| 1 | Part A -CCTV Surveillance system and Comprehensive annual maintenance alongwith allied accessories |
| 2 | S/I/T/C of 2MP varifocal lens Bullet IP Camera with following specifications:-Image Sensor: 1/2.8 2MP CMOS or better**Minimum Illumination: 0.1 lux color, 0 lux with IR or better **Shutter Speed:1/3 – 1/100,000 sFrame Rate:25 fps or better **Lens: 2.8 to 12mm Varifocal lensVideo Compression: H.265 or better **S/N Ratio: >45dBResolution: (1920x1080) or better **Protocol: should comply to IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNS, IEEE802.1XIR Range: Minimum 20mOperating Temperature: -20 to 55 deg CentWeatherproof Standard:IP66 or better **Safety standard: UL |
| 3 | S/I/T/C of 8 channel NVR with the following specifications:Camera resolution:upto 8MPInterface: 1 HDMI, 1VGA minimumCompression :H.265or better**Network Throughput :160Mbps or better**USB Port: 2 USB port (USB2.0)minimumHard disk interface: 2 SATA port suitable for 6TB eachProtocol: IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNSOperating temp: -10 to 55 deg CentSafety standard: UL |
| 4 | SITC of 6 TB surveillance HDD |
| 5 | SITC of 8 port Giga PoE switch, 8(PoE 10/100) + 2(10/100) port long distance switch |
| 6 | Supply Installation testing Commissioning of following rack capacity with glass front door, steel rear door, power supply, MCB, cable manager, drawer shelves and wiring channels to accommodate CCTV systems equipment and complete with accessories as reqd. 8 U |
| 7 | S/I/T/C ofLED Monitor full HD LED Monitor,32 inches complying with the following specifications:Resolution : Full HD : 1920 x 1080 or betterBacklight : LEDBrightness : 400 NITS min. Video I/P port a) Min. 02 Nos HDMI 1920x1080. b) Min 01 No VGAContrast : 1200 : 1 or betterPower supply : 230v + / - 10%, 50 HzInstallation at sitewith connections andalong with all accessories of 42 INCHESetc.complete as required. |
| 8 | SITC of IP 65 box (without PoE Switches) of dimention 310 mm X 160 mmX 140 mm on pole or wall with suitable arrangement for support/ installation of 8 port Giga PoE switch and 1 nos 15/16 amp modular switch socket set. |
| 9 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable |
| 10 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 2 run of cable |
| 11 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 3 run of cable |
| 12 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 2 x 2.5 sq. mm. |
| 13 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm |
| 14 | Supply Installation testing and Commissioning ofPigtails 1 meter with Splicing and testing. |
| 15 | Conprehensive Annual Maintenace of CCTV System (A1)Comprehensive Annual Maintainance Contract of whole above system (CCTV System) for another five years after completion of 1 year warranty or defect liability period. |
| 16 | (a) 2nd year @5% of Estimated cost (Part-A) |
| 17 | (b) 3rd year @6% of Estimated cost (Part-A) |
| 18 | (c ) 4th year @7% of Estimated cost (Part-A) |
| 19 | (d) 5th year @8% of Estimated cost (Part-A) |
| 20 | Part-B Air Conditioners and Comprehensive Annual Maintenace alongwith allied accessories |
| 21 | Supply , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). 1.5 TR with 5 Star BEE Rating |
| 22 | S/I/T/C of stand for split AC |
| 23 | S/I/T/C of copper pipe for split AC |
| 24 | S/I/T/C of Drain Pipe |
| 25 | S/I/T/C of 3 Core, 4 Sqmm. Electrical wire for Air Conditioner |
| 26 | S/I/T/C of 5 KVA Voltage Stabilizer having input voltage 150V-270V and output voltage 195-245V |
| 27 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A \"C\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 28 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required a ) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 29 | Comprehensive Annual Maintenance contract for Split type AC of 1.5 ton for one year i.e. repair of PCB compressor/defective part i/e cooling coil/discharge coil/running capacitor/blower/fan blade/filter/gas refiling/as per requirement complete as required including material and servicing for proper functioning of air conditioner. |
| 30 | Part-C Electrical Works |
| 31 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 32 | Supplying and fixing suitable size GI box with modular plate andcover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 33 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2x2.5 sq.mm+1x2.5 sq.mm earth wire |
| 34 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.4x2.5 sq.mm + 2x2.5 sq.mm earth wire |
| 35 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2x4sq.mm+1x4 sq.mm earth wire |
| 36 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3x2.5 sq.mm |
| 37 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3x4sq.mm |
| 38 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 6x6sq.mm |
| 39 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way Double door |
| 40 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Singlepole |
| 41 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole |
| 42 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps |
| 43 | Providing and fixing following rating and breaking capacityand pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 150A, 16KA,TPMCCB |
| 44 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep |
| 45 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 46 | SITC of wall mounted fan 400mm sweep rated voltage 220-230 AC rated frequency 50HZ speed 1280-1350 RPM with desired color |
| 47 | Supply, Installation, Testing and Commissioning ofceiling fan with Brush LessDirectCurrent (BLDC)Motor,classofinsulation:B, 3 nos.metal(Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based)for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019fan Supply, earthing etc. complete as req a)1200mm,service value≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 48 | Supply of 250 mm (10 inch) sweep 1250 rpm exhaust fan Fresh Air Type complete with shutter blades etc. as required. |
| 49 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body materialand construction as per IS : 10322 withdriver (Replaceable)as per the requirement with Driver efficiency >85% ,Operating voltage AC140-270 Volt,freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20,CRI>80, Flicker free, (flickershould be below 5 %), life time (LED,Driver & electrical circuitary), ofminimum 50000BurningHourswith,70%ofinitial Lumenmaintained tilllife ends, CCT3000°K/ 4000°K / 5700°K/6000°K/6500°K(AsperANSIBin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BISstandard andtrade markcertificate(T.C.).Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. completeinallrespecti/cconnectionswith1.5sqmmFRLS,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy≥105 <120lm/Watt output . LM79 & LM80 Test reportfromNABLlab foralltestingrequiredforLED fixtures asper BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement:heatsinkofaluminumhousing such that LED junction temperature shall not rise above 90°C). Powdercoated die cast/ Extrudedaluminium Body (Thickness≥ 1.20 mm). 18-22 Watt |
| 50 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required |
| 51 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 52 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required . |
| 53 | P&F following sizes of PVC insulated & PVC sheathed copper conductor 3 core submersible cable confirming to IS.694/1990 etc. as reqd.3x2.5 Sq.mm. |
| 54 | Supplying and fixing of full stainless steel body self contained drinking water cooler with cooling capacity 150 ltr/ hr, storage capacity 150 ltr and suitable for 230V supply as required. |
| 55 | Supplying andInstallation of Reverse Osmosis (RO) water purifier of capacity 50 ltr/hr complete as required. |
| 56 | Comprehensive AMC of stainless steel body self-contained drinking water cooler with cooling capacity 150ltr per hr, storage capacity 150 ltr and suitable for 230V supply as required for one year i.e. repair of compressor defective part including condenser coil / condenser motor/ discharge coil/running capacitor/Thermostat switch/Float valve/ Motor capacitor/ Condenser fan blade/ gas charging/ as per requirement complete as required including material and servicing for proper functioning of water cooler. |
| 57 | Comprehensive AMC of wall mounted Reverse Osmosis (RO) plus UV plus UF water purifier with upto50 ltr/hr purification capacity and storage tank upto 9 litres capacity for one year with replacement of defective parts including Carbon candle/ RO membrane/ span filter or solenoid valve/ CTO/SMPS/ UV tube/ choke/RO pump/ circuit board etc. |
| 58 | Supplying, installation, Testing & Commissioning of following capacity at full load(Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS) system suitable for Single Phase input, Single Phase output AC Supply. The UPS shallinclude a Rectifier, inverter, battery bank suitable for 30 minutes back up(Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container)and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. The UPS systems shall beMicroprocessor based Digital Control,using Insulated Gate Bipolar Transistor (IGBT)\"s both for the rectifier & inverter with PWM (Pulse Width Modulation) Technology. The quality of design, manufacturingand inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE.The operating efficiency of the UPS systems shall be >95% at 100%non-linear loads. Current total harmonic distortion (ITHD)/ total demand distortion (TDD) on the input gridshall be< 5% at 100 %load. (The required LCfilters shall be included in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ) however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall besuitable for incoming supplyAC single phase 160-270V 50 Hzand delivering output ACsupply true sine wavesingle phase 220/230/240 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins and 150% for 1 minute. Operating temperature0 to 40 deg C, Relative humidity 0-95% non condensing, noise level less than 60db at 1 meter distance, Protection for Under voltage, over voltage, abnormal output voltage, battery over charging, output over current, short circuit, battery deep discharge , 10 KV surge. Displayfor watt/VA,Amp and Voltage power parametersetc. UPS shall comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2,it shall be a Voltage and Frequency Independent (VFI) type UPS (as per standard IEC 62040-1, 2 & 3) . The UPS should be withIGBT Based Inverter Technology, Communication RS232/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge. Required battery racks, DC breaker of suitable rating and interconnecting copper conductorcable of suitable size and connectors and all required accoseries are inclusive in the cost. The UPSshould have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc . 6 KVA |
| 59 | SITC of metal clad, powder coated, compartmentalized cubical panel board as per CPWD electrical specifications including insulated aluminum bus bars, supports, interconnection, erection of switchgears with depth 30 cm to 60 cm and making provisions for termination of incoming/ outgoing cables/ bus ducting and making foundation etc as required. (Suitable for 400 Amp TP & N) |
| 60 | P/FHot press sheet mouldedcompound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof polebox of innerdimension 300x200x105mm (NS) and outer dimension of 333X233X150 mm high dome complete with suitable arrangement for fixing of 4 nosof 6 to 32 amp single pole MCB & 63 Amp. Doublepole isolator (MCB/Isolator excluded) withneutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plateofsuitable size with danger monogram property printed on the coveretc asreqd. |
| 61 | Supplying, installation, Testing & Commissioning of Flood Light,powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >80 , under voltage and over voltageprotection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg120deg as per the application and the project requirement deg, suitable tilt able fitting, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete inall respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 100 Watt. |
| 62 | Supply of 12\" (300mm) sweep 1400 rpm exhaust fan heavy duty complete with shutters, blades etc as reqd. |
| 63 | SITC of single/ three phase monoblock pump set complete with all accessories workable on 240/415 volts, 50 Hz ac supply (a) 1 HP (0.75 KW) single phase pump set, head from 12-30 metre suction and delivery 25×25 mm. |
| 64 | Supply and Fixing of 4.5 kg DCP with C02 gas cartridge fire extinguisher ( Confirming to IS:2171 with cylinder fully charged). |
| 65 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C |
| 66 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1 KV grade conforming to IS-7098 of size 4 core 10 sqmm |
| 67 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1 KV grade conforming to IS-7098 of size 2 core 10 sqmm |
| 68 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm |
| 69 | Part-D Tubewell/Submersible Work |
| 70 | Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of borewell housing/casing pipe, removable as per requirement all complete for borewell of 200 mm dia |
| 71 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level, 1:3:6 (1 Cement: 3 coarse sand (zone-III) drived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources. |
| 72 | Supply, installation, testing and commissioning of cubical type controlpanel board for single phase and three phase submersible pumping set of following rating complete with contactor, relayMCB , condensor, voltmeter,ammmeter and indication lamp etc including connection etc. as reqd. (a) 5.0 HP, Three phase |
| 73 | Supply, lowering, testing and commissioning of vertical type, multistage, totaly enclosed water filled deep well submersible pumping set complete i/c connection etc as required (a) Three phase 5 HP having discharge of 300 LPM approx at 39 m head. |
| 74 | Development of tubewell with suitable capacity of air compressor i/c lowering the necessary induction pipe or line i/c cost of fuel, hire charges of compressor etc as required. The development shall be considered complete when Gravel stops sinking. Discharged ceased to improve and sand contents are not more than 10 PPM after 20 minutes of starting the pump complete as required. |
| 75 | P & F following size of PVC insulated and PVC sheated copper conductor 3 core submersibble cable confirming to IS 694/1990 etc as required 3 x10 SQ MM |
| 76 | Supplying and fixing following sizes of insulated steel flexible safety rope for holding submersibble pumpset i/c clips etc complete as required.6 mm |
| 77 | Supply,lowering and fixing following size of GI pipe (M-class) i/c cutting threading on both sides etc ISI marked etc as required (a) 40 mm dia |
| 78 | S &F following size of GI elbow as required,40 mm dia |
| 79 | S &F following size of GI socket as required,40 mm dia |
| 80 | S & F following size of GI union as reqd. 40 mm |