X. |
| 12 | Lump sum price worked out by the Contractor for“LIGHTNING PROTECTION” as listed in Schedule ‘A’Section-XI. |
| 13 | Lump sum price worked out by the Contractor for“FIRE ALARM SYSTEM” as listed in Schedule ‘A’Section-XII. |
| 14 | Lump sum price worked out by the Contractor for“FIRE FIGHTING” as listed in Schedule ‘A’Section-XIII. |
| 15 | Lump sum price worked out by the Contractor for“DG SET” as listed in Schedule ‘A’Section-XIV. |
| 16 | Lump sum price worked out by the Contractor for“WATER COOLER” as listed in Schedule ‘A’Section-XV. |
| 17 | Lump sum price worked out by the Contractor for“DEMOLITION” as listed in Schedule ‘A’Section-XVI. |
| 18 | SCHEDULE `A\" SECTION - XVII MISC ITEMS Ser No. 19.00 to 143.00 (To be quoted by the tenderer) |
| 19 | INTERNAL WATER SUPPLYS&F fancy type two way bib taps with wall flange,chromium plated cast copper alloy with crutch or butterfly handle,screwed down,screwed for iron pipe or for brass ferrule and fixed complete all as specified & directed. |
| 20 | S&F CP fancy type angular stop cock 15mm dia with wall flange complete all as specfied and directed. |
| 21 | Providing and fixing unplasticised PVC connection pipe 15 mm nominal bore with brass unions of length 450 mm complete all as specified and directed. |
| 22 | S&F CP towel ring square with round flange of standard size complete all as specified& directed. |
| 23 | S&F toilet paper roll holder with stainless steel flap of standard size complete all as specified and directed. |
| 24 | S&F health faucet spray with 1 mtr long easy flex tube in chrome finish & wall hook complete all as specified and directed. |
| 25 | S&F vitreous urinal (with integrated sensor) including bracket with connection pipe complete all as specified and directed. |
| 26 | S&F 1 mm to 1.25 mm thickStainless Steel Kitchen Sink 24\"x18\"x9\" (304 Grade) Handmade Single Bowl Sink With Waste pipe and waste Coupling complete all as specified and as directed. |
| 27 | S&F chromium plated Tall body sensor tap \"Immacula\" (AC & DC) table top wash basins with tap hole complete all as specified and as directed. |
| 28 | S&F square vitreous china wash hand basin counter top, snow white, fancy type of overall size 390x390x150 mm, including 32 mm pop-up CP waste coupling full thread, CP Bottle trap 32mm with 125mm & 175mm long with wall connection pipe & wall flange, 450 mm long PVC Connection pipe etc complete all as specified and directed. |
| 29 | S&F chromium plated pillar sensor tall \"Flora\" (AC & DC) cock table top wash basins with tap hole complete all as specified and as directed. |
| 30 | Providing and Fixing LED looking mirror of superior quality of galss and backing of aluminium composite panel and frame of anodised aluminium & natural finish of size450 mm x 600 wall hung type with quick transmission light complete all as specified and directed. |
| 31 | S&F white vitreous china wash down water closet pan wall mounted flush plate, concealed flushing cistern with full frame of drain set connection to drawn pipe and flushing pipe all as specified and directed. |
| 32 | INTERNAL ELECTRIFICATIONS & F modular type 3 pin 20 A socket with MCB, conforming to IS 1293: 2005 complete all as specified in IS 732: 2019 and directed. (AC/GEYSER POINT) |
| 33 | S & F single pole & neutral, modular type, double door, metallic distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for DP RCCB / RCBO / Isolator / MCB as incomer and SP MCBs as outgoing, reversible metal door, 100 A copper busbar, fully shrouded neutral bar, earth bar, wire set & cable ties for cable management, pre fitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified in IS 732: 2019 and directed.NOTES:[i] DP RCCB / RCBO / Isolator / MCB & SP MCBs shall be measured and paid separately. |
| 34 | single pole & neutral double door DB, 6 way complete all as specified and directed. |
| 35 | Supply and fixing load line distribution board TPN vertical, double door type, fixed on wall semi flush with incoming MCCB 4 poles and, busbars , neutral link, blanking plates complete with all accessories all as specified and as directed. Note: Outgoing MCBs shall be measured and paid separately. |
| 36 | Triple pole & neutral double door DB, 8 way complete all as specified and directed. |
| 37 | S & F MCB for conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters, etc. complete all as specified in IS 732: 2019 and directed. |
| 38 | 32A, 230V, 50Hz, 2P MCB (C\"curve) |
| 39 | 40A, 230V, 50Hz, 2P MCB (C\"curve) |
| 40 | 63A, 230V, 50Hz, 2P MCB (C\"curve) |
| 41 | S & F RCCB for conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA,30mA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters, etc. complete all as specified in IS 732: 2019 and directed. |
| 42 | 32A, 230 V, 30mA, 50 Hz, 2P RCCB |
| 43 | S & F of 63A, 3 pole moulded case circuit breaker (MCCB) with thermal magnetic trip unit (TMD), compression lug connectors, protection against overloads (Ir adjustable from 0.7- 1 X In), protection against short circuits (Isd adjustable from 5- 10 X Ir), inbuilt encapsulated double break roto active type instanteneous protection, earth fault leakage protection, etc. having Ics = 100% = Icu = 16 kA as per IEC 60947-2 and suitable for 3-Phase, 415 V, 50 Hz electric supply complete all as specified and directed. |
| 44 | Supply and fixing LED 2X2 panel ceiling mounted type with high out put, 36 watt 220 V AC decorative type with driver holder and LED lamp including connec`ting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 45 | Supply and fixing 12 W LED light fitting, surface down type with high out put diffuser 140mm dia, 12 watt 220 V AC decorative type with driver holder and LED lamp including connec`ting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 46 | Supply and fixing 12 W LED light fitting, recessed mounteddown type with high out put diffuser 140mm dia, 12 watt 220 V AC decorative type with driver holder and LED lamp including connec`ting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 47 | Supply and fix 3 phase, 32A industral type swich board, including 3 phase socket and 3 pole 32A MCB, switch board having sturdy metalic body, shall be walll mounted and having separate cable entry with gland complete all as specified and directed. |
| 48 | Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type MDB-F_PANEL (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required ratings, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. |
| 49 | The MLTP shall comprise of the following: [A] BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 300 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection[B] INCOMING[i]250A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos.[ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos.[iii] LED phase indicators (Red, Yellow, Blue)- 01 Set[C] OUTGOING[i]63A, 415 V, Ics = 100% Icu = 16 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 02 Nos.[ii]63A, 415 V, Ics = 100% Icu = 16 kA, 50 Hz 3P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 02 Nos.[iii]40A, 415 V, Ics = 100% Icu = 16 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos.[iv]32A, 415 V, Ics = 100% Icu = 16 kA, 50 Hz 3P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos.[v] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 6 Nos.[vi] LED phase indicators (Red, Yellow, Blue)- 6 Set |
| 50 | Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type PDB-1_PANEL (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required ratings, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. |
| 51 | The MLTP shall comprise of the following: [A] BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 3200 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection[B] INCOMING[i]2500A, 415 V, Ics = 100% Icu = 50 kA, 50 Hz 4P ACB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos.[ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos.[iii] LED phase indicators (Red, Yellow, Blue)- 01 Set[C] OUTGOING[i]2000A, 415 V, Ics = 100% Icu = 50 kA, 50 Hz 4P ACB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos.[ii]400A, 415 V, Ics = 100% Icu = 16 kA, 50 Hz 3P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 02 Nos.[iii]16A, 415 V, Ics = 100% Icu = 16 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 02 Nos.[iv] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 5 Nos.[v] LED phase indicators (Red, Yellow, Blue)- 5 Set |
| 52 | Supply, installation, testing and commissioning of sandwich type (3L+N+PE) busbar trunking system complete with two runs of 50 mm X 6 mm aluminium earthing strip and accessories all as specified and directed The BTS shall conform to the following technical specifications:-[A] GENERAL[i] The busbar trunking system (BTS), both feeder and plug-in, shall be of sandwich construction. All components and fittings (straight length, elbow, tee, flanged end, cable tap-off box and circuit breaker etc.) shall conform to IEC 61439-6:2012 or UL 857.[ii] The BTS shall have IP 66 protection with canopy for outdoor application and IP 54 protection for indoor application in accordance with IEC 60529: 1989.[iii] The rated operation voltage of BTS shall not be less than 1 kV. The neutral conductor shall have the same cross-sectional area as the phase conductor and the earth busbar shall be provided on both sides of the housing.[B] CERTIFICATE[i] The busbar, of full range and each rating, shall pass full type tests specified in IEC 61439-6-2012. The certificate shall be issued by an international independent testing authority, e.g. ASTA. KEMA. UL, ERDA, CPRI etc.[ii] A product safety mark, e.g. KEMA-KEUR, ASTA DIAMOND, UL and ERDA, CE, etc. shall be on the product offering a visual assurance of full product safety testing, factory inspection and ongoing surveillance under independent authority.[iii] The BTS shall be certified for siesmic tests conforming to IEEE 693-2018 for seismic zone V |
| 53 | [C] SHORT-CIRCUIT RATINGS & TESTS[i] The entire BTS (busduct and plug-in box assembly) shall be capable of withstanding the short-circuit of electrical installation without undergoing any electrical, mechanical or thermal stress under fault condition at a service voltage of 1 kV at 50 Hz frequency. The minimum rated insulation voltage shall be 1 kV.[ii] The minimum certified short-circuit withstand capacity for 3200 A rating shall be 80 kA for 1 sec.[D] HOUSING[i] The busbar trunking housing shall be constructed of 1.6 mm thick electro-galvanised steel and shall be provided with a suitable protective finish of epoxy paint.[ii] The busbar trunking housing shall be totally enclosed non-ventilated for protection against mechanical damage and dust accumulation and it shall be tested for its characteristics offering resistance against corrosion. It shall also pass at least 1000 salt spray test to ensure its anti-corrosion ability.[iii] The totally enclosed housing shall be manufactured by the BTS OEM and modifications of busbar trunking to make it totally enclosed by housing other than the busbar trunking OEM shall be unacceptable without written consent of the OEM.[E] BUSBARS[i] The busbars shall be of aluminium with tin / silver plating at joint and conductivity of the joint shall be > 60% IACS[ii] There shall be no bolts passing through the busbars of the BBT.[iii] Each busbar shall be insulated with Class-F (155 ⁰C) multilayer PET insulation. Epoxy and Mica insulation shall be unacceptable.[iv] The temperature rise at any point of busbar trunking enclosure shall not exceed 55 ⁰C above the ambient temperature of 40 ⁰C when operated at the rated current. |
| 54 | [F] JOINTS[i] The busbar trunking joint shall be of one-bolt type utilizing high strength steel bolt(s) and Belleville washers to maintain proper pressure over a large contact surface area.[ii] The bolt(s) shall be torque indicating and at earth potential.[iii] The nut(s) shall be of two-headed design to indicate proper torque has been applied and shall require only a standard long handle wrench to be properly activated.[iv] Access shall be required to only see one side of the busbar trunking to tighten joint bolts.[v] It shall be possible to remove any joint connection assembly to allow electrical isolation or physical removal of a busbar trunking length without disturbing adjacent busbar trunking lengths.[G] PLUG-IN OPENING[i] The connecting jaw of a plug-in unit shall plug directly onto the busbar and have full contact with busbar itself. Welded tab at plug-in busbar is unacceptable.[ii] All contact on joint and plug-in opening shall be of copper strip in order to avoid external force damage on busbar while plugging in or plugging out operation.[iii] On plug-in busbar trunking there shall be three dead front, hinged cover type plug-in opening on each side.[iv] All openings shall be usable simultaneously. Busbar trunking shall be installed in such a manner that plugs are side mounted to permit practical use of all plug-in openings.[v] It shall be possible to inspect the plug-in opening and busbars prior to the installation of plug-in units. |
| 55 | [G] PLUG-IN OPENING[i] The connecting jaw of a plug-in unit shall plug directly onto the busbar and have full contact with busbar itself. Welded tab at plug-in busbar is unacceptable.[ii] All contact on joint and plug-in opening shall be of copper strip in order to avoid external force damage on busbar while plugging in or plugging out operation.[iii] On plug-in busbar trunking there shall be three dead front, hinged cover type plug-in opening on each side.[iv] All openings shall be usable simultaneously. Busbar trunking shall be installed in such a manner that plugs are side mounted to permit practical use of all plug-in openings.[v] It shall be possible to inspect the plug-in opening and busbars prior to the installation of plug-in units.[H] SUPPORT STRUCTURE[i] Support structure shall be provided as per OEM\"s recommendation.[ii] Indoor feeder and plug-in busbar trunking shall be approved for hanger spacing of up to 3 m for horizontally mounted run and 4.88 m for vertically mounted runs. Outdoor feeder busbar trunking shall be approved for spacing up to 1.5 m for horizontally or vertically mounted runs.[I] VOLTAGE DROP[i] The voltage drop (sending end voltage minus receiving end voltage) specified shall be based on the busway operating at full rated current and stabilized operating temperature in [ii] The 3- Phase line to line voltage drop shall not exceed 3.4 V per 100 feet length at 40% power factor concentrated load which may exist during motor starting.[iii] The line to line voltage drop shall not exceed 4.1 V per 100 feet at the load power factor which produces the maximum voltage drop in the busway.[J] INSPECTION / SUPPORT OF INSTALLATION[i] The installation of busbar trunking system (BTS) shall be executed by skilled professionals with minimum experience of 4 yrs. having sufficient installation base and pre-commissioning experience.[ii] The entire installation shall be directly supervised by the OEM. [iii] The OEM shall also furnish a commissioning report underlining satisfactory installation after the commissioning of BBT system. |
| 56 | 2500 A BBT (TECH LAB BUILDING)2500A AL IP-54 Straight Run Feeder having IP54 complete all as specified and directed. |
| 57 | 2500A AL IP-54 Flange End with Equalizer / Shorting Plate complete all as specified and directed. |
| 58 | 2500A AL IP-54 Horizontal / Vertical Bend complete all as specified and directed. |
| 59 | 2500A AL IP-54 Plug-in Point (Without Switchgear) complete all as specified and directed. |
| 60 | 2500A AL IP-54 Vertical Spring Hanger / Fix Hanger complete all as specified and directed. |
| 61 | 2500A AL IP-54 End Cover complete all as specified and directed. |
| 62 | 2500A AL IP-54 Expansion Joints complete all as specified and directed. |
| 63 | 2500A AL IP-54 Tinned Copper Braided Flexibles with Hardware- Nuts & Bolts complete all as specified and directed. |
| 64 | 2500A AL IP-54 Adapter Box complete all as specified and directed. |
| 65 | 2500A AL IP-54 PIB / TOU with 250 A, 415 V, 16 kA, 50 Hz, FP MCCB complete all as specified and directed. |
| 66 | 2500A AL IP-54 End Feed Unit (EFU) with 2500 A, 50kA, 415 V, 50 Hz, FP ACB complete all as specified and directed. |
| 67 | 2500A AL IP-54 Horizontal Fixing Clips complete all as specified and directed. |
| 68 | Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type UPS PDB_PANEL (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required ratings, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. |
| 69 | The MLTP shall comprise of the following:[A] BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 500A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection[B] INCOMING[i]400A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2 & 3, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos.[ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos.[iii] LED phase indicators (Red, Yellow, Blue)- 01 Set[C] OUTGOING[i]63A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 09 Nos.[ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 09 Nos.[iii] LED phase indicators (Red, Yellow, Blue)- 09 Set |
| 70 | EXTERNAL WATER SUPPLYM&L for drilling and tapping cast iron water mains of any sizefor provision of branch connection and fixing offittings such as staright plain brass ferrules( or connecting screws) screwed both ends and fixed of size 40mm with internal dia 40mm complete all as specified and directed. |
| 71 | S&F Bronze gate valve class-2for 50mm bore pipe,with iron wheel head, screwed both ends for iron pipe and fixed,Screwed in Bonnet, Inside Screw, Non-Rising Stem, Integral Seat, Solid Wedge,Maximum Working Temperature : 45°C, ISI marked conforming to IS 778: 1984, complete all as specified and directed. |
| 72 | Supply and fix high pressure, heavy duty castiron non return valve/ check valve sluice valve of size 50 mm nominal diaboth ends flanged ,swing type, PN 1.6 rating suitable to hydrostatic test pressure for body 2.4MPa & for seat 1.6 MPa as per IS 5312 and other accessories as per IS 1538 complete all as specified and directed.Note : Suitable size flanges for pipe line, Joints and jointing materials shall be included under this item. |
| 73 | Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.Isurface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:1.5:3 mix (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size), including necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 complete all as specified and as directed. |
| 74 | Supply, installation,testing and commissioning ofCentrifugal monoblock pumpset with copper rotor suitable for clear water application, suitable for operation on 3 phase 415 volts ,50 Hz AC supply, capacity 5 HP with 45 mtr head. The pump shall have CI body,and casing ring,inlet X outlet(50mm X 50mm)confirming to IS 14220(1994) with stainlessSS 410 Shaft and shaft sleeve , bronzeimpeller ,bronze bush and stamping lamination with high permeability steel for long life and increased efficiency,coupling guard, common base plate, foundation bolts, etcPumps shall be provided with mechanical seal.Insulation: F class Protection: IP 55.The cap of motor in HP/KW shall beas perrecommendation of the manufacturer. Each pump shall have TEFC 1450 / 2900 RPM three phase electric motor.The cap of motor in HP/KW shall beas perrecommendation of the manufacturer.The motor shall be confirming to IS:9283(1994) with minimum 80% efficiency and Guaranteed Pump efficiency at design flow should be equal or greater than 85%. complete all as specified and as directed. |
| 75 | Supply and fix DOL starter for 7.5 HP motor 3 phase 415 Volts complete all as specified and directed. |
| 76 | EXTERNAL ELECTRIC SUPPLYSupply, installation, testing and commissioning step down transformer of capacity 1600 KVA, Copper wounded, Outdoor type complete with standard fittings HT 11 KV 3 Phase and LT 433 Volts 3 phase 4 wire, 50 Hz, core type double copper wound, oil immersed. oil cooled, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with victor group DYN-11 with natural brought out on secondry side (LV side) and having tapping at + 7.5% in step of + 2.5% on HV side to be changed by means of hand operated off load tap changer gear. The maximum temp rise should not exceed 45 degree celsius in oil and 55 degree Celsius in HV/LV winding when measured by resistance method after continous full load run on an ambient temperature of 40 degree Celsies. The Transformer shall be IS- 1180, level III marked and shall comprises of the following :- |
| 77 | (a) One cable box on HT side (Primary) consisting of three Nos porceian bushing suitable for 11 KV on HV side complete with copper rods, nuts and washers.(b) One cable box on LT side (Secondary side) consisting of four Nos porcelain bushing with copper rods, complete with nuts and washers with cable glands (c) Buchholz Relay (having contacts for alarm & trip)(d) OTI (having contacts for alarm & trip)(e) WTI (having contacts for alarm & trip)(f) Marshalling box(c ) Oil conservator with filter type drain valve and oil level gauge(d) De- hydrating breather with first type fill of dehydrating agent (Silica Gel)(e) Explosive vent, thermometer pocket on tank cover, Oil level gauge, Oil dgain filter valve, Lifting lugs, Oil filling hole with cap , plug with connection plate complete. Air release valve plug and four nos plain solid caststeel detachable rollers.(f) One no 100 mm dia dial type thermometer vapour pressure type , having range 0-120 Degree Celsius with metal guard having mazimum perimeter temperature reading indicator with re- setting devices(g) Two earthing terminal on tank cover to facilitate fixing of 32x6 mm GI iron earth strip for earthing of body (h) Rating plate and terminal marking plate(j) Extra bushing for neutral, out side the cable box for providing independent set of earthing for neutral. (k) Frist filling of new transformer oil, IS- 335 marked, filtered and tested. Transformer shall be painted two coat of epoxy paint all as specified.Note:- PCC foundation and MS angle steel fence as per OEM drawing is included in the quoted rate and No extra payment paid to contractor for the same. |
| 78 | Supply, fixing, testing and commissioning ofcompact air insulated type bus trunking system with copper busbar suitable for rated current 3400 Amps, 50 KA breaking capacity and IP 68 degree ofprotection for low voltage distribution (415V) as per IEC 61439-1 , IEC 61439-6, 3 Phase 50 Hz with tap-offs for floor/riser distribution in rigid metal hausing of non magnetic aluminium iwth epoxy polyster powder coated finish and with proper identification,marking & safety complete all as specified and directed. |
| 79 | Supply, install, testing and commissioning offactory made LTcubical outdoor type panel (MLTP) CPRI approved madeof 3.15 mm thick totally enclosed with front and rear opening hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangement along with lugs, cable glands of various sizes for cable,danger noticeconnector for connecting multi cables located in cable chamber terminated form the switchergear and the nuts/ bolts etc used are to be made of rust proof material including copper bus bar 3400 Amps for phase and 3400 Amps for neutral with insulators suitable for three phase and capacity suitable bus trunking system connection complete & powder coating necessary internal electric connection as required and provision of the following:- |
| 80 | (i) Incoming :-(a) Supply & fix LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with air circuit breaker, overload protection, no-volt release with necessary CTs,meter and cable boxes of rating upto 2500 Amps(b) Digital Ammeter 3 Phase AC0 – 2500 Amps, with 3 current transformer of suitable ratio and capacity Qty -01 No. (c) Indicating lamps LED type for three phases-R Y B of 3 Nos,(d) Digital Voltmeter 3 Phase AC 0 – 500 Volts.Qty -01 No.(e) Bus-bar chamber having 4 nos colour insulated copper bus-bar of 3400 Amps rating of suitable shape and size.(ii) Out Going (a) Supply & fix LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with air circuit breaker, overload protection, no-volt release with necessary CTs,meter and cable boxes of rating upto 2500 Amps - 02 Nos (01 Nos for PDB-1, 01 Nos Spare)(b) MCCB, 400 Amp 4 pole 36 KA, 415 Volts, AC supply,having breaking capacity , with adjustable thermal magnetic protection setting, Qty – 02 No(01 Nos for APFC Panel & 01 Nos standby)(c) MCCB, 320 Amp 4 pole 36 KA,415 Volts, AC supply,having breaking capacity ,with adjustable thermal magnetic protection setting, Qty – 01 No (For Fire Fighting Panel)(d) MCCB, 16 Amp 3 pole 16 KA,415 Volts, AC supply,having breaking capacity , Qty – 01 No (For Substation) |
| 81 | Providing and fixing earth bus of 50 mm x 5mm copper strip on surface for connections etc. as required complete all as specified and directed. |
| 82 | Relaying/shifting of route of existing PVC/XLPE Insulated under ground cable, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size from 6 Sqmm 2 Core to 500 sq mm 3.5 core complete all as specified and directed. |
| 83 | Relaying/shifting of route of existing PVC/XLPE Insulated under ground cable, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11 KVolts grade with stranded aluminium conductor of size from 95 Sqmm 3 Core to 185 sq mm 3 core as per directed. |
| 84 | SEWAGE DISPOSALS&F SFRC (Steel Fibre Reinforced Concrete) storm water drain cover with frame of size (1460x1260)/(1410X1210)mm of MD-10 Tone capacity, all as specified and as directed.Note : - Contractor will provide manufacturer test certificate of SFRC cover & frame. |
| 85 | AREA DRAINAGES&F SFRC (Steel Fibre Reinforced Concrete) storm water (grating) drain cover with frame of size 910X450mm of MD-10 Tone capacity, all as specified and as directed.Note : - Contractor will provide manufacturer test certificate of SFRC cover & frame. |
| 86 | S&F SFRC (Steel Fibre Reinforced Concrete) storm water (grating) drain cover with frame of size 350X450mm of MD-10 Tone capacity, all as specified and as directed.Note : - Contractor will provide manufacturer test certificate of SFRC cover & frame. |
| 87 | RAIN WATER HARVESTINGProviding and fixing on wall face 110 mm diameter unplasticised Rigid PVC single socketed rain water pipes conforming to IS: 13592 Type A including jointing with seal ring conforming to IS: 5382, leaving 10 mm gap for thermal expansion complete all as specified and directed. |
| 88 | Providing and laying cement concrete 1:5:10 (1 cement: 5 coarse sand: 10 graded stone aggregate 40 mm nominal size) type-C2 upto haunches fo 110 mm diameter S.W pipe including bed concrete as p[er standard design complete all as specified and directed. |
| 89 | Supplying and Filling of sand of size 1.5mm to 2.0mm in rain water harvesting pit complete all as specified and directed. |
| 90 | Supplying and Filling of pea gravel of size 5.0mm to 10.0mm in rain water harvesting pit complete all as specified and directed. |
| 91 | Supplying and Filling of stone gritt of size 40.0mm in rain water harvesting pit complete all as specified and directed. |
| 92 | Supplying and Filling of brick ballast (half burnt) in rain water harvesting pit complete all as specified and directed. |
| 93 | Boring for rain water harvesting 200mm diameter boring from ground level to first water table level complete all as specified and directed. |
| 94 | M&L for laying of 150mm dia, UPVC slotted pipes located centrally in 200mm diameter bore complete all as specified and directed. |
| 95 | AIR CONDITIONINGSupply and fix air cooling and heating split unit air conditioner electric driven single phase of capacity of 2 TR, BEE 3 star rated complete all as specified and directed. |
| 96 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA complete all as specified and directed. |
| 97 | Supply and fix Chlorinated Polyvinyl Chloride (CPVC) pipes, 50 mm , including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing or cutting chases, concealing the pipe where required and making good the disturbed surfaces & jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete all as specified and directed. |
| 98 | Supply and fix Chlorinated Polyvinyl Chloride (CPVC) pipes, 32 mm , including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing or cutting chases, concealing the pipe where required and making good the disturbed surfaces & jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete all as specified and directed. |
| 99 | Supply and fix Chlorinated Polyvinyl Chloride (CPVC) pipes, 40 mm , including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing or cutting chases, concealing the pipe where required and making good the disturbed surfaces & jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete all as specified and directed. |
| 100 | Supply and fix Chlorinated Polyvinyl Chloride (CPVC) pipes, 25 mm , including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing or cutting chases, concealing the pipe where required and making good the disturbed surfaces & jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete all as specified and directed.Note :- The provision for drainage of condensed water from AC shall be done as under.a) 25 mm dia vertical pipe concealed in wall from indoor unit to floor.b) Horizontal pipe 32 mm dia from 25 mm pipe concealed in floor to 40 mm network above false ceiling.c) A network of 40 mm pipe above false ceiling along the wall till vertical 50 mm dia pipe in shaft outside.d) 50 mm dia vertical pipe in outside shaft till storm water drain fixed on wall.e) Any cut in slab is to be done using core cutting machine of max dia 100 mm (cost included in scope). |
| 101 | Supply and fix refrigeration copper pipe of soft and prime quality of 22 SWG of size 5/8 inch dia suitable for 2 tonsplit ACwith class \"O\" nitrileinsulation (fire retardant) of min 12 mm size complete with connecting accessories like split valve and shutoff valve and fixing accessories like clamps & hangers etc as per site conditioncomplete all as specified and directed. |
| 102 | Supply and fix refrigeration copper pipe of soft and prime quality of 22 SWG of size 3/8 inch dia suitable for 2 tonsplit ACwith class \"O\" nitrileinsulation (fire retardant) of min 12 mm size complete with connecting accessories like split valve and shutoff valve and fixing accessories like clamps & hangers etc as per site conditioncomplete all as specified and directed. |
| 103 | FIRE ALARM SYSTEMSupply, installation, testing and commissioning of FM approved and UL listed Network Control Display (NCD) / Repeater Panel capable of full supervision of all inputs and network integrity, having10\"high definition 1024 X 600 colour touchscreen display, environmental adjustment controls to maximize LCD legibility, LED status indicators (for power supply and off normal condition), network connection, three USB connections, trouble relay, tamper and trouble inputs, etc. and features viz. network-wide acknowledge silence, reset, lamp test, fully programmable node-mapping subsystem, colour coded icon based event notification, event vectoring, etc. along with UL listed non-resettable 24 VDC power source complete all as specified and directed |
| 104 | Supply, installation, testing and commissioning of UL listed analogue addressable type Multisensor Detectors with heat & smoke combination withthe fixed temperature of 59 degrees Centigrade and Rate of raise facility of 11.1.Deg C /min with 8 digit dip switches for ( 1 to 254) address settings. Dual LED indication for 360-degree visibility, milky white in color, shall be polarity insensitive, easy to install, advanced detection and communication protocol with insect filter chamber, complete all as specified and directed.Make: NotifieR, Bosch, HochikiMultisensar detectors have following features.[i] Dual LED’s for 360° visibility[ii] Advanced detection and communication protocol[iii] Polarity Insensitive[iv] Regular 100mm base[v] Sleek low-profile housing design[vi] Techincal Specification are as follow:-(A) Operating Voltage : 17 ~ 28V DC(B) Reset Voltage : less than 3V(C) Alarm Current : 7 mA.(D) Thermal Rating : 59 °C (138 °F(E) Smoke Sensitivity : (2.12 ± 0.61) % / f |
| 105 | Supply, installation, testing and commissioning of FM approved and UL listedsurface / semi- flush mounted Dual Action Manual Pull Station \"Push In & Pull Down\" including an addressable interface for the intelligent FACP having built-in bicolour LED which is visible, flashing in normal operation and latching steady red in alarm condition, captive screw terminals wire-ready for easy connection to SLC loop complete all as specified and directed. |
| 106 | Supply, installation, testing and commissioning of UL listed of Horn Strobe, wired as a primary notification appliance, flashing 75 cd at 1 Hz over the strobe\"s entire operating voltage range, xenon flash tube and associated lens / reflector system, built-in synchronization feature keeping strobes in sync for up to 30 minutes,horn producing audible annunciation of 75 dBA at 3 m distance complete all as specified and directed. |
| 107 | Supply, installation, testing and commissioning of FM approved & UL listed Remote power supply conforming to UL 864 & 1481 and NFPA 72 with integral battery charger capable of charging up to 18 Ah batteries to provide regulated and filtered 24 VDC power to notification appliance circuits, having power-supervision relay, fully regulated and filtered power output, AC trouble report selectable for immediate 2-hour delay, selectable earth fault detection, etc. complete all as specified and directed. |
| 108 | Supply, installation, testing and commissioning of UL listed all purpose 6 W Ceiling speaker having crush and rust resistant design and fully ABS plastic & ABS grille with tap-setting range between 1/4 W and 4 W, rated (RMS) voltage 70.7 V, sound pressure level at 1 W (1 m & 1 kHz) 80 ± 4 dB, frequency response 125 Hz- 16 kHz, (-10 dB with reference to 1 kHz), complete all as specified and directed. |
| 109 | M & L for transparent FR PVC insulated, twin core copper conductor flexible Speaker cable having stranded annealed tinned copper conductor, PVC insulated cores twisted to form pairs, shielded for interference rejection, unarmoured PVC sheathed 1.1 kV grade in conductor size 2 X 1.0 mm2 including laying, termination and ferruling complete all as specified and directed. |
| 110 | M&L flame retardant, low smoke & low halogen fire alarm armoured cable having stranded class 2 copper conductor conforming to EN 60228, insulated with XLPE type GP8 conforming to BS 7655-1.3, extruded inner sheath with PVC conforming to BS 5467, armoured with galvanised steel round wire and sheathed with extruded FRPL PVC conforming to BS 5467, suitable for voltage rating 600/1000 V, maximum operation temperature 90 °C, maximum conductor temperature at short-circuit 250 °C, RED in colour, including laying, termination and ferruling complete all as specified and directed. |
| 111 | 2 core, 1.5 mm² |
| 112 | 2 core, 2.5 mm² |
| 113 | Supply, installation, testing and commissioning ofUL listed (fire fighter\"s) addressable Telephone Jack mounted to a single-gang electrical back box with suitable interface module for two way communication with the Central Fire Fighter Telephone Console complete all as specified and directed. |
| 114 | Supply, installation, testing and commissioning of UL listed Fire Fighter\"s Telephone Handset for two way communication with the Central Fire Fighter Telephone Console complete all as specified and directed. |
| 115 | Supplying, installation, testing and commissioning of addressable phone control module complete all as specified and directed. |
| 116 | Supplying, installation, testing and commissioning of response indicator on surface/recess MS box having two LESs metallic cover complete with all connections etc. as required complete all as specified and directed. |
| 117 | FIRE FIGHTINGSupply, installation, testing and commissioning of Electric driven Main Fire Pump to deliver 2280 LPM flowrate at 70 MWC head and suitable for automatic operation and consisting of following, complete with accessories all as specified and directed.[i] Horizontal type, single-stage, single suction, horizontal shaft type, end suction, volute type with top centreline discharge centrifugal pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal, etc. conforming to IS 12469: 2019, suitable to deliver 2280 LPM flowrate at 70 MWC head[ii] Suitable HP squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 3- Ph, 415 V, 50 Hz AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class \"F\" insulation, conforming to IS 12615: 2018[iii] MS fabricated common base-plate, coupling, coupling guard, foundation bolts, etc. complete with accessories as required.[iv] Suitable cement concrete foundation duly plastered with anti vibration pads.NOTES:[i] The pump shall be capable of furnishing not less than 150% rated capacity at a head of not less than 65% of the rated head.[ii] The shut-off head shall not exceed 120% of rated head.[iii] The coupling guard shall be of zero access type.[iii] The coupling guard shall be of zero access type.[iv] The quoted rate shall include providing and fixing of vibration pad, common base plate, foundation bolts, grouting etc. [v] Pump sets shall be as per NFPA-20.[vi] Pump sets shall be installed as per IS 15301: 2003.[vii] Testing of FF pumps shall be as per NFPA - 25/2017/ relevent latest IS code. |
| 118 | Supply, installation, testing and commissioning of Diesel engine driven main fire pump to deliver 2280 LPM flowrate at 70 MWC head and suitable for automatic operation and consisting of following, complete with accessories all as specified and directed by the engineer-in-charge.[i] Horizontal type,single-stage, single suction, horizontal shaft type, end suction, volute type with top centreline discharge centrifugal pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal, etc. conforming to IS 12469: 2019, suitable to deliver 2280 LPM flowrate at 70 MWC head[ii] Suitable HP, 1500 RPM diesel engine, water cooled with radiator, conforming to IS 10002: 1981, complete with auto starting mechanism, 12/24 V electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour, etc. as required[iii] MS fabricated common base-plate, coupling, coupling guard, foundation bolts, etc. complete with accessories as required.[iv] Suitable cement concrete foundation duly plastered with anti vibration padsNOTES:[i] The pump shall be capable of furnishing not less than 150% rated capacity at a head of not less than 65% of the rated head.[ii] The shut-off head shall not exceed 120% of rated head.[iii] The coupling guard shall be of zero access type.[iv] The quoted rate shall include providing and fixing of vibration pad, common base plate, foundation bolts, grouting etc. [v] Pump sets shall be as per NFPA-20[vi] Pump sets shall be installed as per IS 15301: 2003[vii] Testing of FF pumps shall be as per NFPA - 25/2017/ relevent latest IS code. |
| 119 | Supply, installation, testing and commissioning of Electric driven pressurization pump (Jockey Pump) suitable for automatic operation to deliver 180 LPM flowrate at 70 MWC head and consisting of following, complete with accessories all as specified and directed.[i] Horizontal type, centrifugal, split-casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal, etc. conforming to IS 12469: 2019, suitable to deliver 180 LPM flowrate at 70 MWC head.[ii] Suitable HP squirrel cage induction motor, TEFC, suitable for operation on 3- Ph, 415 V, 50 Hz AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class \"F\" insulation, conforming to IS 12615: 2018.[iii] MS fabricated common base-plate, coupling, coupling guard, foundation bolts, etc. complete with accessories as required.[iv] Suitable cement concrete foundation duly plastered with anti vibration pads.NOTES:[i] The pump shall be capable of furnishing not less than 150% rated capacity at a head of not less than 65% of the rated head.[ii] The shut-off head shall not exceed 120% of rated head.[iii] The coupling guard shall be of zero access type.[iv] The quoted rate shall include providing and fixing of vibration pad, common base plate, foundation bolts, grouting etc.[v] Pump sets shall be as per NFPA-20 [vi] Pump sets shall be installed as per IS 15301: 2003[vii] Testing of FF pumps shall be as per NFPA - 25/2017/ relevent latest IS code. |
| 120 | Supply, installation, testing and commissioning of Electric driven Booster Pump (Terrace Pump) to deliver 900 LPM flowrate at 35 MWC head and suitable for automatic operation and consisting of following, complete with accessories all as specified and directed.[i] Horizontal type, centrifugal, split-casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal, etc. conforming to IS 12469: 2019, suitable to deliver 900 LPM flowrate at 35 MWC head.[ii] Suitable HP squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, having IE3 efficiency and suitable for operation on 3- Ph, 415 V, 50 Hz AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class \"F\" insulation, conforming to IS 12615: 2018.[iii] MS fabricated common base-plate, coupling, coupling guard, foundation bolts, etc. complete with accessories as required.[iv] Suitable cement concrete foundation duly plastered with anti vibration padsNOTES:[i] The pump shall be capable of furnishing not less than 150% rated capacity at a head of not less than 65% of the rated head.[ii] The shut-off head shall not exceed 120% of rated head.[iii] The coupling guard shall be of zero access type.[iv] The quoted rate shall include providing and fixing of vibration pad, common base plate, foundation bolts, grouting etc. [v] Pump sets shall be as per NFPA-20[vi] Pump sets shall be installed as per IS 15301: 2003 |
| 121 | Supply, installation, testing, and commissioning of Fully automatic DOL starter, suitable for the booster pump as mentioned as Item No. 104 here-in-before, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc.with complete all as specified and directed. |
| 122 | Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor, cubical compartmental type \"Motor Control Center\" (MCC) of suitable size, conforming to IEC 61641, having both sides openable with hinged double doors & locking arrangement and IP 54 protection made out of 2.00 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation(1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed. |
| 123 | The MCC shall comprise of the following:[A] BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 630 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection[B] INCOMING[i] Circuit Breaker(a) 320 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2: 2016, having microprocessor based trip unit, adjustable overload setting, adjustable short-circuit setting, adjustable neutral protection, electrical interlocking, front indication LEDs, etc.- 01 Nos.[ii] Instrumentation & Measurement(a) Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos.(b) 400/5A Cl. 1.0 C.T. with 15 VA burden- 01 Nos.(c) 6A, 10kA, 415V, 50 Hz 4P MCB- 01 Nos.[iii] Indication & Annunciation(a) LED phase indicators (Red, Yellow, Blue)- 01 Set(b) LED status indicators (ON, OFF, TRIP)- 01 Set(c) LED status indicators (SC, SP, TP)- 01 Set |
| 124 | [C] OUTGOING[i] 125 A, 415 V, Ics = 100% Icu = 16 kA, 50 Hz 3P MCCB, conforming to IEC 60947-2- 03 Nos. [for electric driven main fire pump][ii] Fully automatic digital soft starter suitable for 45 kW drive having adaptive acceleration control, built-in RTD & thermistor inputs, programmable auto start/stop, emergency run operation, fully programmable overload trip, etc. complete with contactors, push button, LED type indicators, auto/manual selector switch, current sensing type single phase preventer complete with all accessories and wiring etc.- 03 Nos. [iii] 32 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz 3P MCCB, conforming to IEC 60947-2, 02 Nos. [for jockey pump][iv] Fully automatic DOL starter, suitable for 5.5 kW motor, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc.- 03 Nos. [v] Control for diesel engine comprising of automatic / manual selector switch & three attempts starting device, timers and relays as required, push buttons, start / stop in manual mode, indicating lamp for high / low lubrication oil pressure, high water temperature and engine on indication, battery charger suitable for 12 V / 24 V DC with boost and trickle selector switch, 0- 30 V DC voltmeter and 0-20 A DC ammeter complete with all standard relays and accessories for automatic operation of the diesel engine - 01 Nos. [for diesel engine pump][vi] 32 A, 10 kA, 250 V, 50 Hz, SPN MCB- 01 Nos. |
| 125 | Instrumentation & Measurement(a) 200/5A Cl. 1.0 C.T. with 15 VA burden- 03 Nos.(b) 50/5A Cl. 1.0 C.T. with 5 VA burden- 02 Nos.(c) 0-200 A ammeter- 03 Nos.(d) 0-50 A ammeter- 02 Nos.Indication & Annunciation(a) LED status indicators (ON, OFF, TRIP)- 04 SetNOTES: [i] The Panel shall be purchased from the original equipment manufacturer (OEM) only.[ii] The bidder shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, GADs, etc. for approval of the Engineer-in-Charge. |
| 126 | M&L for low smoke zero halogen (LS0H) Fire survival Control cable with circuit integrity, conforming to BS 7846 and rated for 600 V, having plain annealed stranded copper conductor with fire-resistant mica tapes covered by an extruded layer of cross-linked polyethylene, extruded layer of thermoplastic low smoke zero halogen (LS0H) compound, single layer of galvanized steel wires and thermoplastic LS0H compound sheath, suitable for operating temperature range -40 ˚C to +90 ˚C and minimum bending radius being 12 times the overall cable diameter, including laying, clamping, termination and ferruling complete all as specified and directed. |
| 127 | 2 core, 2.5 mm² (for instrumentation) |
| 128 | 3 core, 2.5 mm² (for auto start/stop panel) |
| 129 | 12 core, 2.5 mm² (for diesel engine pump) |
| 130 | M & L for 1.1 kV grade Copper conductor, XLPE insulated armoured cable conforming to IS 7098-1: 1988, having stranded aluminium compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination complete all as specified and directed. |
| 131 | 3 core 95 mm² (for electric motor driven main fire pump) |
| 132 | 3 core 6 mm² (for jockey pump) |
| 133 | S & F of perforated hot dipped galvanized iron cable tray having galvanization thickness not less than 50 microns and perforation not more than 17.5% including fittigs viz. joints, bends, tees, etc. in convenient sections of length complete including cable tray supports supports and associated accessories, all as specified and directed. |
| 134 | 300 mm X 50 mm X 1.6 mm |
| 135 | 150 mm X 50 mm X 1.6 mm |
| 136 | 100 mm X 50 mm X 1.6 mm |
| 137 | M & L for PN 1.6 rated 200 mm NB polypropelene Vortex Inhibitor suction lift, conforming to BS 4504 with stainless wire mesh, bolts, nuts and washers, etc. complete all as specified and directed. |
| 138 | M & L for PN 1.6 rated CI \"Y\" -type strainer for suction conforming to IS 907: 1984 with SS filter screen and flange drilling standard end connection conforming to IS 1538: 1993 along with necessary accessories complete all as specified and directed. |
| 139 | 150mm NB |
| 140 | 200mm NB |
| 141 | Supply, installation, testing and commissioning of PN 1.6 rated CI Swing Check type reflux (Non Return) valve, conforming to IS 5312 (Part 1): 2004, having CI body & flap, H.T. brass locking pin / hinge pin, EPDM \"O\" ring, G.M. locking plug, CS eye bolt, flange drilling standard end connection conforming to IS 1538: 1993 along with necessary accessories complete as specified and directed. |
| 142 | 200 mm NB (At Main Pump header) |
| 143 | 150 mm NB (At Main Pump discharge, 2 Way Fire Briage connection) |
| 144 | 50 mm NB (At Jockey Pump discharge) |
| 145 | S & F of CL 150 # rated ball valve, designed & manufactured as per IS: 9890 (1981) and tested as per BS 6755 Part- I, having floating type three piece design, CS body, SS- 304 ball, PTFE seal / packing / gasket, CS fastners and lever and screwed/socket weld end connection, etc. with accessories complete all as specified and directed. |
| 146 | 25 mm NB |
| 147 | 50 mm NB |
| 148 | 80 mm NB |
| 149 | Supply, installation, testing and commissioning of bourdon Pressure gauge suitable for 0-21 kg pressure range with 4\" dial, die cast aluminium body, ball valve, nipple, socket, etc. for delivery lines of fire pump sets near the flow switches all complete as specified and directed. |
| 150 | M & L for PN 1.6 rated GI puddle flange designed & manufactured as per BS 1560-3.1 & BS 4504 for suction of fire pumps from water tank all complete all as specified and directed. |
| 151 | 200 mm NB |
| 152 | 150 mm NB |
| 153 | 100 mm NB |
| 154 | S & F gunmetal fire hydrant single Landing valve with 80 mm NB flanged inlet, brass spindle controlled 63 mm NB female instantaneous outlet type gunmetal coupling, blank cap, chain, twist release type lug & all accessories conforming to IS 5290: 1993 including fixing and flanged tapping from stand post type fire hydrant complete all as specified and directed. |
| 155 | S & F of Orifice plate made out of 6 mm thick SS 304 with orifice of required size to be fitted between flange and landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete all as specified and directed. |
| 156 | Supply, installation, testing and commissioning of 2- Way Fire Brigade draw- off connection with two 63 mm NB inbuilt gunmetal non-return valves instantaneous coupling type arranged on 100 mm NB pipe manifold and connected to wet riser main as well as to fire water tank including CI butterfly valve, CI non-return valve and MS cabinet with mounting supports, etc. complete all as specified and directed. |
| 157 | Supply, installation, testing and commissioning of 4-way fire brigade inlet connection, with four 63 mm NB inbuilt gunmetal non-return valves, four 63 mm NB instantaneous couplings arranged on 150 mm NB pipe manifold and connected to fire hydrant ring main and fire hydrant wet riser pipecomplete all as specified and directed. |
| 158 | Supply, installation, testing and commissioning of 2-Way Fire Brigade inlet connection, conforming to IS: 5290- 1993, with two 63 mm NB inbuilt gunmetal non-return valves, two 63 mm NB instantaneous couplings arranged on 100 mm NB pipe manifold and connected to fire hydrant ring main and fire hydrant wet riser pipecomplete as specified and directed. |
| 159 | Supply, installation, testing and commissioning of automatic air-vent valve with 20 mm end connections, brass body and cover, plastic float, brass cap etc. suitable for maximum operating pressure of 16 bar and maximum operating temperature 100 °C respectively, installed on all high points in the water piping system to automatically remove the trapped air complete all as specified and directed. |
| 160 | M & L for FM approved and UL listed, PN 1.6 rated lever operated, wafer type CI Butterfly valve, conforming to IS 13095: 1991,fitted with visual indicator & temper switch, having Cast iron (CI) body with ductile iron EPDM coated disc, SS431 stub shaft, PTFE bushing, flange drilling standard end connection conforming to IS: 1538- 1993 along with necessary accessories complete as specified and directed(for Zone control valve assembly). |
| 161 | 100 mm NB |
| 162 | M & L for FM approved and UL listed 25 mm NB compact 3 position ball valve with drain orifice (Test and Drain valve) to test and drain water flow through sprinkler systems having OFF-TEST-DRAIN position, integral sight glass, rated pressure 300 psi, orifice size 15 mm and K factor 5.6, conforming to NFPA 13, along with necessary accessories complete as specified and directed. |
| 163 | S & F of 4.5 kg light-weight squeeze grip CO2 type fire extinguisher, conforming to IS 15683: 2006, with CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel with wheel type valve, discharge nozzle, bend & horn, wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed.NOTES:[i] Test Pressure: 250 kgf / Sq. cm[ii] Operating temperature :-300C to + 550C[iii] Locking pin and wire seal should be provided to indicate that the extinguisher has not been use.[iv]Every Extinguisher should be supplied with an operating manual. |
| 164 | S & F 6 kg capacity dry chemical powder (ABC) type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket / floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed.NOTES: [i] Operating temperature :-30°C to + 55°C[ii] Performance criteria : Discharge time not less than 45 sec , thrownot less than 4 meters[iii] Hydro test and burst pressure test : Shall pass hydro test pressure of 35 bars 2.5 minutes and with stand a burst pressure of 55 bar |
| 165 | S & F of 9 litre water stored pressure type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted with gunmetal union, high pressure CO2 gas cartridge, hose and ABS type branch pipe and wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed. |
| 166 | S & F 4 kg capacity Clean Agent type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket / floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed. |
| 167 | S&F of the following type of sygnages made out of 3mm thick opaque PVC foam board with computer cut, PVC non-reflective self adhesive vinyl painted foram board, complete with mirror fasteners complete all specified and directed. |
| 168 | S & F of Signage having size 300 mm X 150 mm reading \"EXIT\" in 12.5 mm block letters in Green and white background, self illuminated properly spaced to provide good legibility located directly in corridor near to each staircase and squarely attached to the wall or partition in a way that the top of the sign is not above 2 m from the finished floor level.These lights shall emit the maximum light required even during the electricity supply or in Black out period with high energy efficiency manufactured using superior quality Aluminium Extrusion body raw material complete all as specified and directed.EXIT Signage shall meet the following technical / operational requirements:[i] Product Material: Alluminium ALLOY Extrusion[ii] Product Finish:- Matt Black / Snow white finish after phosphochromate treatment[iii] Wattage:- 5 Watt[iv] Mounting: Surface/ Hanging |
| 169 | S & F of Signage having size of 500 mm X 500 mm, indicating the \"Floor Number\" in bold type and at 75 mm high numerals in red and white background, made out of 3 mm thick opaque PVC foam board with computer cut, PVC non-reflective self adhesive vinyle painted foam board, posted and maintained within each stair enclosure on every floor, securely attached to the stair side of the door in a way that the bottom of the sign is not above 1.5 m from the finished floor level complete all as specified and directed. |
| 170 | S & F of Signage having size of 450 MM X 150 MM reading \"FIRE EXTINGUISHER\" in 12.5 mm block letters in White and Red background, made out of 3 mm thick opaque PVC foam board with computer cut, PVC non-reflective self adhesive vinyle painted foam board,properly spaced to provide good legibility located directly in corridor near to each Manual call point/Fire Extinguisher and squarely attached to the wall or partition in a way that the top of the sign is not above 2 m from the finished floor level complete all as specified and directed. |
| 171 | S & F of Signage having size of 150 mm X 600 mm, posted and maintained at each lift landing and on the side of the stairway door from which egress is to be made on every floor, indicating the \"STAIRCASE\" by an alphabetical letter in bold type and at 75 mm high letters in red and white background, made out of 3 mm thick opaque PVC foam board with computer cut, PVC non-reflective self adhesive vinyle painted foam board,securely attached to the side of the stairway door from which egress is to be made in a way that the bottom of the sign is not above 1.5 m from the finished floor level complete all as specified and directed. |
| 172 | DG SETSupply, installation, testing and commissioning Silent Diesel engine driven generating set complete as per CPCB IV / latest CPCB provision with accoustic enclosure and control system for 1800 KVA out put at site ie at MSL after de rating Ac 415 Vollts, 50 C/S, 3 phase 4 wire directly coupled complete with self starting system with and including accessories, equipment control panel etc as detailed below:-(a) Diesel Engine :-Diesel engine water cooled and electric start suitable to drive mentioned alternator independently, coupled directly through coupling , sixteen cylinder 4 stroke, cold starting,1500 RPM industrial type as per BS:5514/IS-10001/10002 or updated IS standard suitable to regulate speed of DG set from no load to full load complete with fuel tank of capacity as per manufacture\"s recommendations, fuel line exhaust pipe duly insulated with asbestos rope and with support and silencermufflers etc for contuious operation and standard accessories, sump pre heaters etc all as specified and directed. |
| 173 | Air Intake System(i) Air intake mainfold, (ii) Dry type air cleaner, (iii) Vaccum indicatorExhaust System(i) Turbo charger, (ii) Flexible connection, (iii) Exhaust mainfold, (iv) Residential silencerCoolent System(i) Engine water pump, (ii) Radiator, (iii) Coolant additive concentrateLubrication System(i) Oil pan, (ii) Engine mounted lube oil pump, (iii) Full flow spin-on lube oil filterFuel System(i) Electronic Governor-A1, (ii) 24 V DC (Battery 160 AH- 04 Nos) Solenoid coil, (iii) Dual fuel filter systemStarting System(i) 24 Volt DC electric starter(ii) 24 Volt DC battery charging alternator |
| 174 | (b) Alternator :- Synchronous alternator of 1800 KVA output at 0.80 PF AC 3 phase 4 wire 415volts 50 C/S self exicted & self regulated through AVR, alternator will be suitable for tropical climate and screen protected drip proof type with two ends shield ball/ roller bearing with damper winding in each pole faces as per IS:13364/BS -2613-1970 or updated IS standard complete all as specified and directed. (c) Control Panel:-The standard control panel from consisting of control cubical fabricated 14/16 SWG sheet steel construction indoor type suitable for mounting accssories, static energy meter with LED display, digitalpower factor meter, digital frequency meter and digital RPM Meter,digital volt meter (0-500V) with inbuiltselector switch, digital ammeter, CT\"s operatedof suitable rating with inbuilt selector switch , indicator lamp LED type, hours meter , low oil pressure indicaton, over speed indication and high water temperature indicator. |
| 175 | (d) Electric starter equipment:- The equipment will comprise the following.:-(i) Maintenance free battery duly intial charged & battery lead of adequate capacity,, make of battery- Exide/luminious/sukam.(ii) Starter motor(iii) Starter gearing(iv) start/stop push button(v) Invertor cum battery charger 500 VA capacity suitable to work on 230 volts 50 Hz AC supply system for charging of DG set batteriesexternally when DG set is in off position. Make -Sukam/microtec.(vi) Alternator/Dynamo of suitable capacity to charge the batterieswhile DG set is running complete with auto cut all as per manufacture\"s recommendations.PCC foundation for DG set will be as per manufacturer recommendation and directed and rate of PCC foundation is inclusive in the quotaed rate and No extra payment paid to contractor for the same. |
| 176 | (e) AMF Panel:- Auto mains failure panel 415 volts 50 Hz suitable for 1800 KVA Gen set detailed above, made out of 16 guage MS sheet cubical type floor mounted front and rear door openablewith locking arrangement duly powder coated with bus bar trunking system arrangement for connection with main substation panel of suitable capacity for and including the following:- (i) Auto transfer switch 4 pole min 2600 Amps or above 415 volts with 4 No pole 25 KA rupturing capacity MCCBs , ATS electronic control box for automatic switching ON and OFF of DG set and transfer of load, pre assembled and ready to use complete in all respected equipped with microprocessor based controller 100% auto 50% auto by pass arrangement adjustable time delay to engine start , standard setting 3 seconds adjustable0-10 seconds, adjustable time delay on transfer to nominal 0-30 minute time delay(adjustable) to engine cool down 0-5 minutes, adjustable time delay on transfer to emergency 0-15 seconds. |
| 177 | (ii) Volt meter 30-600 volts, flush mfd 96 Sqmm, digital type with selector switch suitable to connect volt meter to stand by main supply.(iii) Ammeter 0-300 amps CT\"s operated flush mfd 96 Sqmm digital typewith selector switchand CT\"s of appropriate ratio. (iv) Digital frequency meter 04 digit flush mfd 96 Sqmm size for frequency range 30 to 19.99 Hz with buikt in transducer. (v) Digital power factor meter 440 volts 5 amps with built in traducer flush mfd 96 Sqmm size.(vi) Indicator lamp LED type 230 volts for Gen/main supply ON/Off indicator and different relay position etc call as required and recommended by manufacturer.(vii) Breaker control switch as per OEM.All accessories prewired with suitable size PVC insulated copper conductor cable of appropriate size including connection from DG set all as required at site including foundation as per manufacturer recommendation. |
| 178 | WATER COOLERSupply and fix Voltage stabilizer for automatic Each operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA complete all as specified and directed. |
| 179 | LIFTSupply, installation, testing & commissioning of Passenger lift machine room lesselectrically operated with modular microprocessor based controls, complete with power driven automatic center opening with 18 SWG stainless steel (SS) moon rock finish sliding car doors and landing doors having stainless steel (SS) car enclosure suitable to carry 08 passenger lifts (544 kgs) at speed of 1.5 M/Sec to serve upto 8 floors (G+7) ,full collective operation with all standard features mentioned below and human interface device (HID) and along with (ARD) automatic resucue deviceconfirming to NBC 2016, IS 14665 (Part-1): 2000 andIS 14665 (Part-2/Sec 1 &2) & (Part-3/Sec 1 &2) : 2000( latest edition and amendment up to date)complete all as specified & directed |
| 180 | (a)Type & capacity :08 Passenger lift (544 Kgs) (b)Type of drive : variable voltage , variable frequencyregenerative drive( Closed loop) with micro processor based controller 15 mm landing accuracy with speed encloder.(c)Speed: 1.5 meter per second.( as per IS provision)(d)Type of Machine : Gearless machine with synchronous permanent magnet motor (located in shaft on top of guide rails)(e)Rise/Travel: Eight Floor (G+7)(f) Electric Supply: The entire lift equipment should be suitable for operation at three phases, 415V±10%, 50 Hz ±3% A.C. electric supply. The supply for illumination and signaling equipment shall be 230V, 1-Ph A.C.(g) Requried well size : 1800 mm x 2100 mm (well size as per NBC/IS code provision)(h)Control: Automatic based simplex collective selective control with provision of with/without attendant control(j)Inner Size/Car size : 1100mmCWx 1400mm CD (approx).(h) Car Enclosure:Car cage made out of SS minimum 18 SWG Stainless steel panel, SS roof/false ceiling (hairline finish and mirror finish handrall ).(k)Flooring : Cage floor made from stainless steel chequered plate 5mm thick (l)Electric light: LEDlight fittings with all accessories.5 LED lightning in car.(m)Fan :Pressure fan, 400 mm sweep-01 No. Brake: Braking of the lift will be done by electronically varying the voltage and the frequency of motor feeding current (variable Voltage and Variable frequency control) i.e., VVVF control(n)Car Entrance: Automatic centre opening in stainless steel hairline finish.(o)Door Opening:Center opening doors 800mm W x 2000mm H with provision of emergency key opening at all landings.SS car door finishwith 2 hr. fire resistance door duly supported by valid test certificate issued by NABL accredited or Independent test laboratory.Car door lock compatible.(p)Door Operation: Automatic power operation with adjustable door opening and closing timings.Variable speed high-traffic door operator(q)Monitoring: Pulse 24/7 belt integrity monitoring system and Automated rescue operation(r)Suspension : Lubrication free,Stainless steel polyurethane-coated belts.(s)Indicators: Hall position indcators for car & landing Direction and position indicator with stainless steel fixtures at all floor. |
| 181 | The following shall also be provided in addition to aboveSTANDARD FEATURE (i)Anti Nuisancecar call protection.(ii)Automatic car return device (homelanding).(iii)Independent service ( for Simplex only).(iv)Overlaoding Device.(v)Nudging.(vi)Emenrgency fireman\"s service.(vii)Audio\"s car call button. (viii)Emergency Car light unit.(ix) High performance contact free infrared curtain door protection.(x) Door time protection.(xi)Emergency Alarm button.(xii)Extra door time of lobby & parking.(xiii)Door open close button.(xiv)Manual rescue operation .(xv) Belt inspection device 7 auto fan cut off. |
| 182 | ADDITIONAL DEVICE Automatic rescue,infra red sensor,overload warning indicator and floor announcing system with music/ariival chimeHUMAN INTERFACE DEVICE(i)Hall button with micro stroke push buttons combained with 16 signals digital LED display position indicator.(ii)Full height car operating panel with micro stroke call push button located on side panel. (iii)Door open door closed on car operating panel.(iv)2 way inter communication system in cabin(v)Dot matrix position indicator.(vi)Battery operated alarm well & emergency light.(vii)Fireman witch at main lobby.(viii)Manual rescue operation(ix) Call register indicator in all landings.(x) Attendant operation in car panel.(xi) Diffused Lighting fixture/LED Lighting(xii) Lighting forcar operating panel with door open/close buttonSAFETY FEATURESMotor overheat protection , phase failureand reversal protection and features as per ISI / IS code /NBC Provision.Every lift installation shall necessarily be provided with the safety features in accordance with IS 14665(Part-4/Sec-4):2001 |
| 183 | Supply, installation, testing & commissioning of Passenger lift machine room lesselectrically operated with modular microprocessor based controls, complete with power driven automatic center opening with 18 SWG stainless steel (SS) moon rock finish sliding car doors and landing doors having stainless steel (SS) car enclosure suitable to carry 20 passenger lifts ( 1360 kgs) at speed of 1.5 M/Sec to serve upto 8 floors (G+7) ,full collective operation with all standard features mentioned below and human interface device (HID) and along with (ARD) automatic resucue deviceconfirming to NBC 2016, IS 14665 (Part-1): 2000 andIS 14665 (Part-2/Sec 1 &2) & (Part-3/Sec 1 &2) : 2000( latest edition and amendment up to date)complete all as specified and l as per following technical specification of Make: KONE / OTIS / SCHEINDER / MITSUBISHI. |
| 184 | (a)Type & capacity :20 Passenger lift (1360 Kgs)(b)Type of drive : variable voltage , variable frequencyregenerative drive( Closed loop) with micro processor based controller 15 mm landing accuracy with speed encloder.(c)Speed: 1.5 meter per second.( as per IS provision)(d)Type of Machine : Gearless machine with synchronous permanent magnet motor (located in shaft on top of guide rails)(e)Rise/Travel: Eight Floor (G+7)(f) Electric Supply: The entire lift equipment should be suitable for operation at three phases, 415V±10%, 50 Hz ±3% A.C. electric supply. The supply for illumination and signaling equipment shall be 230V, 1-Ph A.C.(g) Requried well size : 2300 mm x 2700 mm or (well size as per NBC/IS code provision)(h)Control: Automatic based simplex collective selective control with provision of with/without attendant control(j)Inner Size/Car size : 1300mmCWx 2400mm CD (approx).(h) Car Enclosure:Car cage made out of SS minimum 18 SWG Stainless steel panel, SS roof/false ceiling (hairline finish and mirror finish handrall ).(k)Flooring : Cage floor made from stainless steel chequered plate 5mm thick .(l)Electric light: LEDlight fittings with all accessories.5 LED lightning in car.(m)Fan :Pressure fan, 400 mm sweep-01 No. Brake: Braking of the lift will be done by electronically varying the voltage and the frequency of motor feeding current (variable Voltage and Variable frequency control) i.e., VVVF control(n)Car Entrance: Automatic centre opening in stainless steel hairline finish.(o)Door Opening:Center opening doors 1100mm W x 2400mm H with provision of emergency key opening at all landings.SS car door finishwith 2 hr. fire resistance door duly supported by valid test certificate issued by NABL accredited or Independent test laboratory.Car door lock compatible.(p)Door Operation: Automatic power operation with adjustable door opening and closing timings.Variable speed high-traffic door operator(q)Monitoring: Pulse 24/7 belt integrity monitoring system and Automated rescue operation(r)Suspension : Lubrication free,Stainless steel polyurethane-coated belts.(s)Indicators: Hall position indcators for car & landing Direction and position indicator with stainless steel fixtures at all floor. |
| 185 | The following shall also be provided in addition to aboveSTANDARD FEATURE (i)Anti Nuisancecar call protection.(ii)Automatic car return device (homelanding).(iii)Independent service ( for Simplex only).(iv)Overlaoding Device.(v)Nudging.(vi)Emenrgency fireman\"s service.(vii)Audio\"s car call button.(viii)Emergency Car light unit.(h) Car Enclosure:Car cage made out of SS minimum 18 SWG Stainless steel panel, SS roof/false ceiling (hairline finish and mirror finish handrall ).(x) Door time protection.(xi)Emergency Alarm button.(xii)Extra door time of lobby & parking.(xiii)Door open close button.(xiv)Manual rescue operation .(xv) Belt inspection device 7 auto fan cut off. |
| 186 | ADDITIONAL DEVICE Automatic rescue,infra red sensor,overload warning indicator and floor announcing system with music/ariival chimeHUMAN INTERFACE DEVICE(i)Hall button with micro stroke push buttons combained with 16 signals digital LED display position indicator.(ii)Full height car operating panel with micro stroke call push button located on side panel. (iii)Door open door closed on car operating panel.(iv)2 way inter communication system in cabin(v)Dot matrix position indicator.(vi)Battery operated alarm well & emergency light.(vii)Fireman witch at main lobby.(viii)Manual rescue operation(ix) Call register indicator in all landings.(x) Attendant operation in car panel.(xi) Diffused Lighting fixture/LED Lighting(xii) Lighting forcar operating panel with door open/close buttonSAFETY FEATURESMotor overheat protection , phase failureand reversal protection and features as per ISI / IS code /NBC Provision.Every lift installation shall necessarily be provided with the safety features in accordance with IS 14665(Part-4/Sec-4):2001 |
| 187 | Note for Item No.132.00 & 133.00: (i) Contractor shall notethat the defects liability period for lift shall be three years from the cerftified date of completion on as certified by GE: During the said defects liability period, the lift shall be kept functioned serviceable all the time and all consumable items shall also be provided by contractor for runnig of the lift.(ii)The lift shall be inspected and commissioned by the lift inspector and it shall be the responsibility of the contractor to get the lift inspected & commissioned without any extra cost to the department.(iii) Cost of the above provisions shall be deemed in the rates quated by contractor. (iv) All dimensions given above are recommended dimensions . In the event of any variations mutually agreed between manufacturer and purchaser are permitted. However, variation in car inside dimensions shall be within the maximum area limits specified in 1S 14665 (Part 3/Sec 1).(v) Dimensions of pit depth and overhead may differ in practice as per individual manufacturer’s design depending upon load, speed and drive. However, the pit depth and overhead shall be such as to confirm to the requirements of bottom clearance and top clearanceof IS 14665 (Part 2/Sec 1). |
| 188 | (vi) Contractor to obtain permission and approval prior to commencement of work and lift license from state govt authority.(vii) Item cost includesrequired scaffolding & structural steel brackets for erecting lift as per above specification, obtaining required all necessary permissions of Lift inspector to erect and complete the elevator work, Laisons to operate the elevators including all necessary charges,payments for the same etc complete.(viii) Contractor to verify all above required dimension at site prior to procurement of lift . In the event of any variation the commercially available standard size lift with respect to load and category shall be submit to dept for approval.(ix) Contractor shall submit GA drawing along with other relevant details to GE for approval prior to procurement of lift.(x) The contractor shall be responsible for 2 years defect liability period from certified date of completion of GE. During the said defect liability period the lift shall be kept functional/serviceable all the time & all consumable items shall be provided by contractor for operation & maintenance of lift. All periodical maintenance regular check up/inspection should be carried out OEM during 02 years defect liability period in addition to regular checkups and periodical services special visit/inspection will also be carried to rectify defects by representative of OEM if any emergency / trouble developed. An agreement will be made between contractor & OEM and this shall be submitted to GE onr the date of handing over to lift (date of completion) for the comprenssive maintenance of defect liability period. The cost of above shall be deemed to be included in the quoted rates. (xi) The provision of suitable steel structure/platform for installation of lifts equipment is part of lift items and nothing extra should be paid |
| 189 | Supply and fix double door vertical type load line MCB TPN distribution board, double door triple pole and neutral 4 way 415 volts for lift complete all as specified. |
| 190 | Supply and fixedMCB TPN pole, 63 Amps415 volts, 50 Hz \"C\" Curve having breaking capacity 10 KA with thermal magnetic protection unit and testing Complete all as specified and directed. |
| 191 | S & FMCB SP 240 volts \"C\" Curve suitable for fixing in DB of capacity 6 to 32 Amps complete, all as specified. |
| 192 | M& L for earthing complete with copper earth plate electrode 60cm x60 cm x 3.15.0 mm thick buried directly in ground (earth pit not less than 2.25 Mtrs deep below ground level) with top edge of the plate not less than 1.50 Mtr below normal ground level connected to copper earth lead strip 25 mmx3 mmby means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.5 connected to earthing test point all as specified or indicated including testing on completion including PCC pit in (1:3:6) type C-2 cement concrete .RCC 1:2:4 Mix type B reinforced with 6mm dia MS bars @ 150mm RCC cover slab 40mm thick with two no’s fitting handle, GI pipe 20mm dia light grade with funnel & wire mesh for watering and 40mm dia light grade GI pipe for earth strip 4 mm protection etc. complete all as specified and directed. |
| 193 | M&L for earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6.0 mm thick burried directly in ground not less than 2.25 mtrs deep below normal ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level, surrounded from all sides with mixture of charcoal and common salt and electrode to galvanised earth lead wire 4.00 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel protected by galvanised iron light grade 15 mm dia pipe and GI Pipe 20 mm light grade for water filling including 15x20 mm reducer socket funnel wire mesh, RCC cover PCC chamber pit with PCC (1:3:6) type C-2 excavation and earth work, disposal of surplus spoil, to a distance not exceeding 50 mtrs all as specified and shown on electrical plate No. 3 of 1991 (Part-I) including taking out old existing earthing complete all as specified & directed. |
| 194 | Supply & fix GI wire of dia 4 mm complete with saddles and porcelain insulators fixed at 400 mm apart to each other to hold GI wire/strip including screws in complete all as specified and directed. |
| 195 | Supply & fix aluminium strip 20 mm x 3mm complete with saddles and fixing screws for fitting the strip complete all as specified and directed. |
| 196 | TELEPHONE CONDUITSupply and fixing following size/modules alongwith modular base and cover plate for modular socket in wall required completed all as specified and directed. |
| 197 | 1 or 2 Module |
| 198 | M&L for cutting and chasing of surface/recess in wall for fixing the PVC conduit and making good the distrubed portion of all floor, ceiling etc all specified and directed. |
| 199 | S&F RJ11 Telephone socket modular type with transperent shutter 1 module with modular plate, flush box & frame complete all as specified and directed. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |