| Sl. No. | Item Description |
| 1 | Bidder Please note that, quoted rate are inclusive of tranportation, labour, royalties taxes etc. except GST. GST will be paid as Govt of India, rules and regulation. |
| 2 | Supplying LT cable having Aluminium conductor XLPE insulated sheathed,galvanised steel tape armoured cable with pvc outer sheathing 1.1 KV ( Confirming to IS 7098 Part-II amended upto date as per the following sizes). Including the cost of all materials, lobour, Handling of materials of equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge.3.5 Core x 25 Sqmm Armoured Aluminium (A2XFY)Cable. |
| 3 | Supplying LT cable having copper conductor XLPE insulated sheathed,galvanised steel tape armoured cable with pvc outer sheathing 1.1 KV ( Confirming to IS 7098 Part-II amended upto date as per the following sizes). Including the cost of all materials, lobour, Handling of materials of equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. 4 Core x16 Sqmm Armoured CopperCable. |
| 4 | Supplying LT cable having copper conductor XLPE insulated sheathed,galvanised steel tape armoured cable with pvc outer sheathing 1.1 KV ( Confirming to IS 7098 Part-II amended upto date as per the following sizes). Including the cost of all materials, lobour, Handling of materials of equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. 4 Core x10 Sqmm Armoured CopperCable. |
| 5 | Supplying LT cable having copper conductor XLPE insulated sheathed,galvanised steel tape armoured cable with pvc outer sheathing 1.1 KV ( Confirming to IS 7098 Part-II amended upto date as per the following sizes). Including the cost of all materials, lobour, Handling of materials of equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. 4 Core X 4 sqmm copper armoured cable |
| 6 | Supplying LTcable having copper conductor XLPE insulated sheathed, galvanized steel tape unarmoured cablewith pvcouter sheathing1.1 KV class ( Conforming to IS 7098 Part-II amended upto date as per the followingsizes). Including the cost of all materials, lobour , Handling of materials of equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge.1 Core x 120 SqmmFRLS Heavy Duty unarmoured Copper (CuYY) Cable. |
| 7 | Supplying LTcable having copper conductor XLPE insulated sheathed, galvanized steel tape unarmoured cablewith pvcouter sheathing1.1 KV class ( Conforming to IS 7098 Part-II amended upto date as per the followingsizes). Including the cost of all materials, lobour , Handling of materials of equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge.1 Core x 70 SqmmFRLS Heavy Duty unarmoured Copper (CuYY) Cable. |
| 8 | Providing excavation and refilling of existing earthing pit GI / Copper with Charcoal 90 Kg , solt 10 kg each. Works includes cleaning of all GI/ Copper parts of earthing pit, replacement of connecting nutbolts with new SS nutbolts, replacement of water pipe GI having identical specifications with existing one, if required. Reconstruction of earthing chamber with 450 x 450 size CI cover. Earthing test report should be submitted by the agency as per format issued by IISER Pune. Before execution of work, prior approval from engineer in charge, IISER Pune is required. Work shall be executed as good workmenship. |
| 9 | Providing and fixing LD FRP chamber cover up to load carrying capacity of 2.5 T as per IS standards. Chmaber cover shall be along with frame. Quoted rate shall be removing existing chamber frame and cover and fixing new FRP chmaber cover and frame including necessry fixing arrangement etc., as complete. |
| 10 | Supply, installation, testing and commissioning of Chemical earthing using electrode of size 76 mm minimum diameter, minimum 03 meter longand connected with 50x5 mm copper internal strip, material of conustruction COPPER, complete with existing excavation / bore, civil work for chamber, cast iron cover size 450 x 450 mm, with backfill compound as requred to fill earth pit up to mark. the earth resistance shall be as per IS 3043( Approved make : Yash earthing / True Power / Fast Electrode / Maxwell Earthing ) |
| 11 | Providing boreing / drilling bore well of 150mm dia for casing / strainer pipe , by suitable method, including drilling in all strata, including hiring & running charges of all equipments, tools, plants and machinenaries required for the job, all complete as per direction of Engineer in charge. |
| 12 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE Copper conductor cable of 1.1 KV grade as required.4 X 10 sq. mm ( Approved make : Reachem / Mseal / 3M ) |
| 13 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE Copper conductor cable of 1.1 KV grade as required.4 X 16 sq. mm( Approved make : Reachem / Mseal / 3M ) |
| 14 | END TERMINATION: Supply and installation of End termination ofcables withcompression brass cable glands,Al crimping type lugs should be used for Al cables and Cu lugs withsoldering and ferrules for the following 1.1kv class Al./Cu. XLPE/PVC insulated using necessary crimping tool and all other accessories as required andIncluding the cost of all materials, lobour, Handling of Materialsof equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. 4 Core x 10 Sqmm Armoured Copper Cable. |
| 15 | END TERMINATION: Supply and installation of End termination ofcables withcompression brass cable glands,Al crimping type lugs should be used for Al cables and Cu lugs withsoldering and ferrules for the following 1.1kv class Al./Cu. XLPE/PVC insulated using necessary crimping tool and all other accessories as required andIncluding the cost of all materials, lobour, Handling of Materialsof equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. 4 Core x 16 Sqmm Armoured Copper Cable.( Approved make : Dowells / CI / Electrowerke ) |
| 16 | Supply of pedestal fan with 400 mm sweep, 50 W, oscillatioing movement, 3 step regulator, mounting arragement, hi flow air, 230 V AV, as complete.( Approved make : Crompton / Bajaj / Usha) |
| 17 | PVC RACEWAYS ( Along the wall) DLP U- PVC adaptable trunking: Supply & installation of surface mounted DLP U- PVC adaptable trunkingraceways, fabricated out of U-PVC to Off-White or approved shade as per IS 733 of thickness 2.0mm for the base and sides with removable covers, complete with necessary bends, suitable sized junction boxes, internal angle, external angle, flat 90 degree angle , end caps and tees,minor civil works if any etc, Complete. (For every 1mtr distance cable tag has to be provided for each circuit in the raceways - as more that 1C FRLS copper wire is required for 1 Circuit)PVC RACEWAYS ( Along the wall), DLP U- PVC adaptable trunking . Size: 105x 50mm PVC Raceways for Power & Data with above specifications105x 50mm PVC Raceways ( Approved make : MK Honeywell / Legrand ) |
| 18 | Supplying and fixing following size/ modules, PVC box alongwith modular base & cover plate for modular switches in recess etc. as required.4 module ( Approved make : MK Honeywell / Legrand ) |
| 19 | Supplying and fixing following size/ modules, PVC box alongwith modular base & cover plate for modular switches in recess etc. as required.6 module ( Approved make : MK Honeywell / Legrand ) |
| 20 | Supplying and fixing following size/ modules, PVC box alongwith modular base & cover plate for modular switches in recess etc. as required.8 module( Approved make : MK Honeywell / Legrand ) |
| 21 | Supply and fixing of surface mounted / wall mounted , 2 ft , 10 W LED light fitting, cool day light of based luminaire for surface mountingon ceilingwith module, luminaire complete with lamp and all accessories. Including the cost of all materials, labour, HOM of equivalentand machineries all leadlift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification & as directed by Engineer in charge.( Make Syska / Wipro / Philips / Bajaj / Crompton / Havells ) |
| 22 | Supplying fixing and wiring Current Operated RCBOs,240V/415V 50Hz with 10KA short circuit with standing capacity 25amps. double pole, 30/100mA, and Including the cost of all materials, lobour, HANDLING OF MATERIALSof equipment and machinery all lead lift, loading etc, complete.RCBO63 A,4P, 100 mA.( Approved make : MK Honeywell / Legrand / Schindler ) |
| 23 | Supplying fixing and wiring Current Operated RCBOs,240V/415V 50Hz with 10KA short circuit with standing capacity 25amps. double pole, 30/100mA, and Including the cost of all materials, lobour, HANDLING OF MATERIALSof equipment and machinery all lead lift, loading etc, complete.RCBO32/40 A4P, 100 mA ( Approved make : MK Honeywell / Legrand / Schindler ) |
| 24 | Supplying fixing and wiring Current Operated RCBOs,240V/415V 50Hz with 10KA short circuit with standing capacity 25amps. double pole, 30/100mA, and Including the cost of all materials, lobour, HANDLING OF MATERIALSof equipment and machinery all lead lift, loading etc, complete.RCBO32/40A,DP, 30mA( Approved make : MK Honeywell / Legrand / Schindler ) |
| 25 | Supply and fixing MCCB incomer box with 250 A MCCB 4P 50kA( Approved make : MK Honeywell / Legrand / Schindler ) |
| 26 | Splicing / Termination of Fiber Optic Cable Cores using Fusion splicing with pre-terminated LC pigtails, dressing and proper fixing in splice trays. Including Splicing Kit. |
| 27 | Supply, installation, testing and commissioning of 3KW water Heater 1.25\"\" BSP TP 18\"\" long . With required GI barrel pipe of up to 65 mm dia & 300 mm long having tapping etc as complete.( Approved Make : Hotmax / Bharat ) |
| 28 | Relaying of existing Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 4 sq. mm + 1 X 4 sq. mm earth wire. Measurement will be done on actual relaying of submain wiring. Removing, shifting, storageof cable / wires with all accessories is in scope of agency for this item. During removing of any item from site, nothing should be damaged in such manner to become unservisable. etc complete as per direction of Engineer In‐charge. Nothing extra shall be paid separately. |
| 29 | Relaying of existing Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 3 X 4 sq. mm + 2 X 4 sq. mm earth wire. Measurement will be done on actual relaying of submain wiring. Removing, shifting, storageof cable / wires with all accessories is in scope of agency for this item. During removing of any item from site, nothing should be damaged in such manner to become unservisable. |
| 30 | Refixing of existing 1 to 8 module faceplate & base plate on DLP PVC trunking. Measurement will be done on actual reinstallation of faceplates on DLP trunking. Removing, shifting, storage of faceplates are in scope of agency for this item. During removing of any item from site, nothing should be damaged in such mannerto become unserviable. etc complete as per direction of Engineer In‐charge. Nothing extra shall be paid separately. |
| 31 | Refixing of existing 1 to 8 module modular board on DLP PVC trunking. Measurement will be done on actual reinstallation of modular board on DLP trunking. Removing, shifting, storage of modular board are in scope of agency for this item. During removing of any item from site, nothing should be damaged in such mannerto become unserviable. etc complete as per direction of Engineer In‐charge. Nothing extra shall be paid separately. |
| 32 | Refixing of existingmodule switches ( 5 to 16 A ) on DLP PVC trunking. Measurement will be done on actual reinstallation of modular switches on DLP trunking. Removing, shifting, storage of modular switches are in scope of agency for this item. During removing of any item from site, nothing should be damaged in such mannerto become unserviable. Wiring required for connecting switches to sockets are in scope of agecy. etc complete as per direction of Engineer In‐charge. Nothing extra shall be paid separately. |
| 33 | Refixing of existingmodule sockets ( 5 to 16 A ) on DLP PVC trunking. Measurement will be done on actual reinstallation of modular sockets on DLP trunking. Removing, shifting, storage of modular sockets are in scope of agency for this item. During removing of any item from site, nothing should be damaged in such mannerto become unserviable. Wiring required for connecting switches to sockets are in scope of agecy. etc complete as per direction of Engineer In‐charge. Nothing extra shall be paid separately. |
| 34 | Relaying of existing UTP 4 pair CAT 6 LAN Cable in surface/ recessed medium class PVC conduit as required.UTP 4 pair CAT 6 LAN Cable. Measurement will be done on actual relaying of UTP 4 pair CAT 6 LAN Cable. Removing, shifting, storageof cable / wires with all accessories is in scope of agency for this item. During removing of any item from site, nothing should be damaged in such manner to become unservisable. etc complete as per direction of Engineer In‐charge. Nothing extra shall be paid separately. |
| 35 | Reinstallaion of existing 150x 50 mm DLP trucking on surface incluidind removing, shifting, storage of all accessories of DLP PVC trunking.Measurement will be done on actual reinstallation of DLP PVC trunking. Removing, shifting, storageof DLP PVC trunking with all accessories is in scope of agency for this item. During removing of any item from site, nothing should be damaged in such manner to become unservisable. etc complete as per direction of Engineer In‐charge. Nothing extra shall be paid separately. |
| 36 | Supply and installation ofjoints for PVC DLP trunking ( 105 / 150 mm x 50 mm Size Existing DLP PVC trunking ). Make Legrand / MK. |
| 37 | Supply and installation of Left or right End cap for PVC DLP trunking ( 105 / 150 mm x 50 mm Size DLP PVC trunking ). Make Legrand / MK. |
| 38 | Supply and installation of flat angle / L bend for PVC DLP trunking ( 105 / 150 mm x 50 mm Size ExistingDLP PVC trunking ). Make Legrand / MK. |
| 39 | Supply and installation of internal angle / corner for PVC DLP trunking ( 105 / 150 mm x 50 mm Size ExistingDLP PVC trunking ). Make Legrand / MK. |
| 40 | Supply and installation of External angle / corner for PVC DLP trunking ( 105 / 150 mm x 50 mm SizeExisting DLP PVC trunking ). Make Legrand / MK. |
| 41 | Removing, shifting, store of exisitng 2\"x2\" light fittings along with wires, mounting , screws etc as complete. All removed out material will be handedover to IISER Pune with invertary. During removing of any item from site, nothing should be damaged in such manner to become unservisable. etc complete as per direction of Engineer In‐charge. Nothing extra shall be paid separately. |
| 42 | Removing of exisiting armoured cable from surface/ cable tray. Shifting, store of cable in same campus is in scope of agency.During removing of any item from site, nothing should be damaged in such manner to become unservisable. etc complete as per direction of Engineer In‐charge. Nothing extra shall be paid separately. For DB cable / power cable / fume hood cables / fume hood communication cable / fire detector cable ( Upto 35 sqmm ) |
| 43 | Supply, installation, testing and commissioning of Start-Stop switching station having following specification. Specifications a ) Standard Start Push button with NO contact B) Standard Stop Push button with NC contact c) Emergency stop push button with Mashrrom head, self holding mechanism, Red top and yellow base, d ) PVC enclosure box with termination entry on each wall which is suitable for PVC / SS gland , Size of enclouser box 150 mm ( W ) x 100 mm ( H ) x 50 mm( D) minimum. , wall mounting / surface mounting. e ) all Switches, Push buttons and enclosure boxes should be clearly labeled as per site requirement and colour code for each should be followed. Approval for sample component , arragement, GA etc are required from IISER Pune authorities. |
| 44 | Supply of 6 core x 1.5sqmm , copper conductor, armoured cable, 1.1 KV grade, FRLS cable , Make Polycab / finolex / RR. ( For fume hood / fresh air system of OG starter feeder to Push button station ) |
| 45 | Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 6 Core x 1.5 Sqmm Armoured Copper Cable. |
| 46 | Removing of exisiting DLP trucking upto 100x50mmwith all accessories / switch / socket / cable / wires / Data cable etc.from surface/ wall / panel . Shifting, store of DLP PVC trunkingin same campus is in scope of agency.During removing of any item from site, nothing should be damaged in such manner to become unservisable. etc complete as per direction of Engineer In‐charge. Nothing extra shall be paid separately. |
| 47 | Core cutting in brickwork/RCC up to 300mm depth for 100 mm dia including cost packing of gap between pipe and with apropritae expoxy base filling etc complete and as per Direction of Engineer In-charge. |
| 48 | Core cutting in brickwork/RCC up to 300mm depth for 150 mm dia including cost packing of gap between pipe and with apropritae expoxy base filling etc complete and as per Direction of Engineer In-charge. |
| 49 | Supply, installation, testing and commissioning of thermostat 11\"\" long suitable for 3KW1.25\"\" BSP TP 18\"\" long water Heater in existing heater. ( Approved make : Hotmax / Bharat ) |
| 50 | Supplying and drawing of Flat Travelling cable 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable( Approved make : D link / Polycab / Legrand/ Channeltech) |
| 51 | Clean room light : Supply, Testing, commissioning and installation of Recessed Mounted 2\"X2\" LED Luminaire which is useful for cleanroom facility havingclass 100000 cleanroom. Installation should be done on existing metallic or other false ceiling with required accessories as complete. Specifications : IP66, dust free, LED, clean room bottom operating luminaire, Operating temperature 0 to 45 degree celcius, Operating voltage 140 to 270 V, Avg life 50000 hours, high performance electronic driver, CRCA powder coated white after phosphochomate treatment, Screwless bottom frame, Electronic driver with SMPS based constant current supply , output short circuit, protection, surge protection , Light source - efficincy of greater than 120 lm/w and viewing angle of 120 degree to ensure better uniformily. Wattage of fixture 40 to 50 W, System lumens minimum 4000 to 5000 L . |
| 52 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steelprimer allcomplete. Quoted rate shallbe including GST , transportation , lead , lift , scaffolding etc complete. Nothing extra shall be paid separately. |
| 53 | Steelworkin builtuptubular(round,squareorrectangularhollow tubesetc.)trussesetc.,includingcutting,hoisting,fixingin positionandapplyingaprimingcoatofapprovedsteelprimer,includingweldingandboltedwithspecialshapedwashers etc. complete. Hot finished welded type tubes. Quoted rate shall be including GST , transportation , lead , lift , scaffolding etc complete. Nothing extra shall be paid separately. |
| 54 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shilded with fine tinned copper braid and protected with PVC shealth in the existing surface / recessed steel/PVC conduit as required. |
| 55 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. ( Approved make : MK Honeywell / Legrand ) |
| 56 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 57 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 58 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 59 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut,bolt, spring, washer excavation and re-filling etc. as required. |
| 60 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 61 | Providing and fixing 25 mm X 5 mm G Istrip on surface or in recess for connections etc. as required. |
| 62 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 63 | Providing and fixing 4.00 sq mm dia copper Green wire on surface or in recess for loop earthing as required. ( Approved make : Polycab / Finolex / RR kabel ) |
| 64 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with 2 R of 3 m GI strip of 25x5 mm , charcoal/ coke and salt as required. |
| 65 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with 2 R of 3 m copper strip of 25x5x mm , charcoal/ coke and salt as required. |
| 66 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 meter below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 67 | Providingandfixingoflightningconductorfinial,madeof25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85mmdia6mmthickG.I.baseplateincludingholesetc. complete as required. |
| 68 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
| 69 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
| 70 | Excavation for cable trenches in soft soil, depth upto 1.2 m including cum dressing of sides lift upto 1.5 m, including getting out the excavated soil, refilling with sand and or good soil after laying of cable/ pipe etc in layers of 20 cm, ramming, watering and disposal of surplus excavated soil as directed, within a lead of 50 metres. |
| 71 | Excavation of the cable trenches in hard rock not exceeding 1.5 cummetres in width, and lift upto 1.5 metres, including getting out the excavated soil and disposal of excavated soil as directed within a lead of 50 metres. |
| 72 | Providing and laying in position cement concrete 1:2:4 (1 cement: 2 cum coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required. |
| 73 | Light Point Wiring: Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group A |
| 74 | Light Point Wiring: Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group B ( Approved make : Polycab / Finolex / RR Kabel ) |
| 75 | Light Point Wiring: Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C( Approved make : Polycab / Finolex / RR Kabel ) |
| 76 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes ofFRLS PVC insulated copper conductor, single core cable in surface/ recessedmedium class PVC conduit as required 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire( Approved make : Polycab / Finolex / RR Kabel ) |
| 77 | LIGHT CIRCUIT WIRING :Wiring for circuit / submain wiring in concealed pipe below false ceiling (by chieseling the wall and covering with chicken mesh with rough plastering) / surface mounted. Including ISI mark PVC Conduit with 25mm DIa of 2mm thick with PVC insulated FRLS single core wires with colour code of following:2 x 2.5 sqmm + 1 x2.5 sqmm earth wire. ( Approved make : Polycab / Finolex / RR Kabel ) |
| 78 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 4 sq. mm + 1 X 4 sq. mm earth wire( Approved make : Polycab / Finolex / RR Kabel ) |
| 79 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 6 sq. mm + 1 X 6 sq. mm earth wire( Approved make : Polycab / Finolex / RR Kabel ) |
| 80 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 X 4 sq. mm + 2 X 4 sq. mm earth wire( Approved make : Polycab / Finolex / RR Kabel ) |
| 81 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.( Dismanted material should be handed over to IISER Pune )Group C( Approved make : Polycab / Finolex / RR Kebal ) |
| 82 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessedconduit as required 25 MM ( Approved make : Precision / Diamond / Modi ) |
| 83 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required32mm dia conduit pipe (2mm) -( Approved make : Precision / Diamond / Modi ) |
| 84 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessedconduit as required 40 MM |
| 85 | 16 AMP Switch: Supplying and fixing following Modular switch / socket on the existing raceways & PVC DLP truncking with required accessories to complete jobs. including connections, as requiredincluding connections, as required. . 5/6 amp switch( Approved make : MK Honeywell / Legrand ) |
| 86 | 16 AMP Switch: Supplying and fixing following Modular switch / socket on the existing raceways & PVC DLP truncking with required accessories to complete jobs. including connections, as requiredincluding connections, as required. . 15/16 amp switch( Approved make : MK Honeywell / Legrand ) |
| 87 | Supplying and fixing following Modularsocket on the existing raceways & PVC DLP truncking with required accessories to complete jobs. including connections, as required. .6 Pin 15/16 amp socket outlet( Approved make : MK Honeywell / Legrand ) |
| 88 | POWER SWITCHES / SOCKETS on walls - G.I. BOX.: Supplying and fixing following size / modules, GI box along with modular base and cover plate for modular switches in recess etc, as required. ( The job includes cutting & chasing existing wall, fixing the box in position as required including rough plastering.) (In all the rooms, vertical drops of conduits and switch boxes shall be concealed in the wall). Boxes should be of same make as that of modular accessories. :6 Module |
| 89 | Supplying and fixing following Modular switch / socket on the existing raceways & PVC DLP truncking with required accessories to complete jobs. including connections, as required including connections, as required. . 1/2 Module Box with faceplate & cover |
| 90 | Supplying and fixing following Modular switch / socket on the existing raceways & PVC DLP truncking with required accessories to complete jobs. including connections, as required including connections, as required. . 4 Module Box with faceplate & cover |
| 91 | Supplying and fixing following Modular switch / socket on the existing raceways & PVC DLP truncking with required accessories to complete jobs. including connections, as required including connections, as required. . 6 Module Box with faceplate & cover( Approved make : MK Honeywell / Legrand ) |
| 92 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. 1.50.1 Upto 450 mm sweep |
| 93 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable( Approved make : D link / Polycab / Legrand ) |
| 94 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.2 run of cable( Approved make : D link / Polycab / Legrand ) |
| 95 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 3 run of cable( Approved make : D link / Polycab / Legrand ) |
| 96 | Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement: 2 fine sand) including trenching (75 cm deep) and refillinq etc as required.100 mm dia. |
| 97 | Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement: 2 fine sand) including trenching (75 cm deep) and refillinq etc as required.250 mm dia. |
| 98 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 99 | Supplying,installation,testing and commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights / indoor lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required.2 output per phase and suitable for single phase supply |
| 100 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)*8 way double door |
| 101 | Supplying and fixing following way, horizontal type three poleand neutral, sheet steel, MCB distribution board, 415 V, onsurface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But withoutMCB/RCCB/Isolator)4 way (4 + 12), Double door( Approved Make : Legrand / Schneider / L&T ) |
| 102 | Supplying and fixing following way, horizontal type three poleand neutral, sheet steel, MCB distribution board, 415 V, onsurface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But withoutMCB/RCCB/Isolator)6 way (4 + 18), Double door( Approved Make : Legrand / Schneider / L&T ) |
| 103 | FINAL DISTRIBUTION BOARDS. PART - C-DB\"s & MCB\"s : Supply, Installation, Testing and Commissioning of all MCB Distribution Boards (10KA) 415V,made out of 16SWG MS sheet steel enclosurehinged MS cover/over flanged cover (double door)withcutoutsforoperatingthe MCB knobs and comprising of phase bus bars, neutrals and earth bus with tapped holes, bakelite phase barriers, pvc insulator shoes for incoming wire, etc complete. DB\"s shall be mounted by grouting in to the wall/angle to brick wall as required.DB\"s shall be suitable for Three Phase / single phase loads.OrDB\"s shall be mounted on suitableM.S. angle and supporting flat.DB\"s shall includetermination lugs etc., all complete. (Note: Local fabrication not permitted. Only factorymadeboxes shall be installed and all MCB\"s shall be with10 KA rating)Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required4 way (4 + 18), Double door for UPS DB( Approved Make : Legrand / Schneider / L&T ) |
| 104 | FINAL DISTRIBUTION BOARDS. PART - C-DB\"s & MCB\"s : Supply, Installation, Testing and Commissioning of all MCB Distribution Boards (10KA) 415V,made out of 16SWG MS sheet steel enclosurehinged MS cover/over flanged cover (double door)withcutoutsforoperatingthe MCB knobs and comprising of phase bus bars, neutrals and earth bus with tapped holes, bakelite phase barriers, pvc insulator shoes for incoming wire, etc complete. DB\"s shall be mounted by grouting in to the wall/angle to brick wall as required.DB\"s shall be suitable for Three Phase / single phase loads.OrDB\"s shall be mounted on suitableM.S. angle and supporting flat.DB\"s shall includetermination lugs etc., all complete. (Note: Local fabrication not permitted. Only factorymadeboxes shall be installed and all MCB\"s shall be with10 KA rating)Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required8 way (4 + 24), Double door for RPDB ( Approved Make : Legrand / Schneider / L&T ) |
| 105 | PERFORATEDTYPE CABLE TRAYS : Supplying and installing following size of perforated painted with powder coating M.S. cable trayswith perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm Width x 50mm depth x1.6mm thick. |
| 106 | PERFORATEDTYPE CABLE TRAYS : Supplying and installing following size of perforated painted with powder coating M.S. cable trayswith perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm Width x 50mm depth x1.6mm thick. |
| 107 | PERFORATEDTYPE CABLE TRAYS : Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm Width x 50mm depth x1.6mm thick. |
| 108 | PERFORATEDTYPE CABLE TRAYS : Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm Width x 50mm depth x1.6mm thick. |
| 109 | PERFORATEDTYPE CABLE TRAYS : Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm Width x 50mm depth x1.6mm thick. |
| 110 | PERFORATEDTYPE CABLE TRAYS : Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm Width x 50mm depth x1.6mm thick. |
| 111 | PERFORATEDTYPE CABLE TRAYS : Supplying and installing following size of perforated painted with powder coating M.S. cable trays cross members with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm Width x 50mm depth x1.6mm thick. |
| 112 | PERFORATEDTYPE CABLE TRAYS : Supplying and installing following size of perforated painted with powder coating M.S. cable trays cross members with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm Width x 50mm depth x1.6mm thick. |
| 113 | PERFORATEDTYPE CABLE TRAYS : Supplying and installing following size of perforated painted with powder coating M.S. cable trays reducer with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm Width x 50mm depth x1.6mm thick. |
| 114 | PERFORATEDTYPE CABLE TRAYS : Supplying and installing following size of perforated painted with powder coating M.S. cable trays reducer with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm Width x 50mm depth x1.6mm thick. |
| 115 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 35 sq. mm |
| 116 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 35 sq. mm and upto 95 sq. mm |
| 117 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 95 sq. mm and upto 185 sq. mm |
| 118 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 185 sq. mm and upto 400 sq. mm |
| 119 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm Each thick G.l. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 120 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation includingexcavation, sand cushioning, protective covering and refilling the trench etc as reauired.Upto 35 sq. mm |
| 121 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation includingexcavation, sand cushioning, protective covering and refilling the trench etc as reauired.Above 35 sq. mm and upto 95 sq. mm |
| 122 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation includingexcavation, sand cushioning, protective covering and refilling the trench etc as reauired.Above 95 sq. mm and upto 185 sq. mm |
| 123 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation includingexcavation, sand cushioning, protective covering and refilling the trench etc as reauired. Above 185 sq. mm and upto 400 sq. mm |
| 124 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Upto 35 sq. mm |
| 125 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Above 35 sq. mm and upto 95 sq.mm |
| 126 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Above 95 sq. mm and upto 185 sq.mm |
| 127 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Above 185 sq. mm and upto 400 sq.mm |
| 128 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm. |
| 129 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required..Upto 35 sq. mm |
| 130 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 35 sq. mm and upto 95 sq.mm |
| 131 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 95 sq. mm and upto 185 sq.mm |
| 132 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 185 sq. mm and upto 400 sq.mm |
| 133 | END TERMINATION: Supply and installation of End termination ofcables withcompression brass cable glands,Al crimping type lugs should be used for Al cables and Cu lugs withsoldering and ferrules for the following 1.1kv class Al./Cu. XLPE/PVC insulated using necessary crimping tool and all other accessories as required andIncluding the cost of all materials, lobour, Handling of Materialsof equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. 3.5 Core x 25 Sqmm Armoured Aluminium Cable. |
| 134 | END TERMINATION: Supply and installation of End termination ofcables withcompression brass cable glands,Al crimping type lugs should be used for Al cables and Cu lugs withsoldering and ferrules for the following 1.1kv class Al./Cu. XLPE/PVC insulated using necessary crimping tool and all other accessories as required andIncluding the cost of all materials, lobour, Handling of Materialsof equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. 3.5 Core x 300 Sqmm (A2XFY)XLPE AL. AR. Cable.( Approved make : Dowells / CI / Electrowerke ) |
| 135 | END TERMINATION: Supply and installation of End termination ofcables withcompression brass cable glands,Al crimping type lugs should be used for Al cables and Cu lugs withsoldering and ferrules for the following 1.1kv class Al./Cu. XLPE/PVC insulated using necessary crimping tool and all other accessories as required andIncluding the cost of all materials, lobour, Handling of Materialsof equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. 3.5 Core x 400 Sqmm (A2XFY)XLPE AL. AR. Cable.( Approved make : Dowells / CI / Electrowerke ) |
| 136 | END TERMINATION: Supply and installation of End termination ofcables withcompression brass cable glands,Al crimping type lugs should be used for Al cables and Cu lugs withsoldering and ferrules for the following 1.1kv class Al./Cu. XLPE/PVC insulated using necessary crimping tool and all other accessories as required andIncluding the cost of all materials, lobour, Handling of Materialsof equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. 3.5 Core x 70 Sqmm (A2XFY)XLPE AL. AR. Cable. ( Approved make : Dowells / CI / Electrowerke ) |
| 137 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.31/2 X 240 sq. mm( Approved make : Reachem / Mseal / 3M ) |
| 138 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 300 sq. mm ( Approved make : Reachem / Mseal / 3M ) |
| 139 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.31/2 X 400 sq. mm( Approved make : Reachem / Mseal / 3M ) |
| 140 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable inthe existing surface/ recessed steel/ PVC conduit as required.3 x 1.5 sq. mm |
| 141 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable inthe existing surface/ recessed steel/ PVC conduit as required.5 x 1.5 sq. mm |
| 142 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable inthe existing surface/ recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 143 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable inthe existing surface/ recessed steel/ PVC conduit as required. 5 x 2.5 sq. mm |
| 144 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable inthe existing surface/ recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 145 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable inthe existing surface/ recessed steel/ PVC conduit as required. 5 x 4 sq. mm |
| 146 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable inthe existing surface/ recessed steel/ PVC conduit as required.3 x 6 sq. mm |
| 147 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable inthe existing surface/ recessed steel/ PVC conduit as required. 5 x 6 sq. mm |
| 148 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box includingconnections but excluding modular plate etc. as required.2 way 5/6 A switch |
| 149 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box includingconnections but excluding modular plate etc. as required.3 pin 5/6 A socket outlet |
| 150 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box includingconnections but excluding modular plate etc. as required.Bell push |
| 151 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plateswitch box including connections but excluding modular plate etc. as required. |
| 152 | Supplying and fixing following size/ modules, PVC box along with modular base & cover plate for modular switches in recess etc. as required.6 Module (100mmX75mm) |
| 153 | Supplying and fixing following size/ modules, PVC box along with modular base & cover plate for modular switches in recess etc. as required.4 Module (100mmX75mm) |
| 154 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required.12 Module (200mmX150mm) |
| 155 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.12 Module |
| 156 | Installation, Testing and Commissioning of pre-wired, fluorescent fitting / compact fluorescent/ LED fitting ofall types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connectionswith 1.5 sq. mm FRLS/HFFR PVC insulated, copper conductor, single core cable and earthing etc. asrequired. |
| 157 | Installation, Testing and Commissioning of ceiling fan, including wiring the down rods of standard length(upto 30 cm) with 1.5 sq. mm FRLS/HFFR PVC insulated, copper conductor, single core cable etc. as required. |
| 158 | Supplying and fixing extra down rod of 10 cm length G.I. pipe, 15 mm dia, heavy gauge including paintingetc. as required. (Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 159 | Installation, Testing and Commissioning of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.Upto 450 mm sweep |
| 160 | Installation, Testing and Commissioning of exhaust fan in the existing opening, including making good thedamage, connection, testing, commissioning etc. as required.510 mm sweep |
| 161 | Extra for fixing the louvers/ shutters complete withframe for a exhaust fan of all sizes. |
| 162 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group C |
| 163 | Dismantling of ceiling fan and painting the same with one or more coats of spray painting with synthetic enamel paint of approved brand and manufacture to give an even shade, including cleaning of surface with detergent and replacing the damaged rubber reel,nuts and bolts with washers and safety pins, reinstalling the same as required. |
| 164 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required.250 A,36KA,FPMCCB |
| 165 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required.125 A,36KA,FPMCCB |
| 166 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 167 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Double pole |
| 168 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole |
| 169 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole and nuetral |
| 170 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 A |
| 171 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40A |
| 172 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 A |
| 173 | Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A 415 V \"C\" curve TP MCB complete with connections, testing and commissioning etc. as required. |
| 174 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 A \"C\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete withconnections, testing and commissioning etc. as required. |
| 175 | Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 20 A \"C\" curve, TPMCB, in sheetsteel enclosure, on surface or in recess, with chainedmetal cover for the socket out let and complete withconnections, testing and commissioning etc. as required. |
| 176 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 30 A \"C\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete withconnections, testing and commissioning etc. as required. |
| 177 | Supplying, installation, testing & commissioning of following capacity Plug In/ tap off box on the existing Air Insulated Compact Type bus trunking/ rising mains for use on 3 phase 4 wire 415 volts, 50Hz A.C.supply made with 1.6mm thick sheet steel enclosure(IP54) duly powder coated with provision of MCCB/ACB (but without MCCB/ACB) complete etc. as required 125 A, Isc= 15kA for 1 sec |
| 178 | Supplying, installation, testing & commissioning of following capacity Plug In/ tap off box on the existing Air Insulated Compact Type bus trunking/ rising mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick sheet steel enclosure(IP54) duly powder coated with provision of MCCB/ACB (but without MCCB/ACB) complete etc. as required 400 A, Isc= 35kA for 1 sec |
| 179 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt ) Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser andconstruction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim ( 5-7 Watt) |
| 180 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt ) Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser andconstruction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testingrequired for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C)Powder coated die cast /Extruded aluminium Body including trim ( 8-10 watt ) |
| 181 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt ) Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operatingvoltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80,UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained tilllife ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specifiedrating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connectionswith 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Wattoutput . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as perrequirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminiumBody including trim ( 12-15 Watt) |
| 182 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt )Supplying, Installation, Testing & Commissioning ofLED Recessed/ surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per therequirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -50C to 400C, internal surgeprotection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flickershould be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained tilllife ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum powerconsumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ NameEngraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Wattoutput . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be asapproved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junctiontemperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim( 18 watt ) |
| 183 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material andconstruction as per IS : 10322 with driver as per therequirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuitprotection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 BurningHours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(StandardDeviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. asrequired with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not riseabove 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) 18 watts |
| 184 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning ofPanel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz,Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 BurningHours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard.Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) 36 watts |
| 185 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt). Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement withDriver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker shouldbe below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumptionshould not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sqmm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management:heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) 18-22 watt |
| 186 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt). Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement withDriver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker shouldbe below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumptionshould not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sqmm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management:heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) 40 watt |
| 187 | Brush Less Direct Current (BLDC) Fan without Remote Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance asper IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR,PVC insulated copper conductor single core cable and earthing etc. as required. 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 188 | Brush Less Direct Current (BLDC) Fan without Remote Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance asper IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR,PVC insulated copper conductor single core cable and earthing etc. as required. 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) 1400mm, service value ≥ 6.0 CM/Min/Watt, airdelivery 245 CM/Min (Minimum) |
| 189 | Supplying & fixing PVC insulated PVC sheathed copper conductor submersible flat cable ISI Marked in existing metal/ HDPE / PVC/ pipe/ in bore well/ in sump including fixing the cable to GI/HDPE pipe with suitable cable tags of following sizes etc. complete as required.3 Core 2.5 Sq mm Flat Cable |
| 190 | Supplying & fixing PVC insulated PVC sheathed copper conductor submersible flat cable ISI Marked in existing metal/ HDPE / PVC/ pipe/ in bore well/ in sump including fixing the cable to GI/HDPE pipe with suitable cable tags of following sizes etc. complete as required.3 Core 4.0 Sq mm Flat Cable |
| 191 | Supplying & fixing PVC insulated PVC sheathed copper conductor submersible flat cable ISI Marked in existing metal/ HDPE / PVC/ pipe/ in bore well/ in sump including fixing the cable to GI/HDPE pipe with suitable cable tags of following sizes etc. complete as required.3 Core 6.0 Sq mm Flat Cable |
| 192 | Supplying, Installation, Testing and Commissioning of underwater Luminaries surface mounted RGB LED spot light 3 x 3W with IP 68 protection, SS/ aluminum dia casting body with power coated paint, soft rubber gasket along with 2 years free replacement guarantyetc. complete as required. |
| 193 | Supplying, Installation, Testing and Commissioning of three phase openwell ISI Marked submersible pump set of 7.5 H.P. capacity suitable for operation on 415V(+-10%), 3- phase AC supply compatible for operations on dynamic variable frequency / speed having IP 68 Protection including providing required no\"s of heavy duty M.S clamps made of flat iron and suitable size top cover made of suitable thick MSsheet as required. and making of flexible IP68 cable connections etc. complete as required. |
| 194 | Supplying Installation Testing and Commissioning of 24 port Cat6 Patch Panel loaded. Must be of 1U height with clear label holders and white label with the panel.24 Ports Cat-6 Patch Panel should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required. |
| 195 | Supplying, Installation, Testing and commissioning of following CAT6 Patch Cord should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required. Copper Patch Cords of length 1m (3ft) |
| 196 | Supplying, Installation, Testing and commissioning of CAT6A Copper Information Outlet (IO) with face plate of color as per site requirement, should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D. All copper Cable and Components should be from same OEM to maintain compatibility and interoperability etc. complete as required. |
| 197 | Supplying and drawing following core Fiber Optic Cable having corrugated steel armoring. The Fiber should be SM Fiber Central -loose tube filled with Thixotropic jelly, duly following Standards: ISO 11801, IEC 60793-1/60794-1-2, ITU-T-REC G.652D and Telecordia GR-20-core, High quality Electro hromium Coated Corrugated Steel tape (ECCS ) and HDPE- Sheath, Operating ambient Temperature should be – 5 0C to +50 0C and Storage Temperature shall be – 5 0C to +50 0C, Max Attenuation ± 0.36 (db / km) at Operational Wavelength 1310 nm and ± 0.22276 DELHI SCHEDULE OF RATES (E&M)-2025 db / km at Operational Wavelength 1550 nm. type offiber should be 9/125 / G.652D & Refractive Index should be 1.4670/1.4675. The value for Mode-filed, Cladding Diameter 9.2 ± 0.4 μm and 125 ± 0.7 μm correspondingly. The Dispersion value < 3.5 < 18 ps/nm-km and PMD value < 0.2 ps/km and Cable Cutoff wavelength < 1260 nm i/c splicing & marking etc complete as required. Single Mode 6 Core Optical fiber cable |
| 198 | Supplying and drawing following core Fiber Optic Cable having corrugated steel armoring. The Fiber should be SM Fiber Central -loose tube filled with Thixotropic jelly, duly following Standards: ISO 11801, IEC 60793-1/60794-1-2, ITU-T-REC G.652D and Telecordia GR-20-core, High quality Electro hromium Coated Corrugated Steel tape (ECCS ) and HDPE- Sheath, Operating ambient Temperature should be – 5 0C to +50 0C and Storage Temperature shall be – 5 0C to +50 0C, Max Attenuation ± 0.36 (db / km) at Operational Wavelength 1310 nm and ± 0.22276 DELHI SCHEDULE OF RATES (E&M)-2025 db / km at Operational Wavelength 1550 nm. type offiber should be 9/125 / G.652D & Refractive Index should be 1.4670/1.4675. The value for Mode-filed, Cladding Diameter 9.2 ± 0.4 μm and 125 ± 0.7 μm correspondingly. The Dispersion value < 3.5 < 18 ps/nm-km and PMD value < 0.2 ps/km and Cable Cutoff wavelength < 1260 nm i/c splicing & marking etc complete as required. Single Mode 12 Core Optical fiber cable |
| 199 | Supply and fixing following port Rack Mount loaded LIU with pigtail, Front-mounted cable saddles for jumper management, suitable to manage both splices and terminations, Pre-assembled shelves in multiple configurations, Rubber fiber slotted bracket built-in, metal splice shelf to protect the fibers, 2 fiber spools built-in for 900μm tight buffered fiber storing, Capable of storing up to 3 meters of 900μm tight buffered fiber per adapter, Removable front and rear covers for better access to interior of LIU, Should be Single / Multi mode LC Type fully loaded. Accessory kit consists of cable ties, mounting ear screws, and spiral wrap tube etc complete as required.6 port LIU |
| 200 | Supply and fixing following port Rack Mount loaded LIU with pigtail, Front-mounted cable saddles for jumper management, suitable to manage both splices and terminations, Pre-assembled shelves in multiple configurations, Rubber fiber slotted bracket built-in, metal splice shelf to protect the fibers, 2 fiber spools built-in for 900μm tight buffered fiber storing, Capable of storing up to 3 meters of 900μm tight buffered fiber per adapter, Removable front and rear covers for better access to interior of LIU, Should be Single / Multi mode LC Type fully loaded. Accessory kit consists of cable ties, mounting ear screws, and spiral wrap tube etc complete as required.12 port LIU |
| 201 | Supplying and fixing Patch Cord of Optical Fiber Multi Mode or Single Mode LC to LC Fiber Duplex having high precision ceramic ferrule with good concentricity, Fiber corning single mode G652D, Cable Type 2mm with Mechanical specification Apex Offset < 50 μm, Fiber Height + 100 nm, End-face radius of Curvature 7mm < R <25mm, Repeatability < 0.2 db, Working ambient Temperature – 5 0C to +50 0C, Storage Temperature – 10 0C to +50 0C, Length -- 2meter, Type -- LC-LC Duplex etc complete as required. |
| 202 | Supplying and fixing of following size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knocked-down condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with \"U\"Marking, Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required.9 U rack |
| 203 | Supply and installation of Fly catcher tube, 18 watts with blue colour into existing fly catchers as complete. |
| 204 | Supply and installation of Fly catcher ballast for , 2x18 wattsinto existing fly catchers as complete. |
| 205 | Supply and installation of Fly catcher ballast for HV ,230 V, into existing fly catchers as complete. |
| 206 | Supply and installation of UV tube of specifications UV-C radiation 8 W , G8 T5 , 1ft, into existing pass box , as complete. |
| 207 | Supply and installation of PL tube of specifications 6500 K, 8 w, T5 , 1ft into existing pass box , as complete. |
| 208 | Supply and installation of Ballast for PL & UV tube of pass box,specifications 1 x 9-13 W PL into existing pass box , as complete. |
| 209 | Supply and installation of Lead acid batteries of SMF 12 V 12 Ah, in existing panel / lift panel etc as required. Warranty 01 years. |
| 210 | Supply and installation of Lead acid batteries of SMF 12 V 07 Ah, in existing panel / lift panel etc as required. Warranty 01 years. |
| 211 | Supply and installation of Veriable frequncy drive , wall mounted with required accessories as complete. Specifications : Operating temp 0 degree celcius to 55 degC, Transiednt over torque more than 170 %, minimum 4DIs, 2DOs,1AI, 1AO, inbuild PID with minimum 2 presents ref, automatic restart, manual setting for output frequency, display for showing load current, Output voltage, output frequency, error code, 3phase , 440 A, Heavy duty, suitable for AHU blower motor of 2.2 KW. |
| 212 | Supply and installation of Veriable frequncy drive , wall mounted with required accessories as complete. Specifications : Operating temp 0 degree celcius to 55 degC, Transiednt over torque more than 170 %, minimum 4DIs, 2DOs,1AI, 1AO, inbuild PID with minimum 2 presents ref, automatic restart, manual setting for output frequency, display for showing load current, Output voltage, output frequency, error code, 3phase , 440 A, Heavy duty, suitable for AHU blower motor of 3 KW. |
| 213 | Supply and installation of Veriable frequncy drive , wall mounted with required accessories as complete. Specifications : Operating temp 0 degree celcius to 55 degC, Transiednt over torque more than 170 %, minimum 4DIs, 2DOs,1AI, 1AO, inbuild PID with minimum 2 presents ref, automatic restart, manual setting for output frequency, display for showing load current, Output voltage, output frequency, error code, 3phase , 440 A, Heavy duty, suitable for AHU blower motor of 4 KW. |
| 214 | Supply and installation of Veriable frequncy drive , wall mounted with required accessories as complete. Specifications : Operating temp 0 degree celcius to 55 degC, Transiednt over torque more than 170 %, minimum 4DIs, 2DOs,1AI, 1AO, inbuild PID with minimum 2 presents ref, automatic restart, manual setting for output frequency, display for showing load current, Output voltage, output frequency, error code, 3phase , 440 A, Heavy duty, suitable for AHU blower motor of 5.5 KW. |
| 215 | Supply and installation of Veriable frequncy drive , wall mounted with required accessories as complete. Specifications : Operating temp 0 degree celcius to 55 degC, Transiednt over torque more than 170 %, minimum 4DIs, 2DOs,1AI, 1AO, inbuild PID with minimum 2 presents ref, automatic restart, manual setting for output frequency, display for showing load current, Output voltage, output frequency, error code, 3phase , 440 A, Heavy duty, suitable for AHU blower motor of 11 KW. |
| 216 | Supply and installation of Veriable frequncy drive , wall mounted with required accessories as complete. Specifications : Operating temp 0 degree celcius to 55 degC, Transiednt over torque more than 170 %, minimum 4DIs, 2DOs,1AI, 1AO, inbuild PID with minimum 2 presents ref, automatic restart, manual setting for output frequency, display for showing load current, Output voltage, output frequency, error code, 3phase , 440 A, Heavy duty, suitable for AHU blower motor of 15 KW. |
| 217 | Supply and installation of Veriable frequncy drive , wall mounted with required accessories as complete. Specifications : Operating temp 0 degree celcius to 55 degC, Transiednt over torque more than 170 %, minimum 4DIs, 2DOs,1AI, 1AO, inbuild PID with minimum 2 presents ref, automatic restart, manual setting for output frequency, display for showing load current, Output voltage, output frequency, error code, 3phase , 440 A, Heavy duty, suitable for Water pump 3 phase of 2.2 KW. |
| 218 | Supply and installation of Veriable frequncy drive , wall mounted with required accessories as complete. Specifications : Operating temp 0 degree celcius to 55 degC, Transiednt over torque more than 170 %, minimum 4DIs, 2DOs,1AI, 1AO, inbuild PID with minimum 2 presents ref, automatic restart, manual setting for output frequency, display for showing load current, Output voltage, output frequency, error code, 3phase , 440 A, Heavy duty, suitable for Water pump 3 phase of 3 KW. |
| 219 | Supply and installation of Veriable frequncy drive , wall mounted with required accessories as complete. Specifications : Operating temp 0 degree celcius to 55 degC, Transiednt over torque more than 170 %, minimum 4DIs, 2DOs,1AI, 1AO, inbuild PID with minimum 2 presents ref, automatic restart, manual setting for output frequency, display for showing load current, Output voltage, output frequency, error code, 3phase , 440 A, Heavy duty, suitable for Water pump 3 phase of 4 KW. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail