| 1 | Excavation over area for depth n.exc 1.5m deep and getting out in any kind of soil complete all as specified and directed. |
| 2 | Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth or n exc 10 Sqm on plan and n exc 1.5 m in depth & getting out, for layingunderground cable in soft/losse soil complete all as specified and directed. |
| 3 | Excavation over area for each additional 1.5m or part thereof in depth beyond the first 1.5 m for footing and getting out in hard/ dense soil complete all as specified and directed. |
| 4 | M&L Test point terminal block made ofPhosphorous bronze size 75 x 75 x 25 mm drilled & screwed incl 3 Nos, 8mm dia, 25mm long Hexagonal head Screw complete all as specified and as directed . |
| 5 | Supplyingand laying/fixing GI tubing light grade 40 mm dia for encasingstrip for mechanical proctection, laid under Plinth / Floors/ Paths Culverts or fixed on wall or concealed in wall/floor or as mounting bracket bend to shapewith complete accessories such as bends/sockets/reducers/saddlesincl necessary threading/drilling works all as specified and directed. |
| 6 | Returning and fillingincluding spreading, levelling, watering and well ramming in layers not exc 25 cm thick in any type of soil complete all as specified and as directed. |
| 7 | Removing surplus hard soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 meter above the starting point complete all as specified and as directed. |
| 8 | Material & Labour for point wiring with three layer PVC Insulated 1.5 Sqmm multi-strand copper conductor FRLSH cable 1100 Volts grade drawn into in stove enamelled steel conduit conduits including all fitting and fixing accessories( bend, tee, junction box etc)on surface/concealed conduit of size 20mm heavy duty ISI marked , fire proof steel terminal sunken boxes for One light/ Fan Point controlled by one switch including 1.5 sqmm copper conductor cable FRLSH connected to common earth dolly complete all as specified and as directed . |
| 9 | Supply and FixingLED flameproof light1X16/20 Watt, 4\" long with die cast alluminium housing with heat resistance toughten glasswith LED tube lightfixture driver, holder, connector etc prewiredincluding connecting up with 3 corecopper cable in steel flexible pipe complete all as specified and directed. |
| 10 | S&F flame proof / weather proof Exhaust fan 12\" single phasewith louverscomplete all as specified and as directed. |
| 11 | S&Fflame proof / weather proof LED Bulkhead light fitting complete with 10 watt LED and making necessary electric connection to ceiling rose with copper condutor of suitable size & length complete all as specified and directed. |
| 12 | S&Fflame proof switch rotary type with termination box in LM 6,16 Amp , Single pole ON-OFF, 240 Volt Complete all as specified and as directed. |
| 13 | S&Fflame proof/ WP enclosure for control panel / Distribution panel Incoming 63 Amps ,240 Volt , out going terminal chamber Out Going MCB 63 Amp DP-01 No , 10Amp SP-04 Nos , 32 Amp SP-04Nos, 40 Amp SP-04 NosComplete all as specified and as directed . |
| 14 | S&Fflame proof / weather proof LED Floodlight fitting 60Wattcomplete all as specified and as directed. |
| 15 | Supply and fix Air termination , single pointed aluminium rod 12 mm dia and 300 mm long complete all as specified and directed. |
| 16 | Material and labour for 25 mm Bore galvanised steel tubes of following sizes , medium grade, ISI marked, with all fittings and fixtures such as bends, tees, elbows, reducers, unions, plugs and sockets etc., and laid in trenches complete all as specified and directed. |
| 17 | Material and labour for 20 mm Bore galvanised steel tubes of following sizes , medium grade, ISI marked, with all fittings and fixtures such as bends, tees, elbows, reducers, unions, plugs and sockets etc., and laid in trenches complete all as specified and directed. |
| 18 | Material and labour for 15 mm Bore galvanised steel tubes of following sizes , medium grade, ISI marked, with all fittings and fixtures such as bends, tees, elbows, reducers, unions, plugs and sockets etc., and laid in trenches complete all as specified and directed. |
| 19 | Supply and fix 25 mm Bore Gun-metal, globe or gate valves, with iron wheel head, screwed both endsfor iron pipe and fixed conforming to IS 9338 complete all as specified and directed. |
| 20 | Supply and fix 15 mm Bore Gun-metal, globe or gate valves, with iron wheel head, screwed both endsfor iron pipe and fixed conforming to IS 9338 complete all as specified and directed. |
| 21 | Supply, laying, testing and commissioning cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, elecric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 70 Sqmm3.5 core complete all as specified and directed.Note:-(i) Cable may be laid in trenches, under road, across the Nallah, along poles/walls and ducts etc.(ii) Excavation, earthwork, sand cushioning, cable cover, pipe for cable protection to be measured and paid separately. |
| 22 | Supply and fix in replacement ofAluminium strip 25X3.15 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as specified and as directed . |
| 23 | S & F for 9 kg capacity dry chemical powder (ABC) type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket / floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed |
| 24 | S & F for Galvanized mild steel Fire bucket (Filled with dry sand & water) conforming to IS 2546: 1974 round bottom type enamel painted, white inside & Red out side and Letter \"FIRE\" in black out side and handle with mounting bracket complete as specified and directed |
| 25 | S & F for Galvanized mild steel Fire hook bracket with 3 mtr bamboo handle painted with red colourcomplete as specified and directed. |
| 26 | S & F Galvanized mild steel Fire breater bracket with 3 mtr bamboo handle painted with red colourcomplete as specified and directed |
| 27 | M & L for Fire point construted with angle iron frame mounted on PCC platform with PCC (1:3:6) and covered with GI Sheet painted with red colour and letter \"FIRE\" in top of shed complete as specified and directed. |
| 28 | & F Galvanized mild steel Fire Shovels hand tooldulypainted with red colourcomplete as specified and directed. |
| 29 | S & F Galvanized mild steel Firepickshand tool painted with red colourcomplete as specified and directed. |
| 30 | M & L for earthing with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm buried directly in ground ( earth pit not less than 2.25 m deep below normal ground level), with top edge of the plate vertically to depth of not less than 1.5 m below normal ground level connected to and incl GI strip 25x4 mm and GI pipe 40 mm dia light grade for protection to the extent of 7.5 m as earthing lead by means of GI bolts and nuts etc connecting to equipment with provn of charcoal and salt etc all as per electrical plate No 3 of SSR Pt-I incl PCC cover and , watering arrangement with GI pipe 20 mm dia and MS funnel, concrete pit incl excavation and earth work in any type of soil and testing on completion etc complete all as specified and directed.( Note : PCC chamber shall be constructed at least 1.5m away from earth pit pipe for watering shall be provided in slanting manner.) |
| 31 | Surface dressing n exc 15 cm deep and getting out in any kind of soil complete all as specified and directed. |
| 32 | Excavating in trenches, n.exc 1.5m wide and n exc 1.5m in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n.exc 10sq m on plan and n.exc 1.5m in depth and getting out in Hard/dense soil complete all as specified and directed. |
| 33 | M&L for 100 mm thick PCC (1:4:8), type D2as in foundations, filling and mass concrete using 40 mm graded stone aggregate complete all as specified and directed. |
| 34 | M&L Pre-cast cement concrete (1:3:6) type C-1 (using 20mm graded stone aggregate) block masonry with solid blocks, exc. 10 cm in width and setting in Cement mortar 1:6, complete all as specified and directed. |
| 35 | M&L reinforced cement concrete M-25 (Design mix) using 20mm graded stone aggregate in foundations including rafts, footings, foundation beams, plinth beams, bases for columns, under reamed piles and mass concrete complete all as specified and directed. |
| 36 | M&L reinforced cement concrete M-25 (Design mix) using 20mm graded stone aggregate in columns, pillars, piers, posts, struts and the like complete all as specified and directed. |
| 37 | M&L reinforced cement concrete M-25 grade (Design mix) using 20mm graded stone aggregatein Beams, lintels upto 1.5m clear span,chajjas seismic and other similar bands, lintel bands,roof bands and the like complete all as specified and directed. |
| 38 | M&L RCC M-25 (Design mix) in slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the like complete all as specified and directed. |
| 39 | M&L for use and waste of rough finish formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams and similar work, vertical or to batter for rough finished flat surfaces of concrete complete all as specified and directed |
| 40 | M&L for use and waste of rough finish formwork to sides of pillars, posts, struts, piers, columns and stanchions, square, rectangular or polygonal for rough finished flat surfaces of concrete complete all as specified and directed. |
| 41 | M&L for use and waste of rough finishformwork to sides and soffits of floor or roof beams, beam haunching, girders, bressummers, lintels, cantilevers, shelves including supports, overhangs, etc. also splays between floors and beams, etc. for fair finished flat surfaces of concrete complete all as specified and directed. |
| 42 | M&L for use and waste offormwork to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work, not exc 200mm thick (Horizontal or sloping) for fair finished flat surfaces of concrete complete all as specified and directed. |
| 43 | Formwork to edges of concrete flats, treads, breaks in floors, window cills, concrete railings, openings in concrete walls, floor and roofs n exc 20 cm wide and sides of RCC/PCC bands in walls, horizontal or sloping and similar work exc 10cm but n.exc 20cm wide for rough finished surfaces complete all as specified and directed. |
| 44 | M&L Mild steel bars TMT 10mmdia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed. |
| 45 | All as per item No 44 here-in before but 5mm dia and over upto and including 10mm dia in stirrups, spacers and binders complete all as specified and directed. |
| 46 | M&L rendering 10mm thick in cement mortar 1:6 on fair faces of brick/block masonary or on concrrete surfaces in CM 1:6, finished even & smooth without using extra cement complete all as specified. |
| 47 | M&L rendering 5mm thick on ceiling surfaces in CM 1:3 finished even and smooth without using extra cement complete all as specified and directed. |
| 48 | M&L rendering 15mm thick surface other than fair faces of brick/block masonry work or concrete surface in two layers (5mm thick CM 1:4 over 10mm in CM 1:6) finished even and smooth without using extra cement mixed with water proofing compound @ 3% of cement on top layers complete all as specified and directed. (Note WPC measured and paid separately.) |
| 49 | M&L rendering 10mm thick on concrete surface over the roof in CM 1:4, finished even and smooth without using extra cement mixed with water proofing compound @ 3% of cement complete all as specified and directed.(Note WPC measured and paid separately.) |
| 50 | Supply only Integral water proofing compound compete all as specified and directed. |
| 51 | M&L for cement plastered surfaces with one coat of cold applied bituminous primer @ 0.40 ltr/Sqm conforming to IS-33894 and laying APP based polymeric membrane not less than 3mm thick, weighing not less than 3.5kg/sqm, reinforced with polyester non woven fabric (weighing not less than 150gms/sqm) and upper side of the membrane thermally insulated with white mineral gravel, uniformly embedded during manufacturing process shall only be used.It shall be laid by torch application.Side over laps shall be 75mm and the end lap shall be 100mm and all over laps and joints shall be sealed by torch application.For parapets, membrane shall be taken to a height of minimum 60cm and then inserted inside the parapet groove.This shall be finished by a membrane flashing complete all as specified and directed. |
| 52 | M&L for Framed work of Fe-290 (Gde E165) as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing complete all as specified and directed. |
| 53 | S&F steel door including projecting type hinges, steel handle, complete with glazing bars, dovetailed or welded complete all as specified and directed. |
| 54 | M&L preparation of newsteel surfaces of any description over exc 10cm in width or girth and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. |
| 55 | Earth filling under floors including spreading, leveling, watering and well ramming in layers not exc 25 cm thick complete all as specified and directed. |
| 56 | M&L for hardcore of broken stone or boulders, gauge not exc. 63mm, deposited, spread and leveled in layers not exc 15 cm thick, watered and rammed to a true surface complete all as specified and directed. |
| 57 | M&L for 100 mm thick cement conrete1:4:8 type D2 (using 40mm grade stone aggregate)as in sub base of floorscomplete all as specified and directed. |
| 58 | M&L for 55 mm thick PCC 1:2:4 type B0 as in floor finishes complete all as specified and directed. |
| 59 | M&L for 75 mm thick, plain cement concrete 1:3:6, type C-1 (using 20mm graded stone aggregates) as in plinth protection finished even and smooth w/o using extra cement with joints 10mm wide and in full depth at corners and @ 3. m c/c filled with mastic mortar complete all as specified and directed. |
| 60 | M&L for preparing on newly plastered wall surfaces andapplying two coats of cement base paint of 1st grade quality white or tinted in one ormore tints and pattern (camouflage) asapproved,over a coat of primer complete all as sepcified and directed. |
| 61 | M&L for preparing newly plastered surfaces and applying three coats of white wash as in ceiling etc complete all as sepcified and directed. |
| 62 | M&L for preparing newly plastered surfaces and applying three coats of white wash as on walls etc complete all as sepcified and directed. |
| 63 | M&L for Anti Termite Treatment the bottom and sides of excavation at the rate of 5 litres of emulsion per square metre of surface area complete all as sepcified and directed. |
| 64 | M&L for Anti Termite Treatment the backfill in contact with foundation at the rate of 7.5 litres of emulsion per square metre of vertical surface (Area of the sub structure in contact with backfill to be measured) complete all as sepcified and directed. |
| 65 | M&L for Anti Termite Treatment the top surface of filled earth at the rate of 5 litres of emulsion per square metre of surfacecomplete all as sepcified and directed. |
| 66 | M&L for Anti Termite Treatment the soil under plinth protection at the rate of 5 litres of emulsion per square metre of surface area complete all as sepcified and directed. |
| 67 | Demolition of Cement Concrete (Unreinforced) of any description and in any position not otherwise specifically provided forcomplete all as specified and directed. |
| 68 | M&L cement concrete in foundations, fillings and mass concrete 1:2:4 type B-2 using 40 mm graded stone aggregates complete all as specified and directed. |
| 69 | S&F steel work in tubular trusses including special shaped washer etc. Complete using ERW or induction butt welded tubes conferming to IS 1161-1979 grade St -240 complete all as specified and directed. |
| 70 | M & L for Preparation of newly steel surface any descriptionexc 10cm in width or girthand applying two coat of synthetic enamal paint over a coat ofred oxide primer completeall as specified and directed. |
| 71 | S&F for pre painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50 mm thick Sandy colour having tensile strength of 550 Mpa as in roof covering / cladding to wall /Eaves, fixed with self tapping screws as specified and as per manufacturer specification. |
| 72 | Surface excavation n exc 30 cm deep and averaging 15 cm deep and getting out soft/loose soil complete all as specified and directed. |
| 73 | M & L for Sand filling under floors 25 to 30mm thick layer of sand cushioningcomplete all as specified and directed. |
| 74 | M & L for 80mm thick machine pressed precast interlocking paving blocks factory casted using grey cement and pigment, casted in an automatic plant working on vibration and simultaneous hydraulic compression from top, confirming to IS-15658-2006 and of shape haxagon/ triangular/ zigzag/ I-shaped etc. as directed having compressive strength not less than (M-40 Grade) etc complete all as specified and directed. |
| 75 | S&FLT feeder pillar box factor made cubical type dust proof, out door type both side opening of size 100 x 80 x 40 cm of MS sheet 3 mm thick power coated machine pressed front opening with rubber gasket / bedding , locking arrangement with sliding bolt including aluminium bus bar of400 amps 4 strips mounted on insulators each strip should be munted minimum two insulator and nut bolt panel shall be mounted on angle iron frame and legs made from angle iron of suitable size duly spray painted internally and externally with two coat of synthetic enamel paint over a coat of red oxide primer grouted in PCC 1:2:4 type ‘B’ ( using 20 mm graded stone aggregate complete incoming / outgoing cable provision. with controling Incoming MCCB 100 Amps - 01 Nosand OutGoing MCCB -01 Nos complete all as specified and as directed. |
| 76 | Supply, laying, testing and commissioning cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, elecric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 25 Sqmm3.5 core complete all as specified and directed.Note:-(i) Cable may be laid in trenches, under road, across the Nallah, along poles/walls and ducts etc.(ii) Excavation, earthwork, sand cushioning, cable cover, pipe for cable protection to be measured and paid separately. |
| 77 | M&L for dry tibba sand in trenchesfor cushioning to under ground cable spreading, levelling, hand punning complete all as specified and directed.Note- Punned down thickness will be measured for payment purpose. |
| 78 | Supplying and laying un-reinforced precast concrete cable cover, Class LV, Type I, flat, size 250mm x 150mm x 40mm, laid by dry and abutting each other with gap between adjacent slab not exedding 10 mm over under ground cable for protectioncomplete all as specified and directed. |
| 79 | Material & labour for Providing, cement concrete (1:2:4) type B0 using 12.5mm graded stone aggregate for pole base foundation and copingcomplete all as specified and directed. |
| 80 | Material and labour for 40mm graded stone aggregate for spreadng/ loose filling under four pole structure, E/M installation and other placescomplete all as specified and directed. |