| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group C |
| 3 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 4 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 5 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 6 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 7 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 8 | 2 x 6 sq. mm |
| 9 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 10 | 25 mm |
| 11 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 12 | 15/16 A switch |
| 13 | 6 pin 15/16 A socket outlet |
| 14 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 15 | 6 Module (200mmX75mm) |
| 16 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 17 | 4 way (4 + 12), Double door |
| 18 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 19 | Single pole |
| 20 | Triple pole |
| 21 | Triple pole and neutral |
| 22 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 23 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 24 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessoriesn including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 25 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 26 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 27 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 28 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 29 | 4 X 25 sq. mm (28mm) |
| 30 | Supply, loading, transportation, unloading at site, storage st site, shifting from storage place to site of following size of XLPE Insulated PVC Sheathed, Aluminium Conductor armoured power cable of 1.1 KV grade conforming to IS amended upto date and as per specifications |
| 31 | 4C X 25 sq. mm XLPE Al Cable |
| 32 | Supplying and fixing 63 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 33 | Triple pole |
| 34 | Four pole |
| 35 | Supplying and fixing of 32A, 415V , 3P+N+E FP Industrial type Plug and socket DBin sheet steel enclosure, on surface or in recess complete with connections, testing and commissioning etc. as required. |
| 36 | Supplying and fixing of 63A, 415V , 3P+N+E FP Industrial type Plug and socket DBin sheet steel enclosure, on surface or in recess complete with connections, testing and commissioning etc. as required. |
| 37 | Supply, Installation, testing and commissioning of 30W LEDwell glass Luminaire, environmental friendly, energy saving long life corrosion resistant, vertical surface mounting pressure die-cast aluminium housing (light engine) with high power LED as light source , complete with all accessoriesetc. connection with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable and earthing etc. as required. |