| 1 | Supply , installation , testing and commissioning in replacement of microprocessor basedfire alarm control panel 1/2 loop capacity analogue addressable(FC 924Panel )including necessary addressing andprogramming of sensors, MCP, Sounders or any other connected device as per site requirement complete all as specified and as directed by Engr-in-charge. Make: Siemens or any other equivalent in honeywell/CEASE Fire/EDWARD |
| 2 | S&F in replacement of Batteries DC , 12 V 7 AH lead acid duly initial charged complete all as specified and as directed by Engr-in-charge. Make: Exide/Amaron/Star Gold |
| 3 | Supply , installation, testing and commissioning of configuration Graphicsoftware -GUI based- to monitor and control the status of the FACP from the windows based system with visual and sound alert for the fire and fault conditions including Location programming for each device- Monitor & control the statuswith valid Licence validity suitable for FACP(CCA-CMPT-DMS CC Compact drns) complete all as specified and as directed by Engr-in-charge.Make: Siemens/Honeywell/CeaseFire/EDWARD Note. Software for Fire Alarm(FACP) with validity of Licence are deemed to be included in quoted rate with necessary T&P charges. |
| 4 | Supply, installation, testing and commissioning of Fiber card ceberus panel Fiber Network card complete including programming and addressing of all connected sensors/MCP/sounder or any other device as per site requirement complete all as specified and as directed by Engr-in-charge. Make Siemens/ Honeywell/Cease Fire/EDWARD |
| 5 | Supply and fix Detectors Complying with and type certified to EN-45Addressable type multisensor detector with heat and smoke combination photoelectirc/optical with base with self built intelligence , the detector should have froup decision technology for faster responce & avoid false alarms, the detector shall have twin bi colour LED for 360 deg viewing addressing shall be with user friendly roatary decimal switches designed to meet UL 268 7th edition complete all as specified and as directed by Engr-in-charge. Make Siemens/Honeywell/ Cease Fire/EDWARD |
| 6 | M&L for taking out old smoke detector/addressable detector/multipupose sensor /response indicator/MCP of any type and capacity and cleaning the same with dust free cloth after cleaning refixing the same in its original location complete all as specified and as directed by Engr-in-charge.Note : Any unserviceable sensor/MCP will be replaced with new one and the same will be paid under respective items separately |
| 7 | M&L for taking out Analogue Addressable loop sounders/Hooter with control module of any type and capacity (Normal/Flame proof) and cleaning the same with dust free cloth after cleaning refixing the same in its original location complete all as specified and as directed by Engr-in-charge.Note : Any unserviceable sounder will be replaced with new one and the same will be paid under respective items separately |
| 8 | M&L for servicing/cleaning of Addressable self aligned motorized addressable Flame proof Beam detector (Set of Emitter & Receiver) complete all as specified and as directed by Engr-in-charge. |
| 9 | M&L for servicing/cleaning of Addressable self aligned motorized addressable Non Flame proof Beam detector (Set of Emitter & Receiver) complete all as specified and as directed by Engr-in-charge.Note for Item Ser No 6 to 9 (i) Rates included necessary T&P , rectification of faults any minor parts to make functional items as per site conditions. (ii) Any major parts shall be paid separately under respective items |
| 10 | Supply , installation , testing and fixing of 2.5 KM range siren with weather proof motor of suitable capacity with 220V 50Hz AC Supply operation with required power contactor , MPCB of control all in a weather proof enclosurenear motor complete all as specified and as directed by Engr -in-charge |
| 11 | Supply , installation testing and commissioning of sounder cum strobe rated at 80 dBA @ 3m for audible and 115 cd flashing at 1Hz for visual indicaiton UL listed complete all as specified and as directed by Engr -in-charge. Make: Notifier by Honeywell/ Cease Fire/EDWARD/Siemens |
| 12 | Supply, installation and commissioning and testing of Addressable manual call point - Resettable type-with back box with binary coded address setting with status LED for 360 visibilty- IP 50 Rating complete all as specified and as directed by Engr -in-charge. Model HMS-S of Siemens and any other equivalent inHoneywell /Cease Fire/EDWARD |
| 13 | Supply, installation and commissioning and testing of Flame Proof Pull type Addressable manual call point/station with addressable monitor modulewith status LED for 360 visibilty- IP 50 Rating complete all as specified and as directed by Engr -in-charge |
| 14 | Supply, installation , testing and commissioning of addressable control module for sounder/strobes/sounder cum strobs . The control module shall provide supervised NAC output rated 24V DC 2A. The device shall have an LED whick blink in normal state and get steady on activation to monitor the health status of the device. Addressing shall be withuser friendly rotary decimal switches, moduler shall be supplied with mounting plate from IEM for ease of installation and maintenancecomplete all as specified and as directed by Engr -in-charge. Make Siemens / honeywell/Cease Fire/EDWARD |
| 15 | Supply, installation, testing and commissioning UPS of cap 1000 VA suitable for backup for FACP including taking down old UPS complete all as specified and as directed by Engr -in-charge.Make : Scheinder/EATON/Siemens |
| 16 | Supply and replacement of UPS battery of capacity 42 Ah complete all as specified and directed by Engr-in-charge.Make:- Amron/Exide / Stargold. |
| 17 | Supply laying in repair of LT Cable with end termination for 1.5 sqmm x 4 core copper conductor armoured cables for 1100 V grade including cost of crimping lugs and single compression glands cable sockets, insulating tape etc complete all as specified and as directed by Engr -in-charge |