| 1 | Supplying of PVC/XLPE armoured cable with aluminium conductor 1.1 KV Gradeconfirming to IS 7098 (part I)1988 with upto date amendments of the following size at the site of work. |
| 2 | 3 X 10 Sqmm |
| 3 | Laying and fixing of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 4 | Upto 35 Sq. mm (Clamped with 1mm thick saddle) |
| 5 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. |
| 6 | upto 35 Sq.mm |
| 7 | Supplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required |
| 8 | Supplying and fixing following way, single pole andneutral, sheet steel, MCB distribution board, 240 V,on surface/ recess, complete with tinned copper busbar, neutral bus bar, earth bar, din bar,interconnections, powder painted including earthingetc. as required. (But without MCB/RCCB/Isolator) |
| 9 | 8 way , Double door |
| 10 | 12 way, Double door |
| 11 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 12 | Single pole |
| 13 | Single neutralpole |
| 14 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 15 | Group C |
| 16 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 17 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 18 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 19 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 20 | 5/6 A switch |
| 21 | 3 pin 5/6 A socket outlet |
| 22 | 15/16 A switch |
| 23 | 6 pin 15/16 A socket outlet |
| 24 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 25 | Supplying and fixing of following size/modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required |
| 26 | 2 Module (75mmX75mm) |
| 27 | 3 Module (100mmX75mm) |
| 28 | 4 Module (125mmX75mm) |
| 29 | 8 Module (125mmX125mm) |
| 30 | Supplying and fixing 30 A,415V, TPN Industrial type socket outlet with 4 pole and earth, metal enclosed plug top alongwith 30 A \"C\" curve, TP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc, as required. |
| 31 | Supplying and fixing 20 A, 240V, SPN Industrial type socket outlet with 2 pole and earth, metal enclosed plug top alongwith 20 A \"C\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc, as required. |
| 32 | LED Batten light (System lumen efficacy ≥120 <135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range-5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P.F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till lifeends, CCT 3000°K / 4000°K / 5700°K /6500°K(As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 33 | 18-22 W |
| 34 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥120 <135 lm/Watt) Supplying,installation, Testing & Commissioningof Street light LED fixture powder coatedpressure die cast aluminium body with driver asper the requirement with Driver efficiency >85%,Input voltage: 140-270 Volt AC, frequency 50/60 hz,Operating temp range -5 0C to 50 0C, internal surgeprotection of 5 KV L,N,E as per IEC 61000-4-5,Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70,under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement: heat sink of aluminium housingsuch that LED junction temperature shall not riseabove 90°C). |
| 35 | 72W |
| 36 | Supplying , installation, testing and commissioning of 35 Watt LED 5700K Post top Lanthern made up of pressure die cast aluminium housing of new generation, energy saving, environmental friendly, long life astheticatly design symmetrical light distribution spun aluminium landscape luminaire with high power LEDs as light source with IP 65,IK 07, avg life- 50000 hours with lumen efficacy of >140 lm/W, System efficacy of > 70 lm/W,colour temp 5700 K,THD( %) < 10 and fixing on pole with suitable clamps and nut bolts including giving connection testing etcat site of required (ISI Certified) |
| 37 | Supplying, installation, testing, and commissioning of 9 watt LED BULB with efficacy min of 100 lumens/Wand Colour Temperature- 6500K along with holder etc at the site of work |
| 38 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value 63(CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperaturerise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 39 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 40 | Supplying and fixing loop in loop out boxes (PVC Sintex Box) of size 140mmx140mmx95mm with PVC enclosure 1 Nos, 2/4 way strip connector including testing as required. |
| 41 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. [ 3 X 10 sq. mm (22mm)] |
| 42 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having lockingarrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 43 | Providing and fixing 25 mm X 5 mm GI strip on surface or in recess for connections etc. as required |
| 44 | Supplying and laying 25 mm X 5 mm GI strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 45 | Supplying and drawing of 1.5 Sq.mm,three core PVC insulated and FR PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volts, conforming to IS: 694 in the existing surface/ recessed steel/ PVC conduit as required. |
| 46 | Supply and Laying of Rubber mats of 1.1 KV grade and size 2 Mtrs x 1 mts x 6 mm ISI certified |
| 47 | Supply of 11 KV/22 KV Hand gloves |
| 48 | Supply and Fixing of Shock instruction chart in English / Hindi /Telugu duly framed with front glass. |
| 49 | Supply of First Aid box 18\" x 12\" x 8\" including accessories |
| 50 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 51 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
| 52 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
| 53 | Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV/LED street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required. |
| 54 | CREDIT ITEMS |
| 55 | Dismantled DBs, switch gears with its accessories |
| 56 | Dismantled obsolete Tubelight fittings/Street Lights/bulbs with its accessories etc., |
| 57 | Dismantled obsolete Fans with its accessories etc., |