| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 2 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. Group C |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5sq. mm earth wire |
| 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 4 sq. mm + 1 X 4 sq.mm earth wire |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 6 sq. mm + 1 X 6 sq.mm earth wire |
| 6 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 10 sq. mm + 1 X 6 sq.mm earth wire |
| 7 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and makinggood the same in case of recessed conduit as required. 20 mm |
| 8 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 9 | Supplying and fixing call bell/ buzzer suitable for single phase,230 V,complete as required. |
| 10 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. asrequired. |
| 11 | Supplying and fixing following way, single pole and neutral, sheet steel,MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way , Double door |
| 12 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc.as required. Single Pole (a) Single Pole |
| 13 | Supplying and fixing following rating, double pole, 240 V, isolator in theexisting MCB DB complete with connections, testing and commissioning etc. as required.(a) 63 amps |
| 14 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc.as required.(a) 40 amps |
| 15 | P/FHot press sheet mouldedcompound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof polebox of innerdimension 200x160x98mm (NS) complete with suitable arrangement for fixing of 2 nosof 6 to 32 amp single pole MCB & 63 Amp. Doublepole isolator (MCB/Isolator excluded) withneutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plateof suitable size with danger monogram property printed on the coveretc asreqd. asreqd. |
| 16 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K/6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.).Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extrudedaluminium Body (Thickness ≥ 1.20 mm)18-22 Watt |
| 17 | Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140 270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 degcentigrade,internalsurge protection of 2.5 KV with Short & Open circuitprotection, THD < 10% , P. F.≥0.95,IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flickershould be below 5 %), life time (LED,Driver & electrical circuitry), of minimum50000 Burning Hours with, 70% of initial Lumen maintained tilllife ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K /4000°K/5700°K /6000°K / 6500°K(As perANSI Bin),SDCM(Standard Deviation Color Matching) <3, Maximumpower consumption should not more than the specified rating and Fixture shall be ofrelevant BIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. completeinallrespecti/c connectionswith1.5sqmmFRLS,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy ≥105<120 lm/Watt output . LM79 & LM80 Test reportfromNABL lab foralltestingrequiredforLED fixtures as per BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement:heatsinkofaluminumhousing such that LED junction temperature shall not rise above 90°C)Powder coated die cast/ Extruded aluminium Body (Thickness≥ 1.20 mm) 36W |
| 18 | Supply, Installation, Testing and Commissioning ofceiling fan with Brush Less DirectCurrent (BLDC)Motor,classofinsulation:B, 3 nos.metal (Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation withregulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019fan Supply, earthing etc. complete as req. 1400mm,service value≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min(Minimum) |
| 19 | SITC of wall mounted Fan 400mm sweep rated voltage 220-230 AC ratedfrequency 50Hz speed 1280-1350 rpm with desire color. |
| 20 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall beignored) |
| 21 | Supply and Fixing of3 mm thick phenolic laminated sheet |
| 22 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \"C\" curve including connections, painting etc. as required. |
| 23 | Supply of 250 mm ( 10\" )sweep 1250 RPM exhaust fan Fresh Air Typecomplete with shutter,blade etc as required. |
| 24 | Installation of exhaust fan in the existing opening, includingmaking good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep |
| 25 | SITC of 4 KVA voltage stabilizer having inpur voltage 150 V -270 and outputvoltage of 195-245 V |
| 26 | SITC of Copper pipe for split AC |
| 27 | SITC of drain pipe |
| 28 | SITC of 3 core , 4 sqmm electrical wire for air conditioner |
| 29 | LED Street light fixture, powder coated pressure die cast aluminum body (Systemlumen efficacy >135 lm/Watt)Supplying,installation,Testing&Commissioning ofStreetlightLEDfixture, powdercoated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage:140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-45, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95,IP 66,IK-10,CRI>80,undervoltageandovervoltageprotection,EMI EMCasper CISPR-15, lenses for beam angle as per IESNA type I/II/III asper the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry)ofminimum50000BurningHourswith70%ofinitial Lumenmaintained tilllifeends as per LM80 extrapolation IES TM-21-11 report,CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(StandardDeviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be ofrelevant BIS standard completeinallrespecti/cconnectionswith1.5sqmmFRLS,PVC insulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy>135lm/Watt output . LM79 & LM80 Test reportfromNABLlab foralltestingrequired forLED fixtures as per BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management:heatsinkofaluminumhousing such that LED junctiontemperature shall not rise above 90°C) 50W |
| 30 | Supply , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R 407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694or IS 9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature).1.5 TRwith 5 Star BEE Rating |