| Sl. No. | Item Description |
| 1 | Schedule \"A\" Part – I to Schedule \"A\" Part – XVI:NOTE: Schedule \"A\" Part – I to Part – XVI are prepriced by MES. Bidders shall insert their Lumpsum amount in Green coloured field under Column - 6 only |
| 2 | Lumpsum price worked out by the contractor for \"BUILDINGS & STRUCTURES\",as listed in Schedule \"A\" Part – I |
| 3 | Lumpsum price worked out by the contractor for \"SITE CLEARANCE / AREA DEVELOPMENT/EARTH WORK/EXCAVATION\",as listed in Schedule \"A\" Part – II |
| 4 | Lumpsum price worked out by the contractor for \"INTERNAL ELECTRIFICATION\", as listed in Schedule \"A\" Part – III |
| 5 | Lumpsum price worked out by the contractor for \"INTERNAL WATER SUPPLY\", as listed in Schedule \"A\" Part – IV |
| 6 | Lumpsum price worked out by the contractor for \"SEWAGE DISPOSAL\",as listed in Schedule \"A\" Part – V |
| 7 | Lumpsum price worked out by the contractor for \"EXTERNAL WATER SUPPLY\",as listed in Schedule \"A\" Part – VI |
| 8 | Lumpsum price worked out by the contractor for \"EXTERNAL ELECTRIFICATION\", as listed in Schedule \"A\" Part – VII |
| 9 | Lumpsum price worked out by the contractor for \"ROADS /PATH/HARD STANDING/ CULVERT\",as listed in Schedule \"A\" Part – VIII |
| 10 | Lumpsum price worked out by the contractor for \"AREA DRAINAGE\",as listed in Schedule \"A\" Part – IX |
| 11 | Lumpsum price worked out by the contractor for \"FIRE FIGHTING SYSTEM\",as listed in Schedule \"A\" Part – X |
| 12 | Lumpsum price worked out by the contractor for \"FIRE ALARM \",as listed in Schedule \"A\" Part – XI |
| 13 | Lumpsum price worked out by the contractor for \"\"LIGHTENING PROTECTION \",as listed in Schedule \"A\" Part – XII |
| 14 | Lumpsum price worked out by the contractor for \"ADD PLUG POINT\",as listed in Schedule \"A\" Part – XIII |
| 15 | Lumpsum price worked out by the contractor for \"AIR CONDITIONING\",as listed in Schedule \"A\" Part – XIV |
| 16 | Lumpsum price worked out by the contractor for \"SOLAR WATER HEATER\",as listed in Schedule \"A\" Part – XV |
| 17 | Lumpsum price worked out by the contractor for \"PILE FOUNDATION\",as listed in Schedule \"A\" Part – XVI |
| 18 | Schedule \"A\" Part - XVII: [Miscellaneous Items] [ Internal Electrification, Internal water supply, External Water Supply, External Electrification, Road/Path/ Hrad standing/ culvert, Fire fighting & Fire alarm, Sewage Disposal,Lifts, Avialtion Light, DG Set,Earthing, Add Plug, Electric chimney, PVC condit, Cooling Appliances, Arboriculture, Pile foundation and Outsourcing of M&O/ Comprehensive Maintenance of Lifts] |
| 19 | Internal Electrification |
| 20 | M&L forPonit wiring with 1.5 sqmmPVC insulated and unsheathed copper conductorcable multistranded 1100 volts grade,FRLS, ISI marked drawn through and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marked, concealed including provn of pre fabricated pressed steel terminal box of suitable size made out of 2 mm thick sheets,for mounting modular brackets, including modular brackets and plates as required at site for fixing modular type switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity green in colour, connected to earth duly complete all as specified and directed forOne lightpoint controlled by one switch :-Note: (a) The PVC conduit shall be concealed and switch boards shall be flush to wall. (b) On columns/ pillars the box type switchboards surface mounted with necessary PVC conduit upto ceiling/nearest junction tapping shall be surface type conduitand quoted rate deemed to be inclusive for the same.(c) The quoted rate inclsuive necessary modules any type as per requirement incl all accessories complete |
| 21 | M&L forPonit wiring with 1.5 sqmmPVC insulated and unsheathed copper conductorcable multistranded 1100 volts grade,FRLS, ISI marked drawn through and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marked, concealed including provn of pre fabricated pressed steel terminal box of suitable size made out of 2 mm thick sheets,for mounting modular brackets, including modular brackets and plates as required at site for fixing modular type switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity green in colour, connected to earth duly complete all as specified and directed forOne bell point controlled by one bell push :-Note: (a) The PVC conduit shall be concealed and switch boards shall be flush to wall. (b) On columns/ pillars the box type switchboards surface mounted with necessary PVC conduit upto ceiling/nearest junction tapping shall be surface type conduitand quoted rate deemed to be inclusive for the same.(c) The quoted rate inclsuive necessary modules any type as per requirement incl all accessories complete |
| 22 | M&L forPonit wiring with 1.5 sqmmPVC insulated and unsheathed copper conductorcable multistranded 1100 volts grade,FRLS, ISI marked drawn through and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marked, concealed including provn of pre fabricated pressed steel terminal box of suitable size made out of 2 mm thick sheets,for mounting modular brackets, including modular brackets and plates as required at site for fixing modular type switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity green in colour, connected to earth duly complete all as specified and directed forOne fan (ceiling fan/Ex.fan) point controlled by one switch:-Note: (a) The PVC conduit shall be concealed and switch boards shall be flush to wall. (b) On columns/ pillars the box type switchboards surface mounted with necessary PVC conduit upto ceiling/nearest junction tapping shall be surface type conduitand quoted rate deemed to be inclusive for the same.(c) The quoted rate inclsuive necessary modules any type as per requirement incl all accessories complete |
| 23 | M&L forPonit wiring with 1.5 sqmmPVC insulated and unsheathed copper conductorcable multistranded 1100 volts grade,FRLS, ISI marked drawn through and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marked, concealed including provn of pre fabricated pressed steel terminal box of suitable size made out of 2 mm thick sheets,for mounting modular brackets, including modular brackets and plates as required at site for fixing modular type switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity green in colour, connected to earth duly complete all as specified and directed forOne 3 Pin socket outlet 6 amps socket on independent board:-Note: (a) The PVC conduit shall be concealed and switch boards shall be flush to wall. (b) On columns/ pillars the box type switchboards surface mounted with necessary PVC conduit upto ceiling/nearest junction tapping shall be surface type conduitand quoted rate deemed to be inclusive for the same.(c) The quoted rate inclsuive necessary modules any type as per requirement incl all accessories complete |
| 24 | M&L forPonit wiring with 1.5 sqmmPVC insulated and unsheathed copper conductorcable multistranded 1100 volts grade,FRLS, ISI marked drawn through and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marked, concealed including provn of pre fabricated pressed steel terminal box of suitable size made out of 2 mm thick sheets,for mounting modular brackets, including modular brackets and plates as required at site for fixing modular type switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity green in colour, connected to earth duly complete all as specified and directed forOne 3 Pin socket outlet 6 amps socket on same board with other switches :-Note: (a) The PVC conduit shall be concealed and switch boards shall be flush to wall. (b) On columns/ pillars the box type switchboards surface mounted with necessary PVC conduit upto ceiling/nearest junction tapping shall be surface type conduitand quoted rate deemed to be inclusive for the same.(c) The quoted rate inclsuive necessary modules any type as per requirement incl all accessories complete. |
| 25 | All as per item No. 16 above but One3 pin socket outlet 15 amps socket on independent board with 4 sqmm FRLS PVC wire for phase and neutral and one run of 4 sqmm copper cable green in colourfor earth continuty conductor complete all as specefied and directed. |
| 26 | All as per item No. 16 abovebut one light point controlled by two Nos of two way switch complete all as specefied and directed. |
| 27 | Supply and fixing LED adore lamp for AC 240Volt supply, B22 type,CDS five star, 10 watts of five star rated complete all as specified and as directed. |
| 28 | Supply and fixing ceiling fan, AC single phase 230 V of size 1200 mm sweep, copper wound with complete set and fixtures such as canopy, down rod etc.5 Star rating, metallic body complete with and inclussive of making necessary electric connection from ceiling rose to fan through twin core flexible wireall as specefied and directed. |
| 29 | S&F Exhaust fan 350 mm sweep or nearest size, plastic body(Heavy duty), complete with louvers suitable for operation on 230 V AC, 50 HzAC supply fixed on wall making opening,fixing and making good the distrubered surfaces etccomplete with and inclussive of making necessary electric connection from ceiling rose to fan through twin core flexible wire all as spcified and as directed. |
| 30 | S&F Exhaust fan 450 mm sweep , (Heavy duty),complete with louvers suitable for operation on 240 V AC, 50 HzAC supply fixed on wall including making of neccessary opening ,fixing and making good the disturbed surfaces etccomplete with and inclussive of making necessary electric connection from ceiling rose to fan through twin core flexible wire all as specified and as directed. |
| 31 | Supply and fixingEnergy efficient LED tube light fitting with tube 5 watts or nearest size ,240V, 50hz surface mounted, decorative ultra slim square profile LED lighting fixture with extruded polycarbonate environmental friendly, energy efficient ready to use pack of complete with mounting bracket etc including connecting up with 1.0 sq mm 3 core flexible copper conductor cable complete all as specified and directed |
| 32 | Supply and fixingEnergy efficient LED tube light fitting with tube 10 wattsor nearest size ,240V, 50hz surface mounted, decorative ultra slim square profile LED lighting fixture with extruded polycarbonate environmental friendly, energy efficient ready to use pack of complete with mounting bracket etc including connecting up with 1.0 sq mm 3 core flexible copper conductor cable complete all as specified and directed |
| 33 | Supply and fixingEnergy efficient LED tube light fitting with tube 2 x 20 wattsor nearest size ,240V, 50hz surface mounted, decorative ultra slim square profile LED lighting fixture with extruded polycarbonate environmental friendly, energy efficient ready to use pack of complete with mounting bracket etc including connecting up with 1.0 sq mm 3 core flexible copper conductor cable complete all as specified and directed |
| 34 | Supply and fixing LED Security light fitting with tube 30W New generation Energy saving &environmental frindly long lifemade up of pressure die cast aluminium housing with high efficient LED as lighting source and PC cover having top opening seperate driver compartment with IP66 protectionpre wired with 1.0 Sq mm copper conductor cable upto connector including 1.5 m long GI Tubing light grade of 32mmdia bend to shape for fixing on wall/pole withsuitable MS brackets nuts and bolts etccompelte all as specified and as directred. |
| 35 | Material and labour for submain wiring complete with earth wire of PVC insulated multistranded copper conductor FRLS cable, ISI marked with and inclussive of suitable size PVC rigid counduit concealed to wall, and PVC wire of size 2x4sqmm for phase and neutral duly colour coded and 1x4 sqmm for earth continuity conductor green in colour complete all as specified and as directed.Note :(i) Two run of 4.0 Sqmm + one run of 4.0 Sqmm as a earth wire cable + one run of PVC conduitshall be measured as an one Unit. |
| 36 | Material and labour for submain wiring complete with earth wire of PVC insulated multistranded copper conductor FRLS cable, ISI marked with and inclussive of suitable size PVC rigid counduit concealed to wall, and PVC wire of size 2x6sqmm for phase and neutral duly colour coded and 1x6 sqmm for earth continuity conductor green in colour complete all as specified and as directed.Note :(i) Two run of 6.0 Sqmm + one run of 6.0 Sqmm as a earth wire cable + one run of PVC conduitshall be measured as an one Unit. |
| 37 | Material and labour for submain wiring complete with earth wire of PVC insulated multistranded copper conductor FRLS cable, ISI marked with and inclussive of suitable size PVC rigid counduit concealed to wall, and PVC wire of size 4x10sqmm for phase and neutral duly colour coded and 1x10 sqmm for earth continuity conductor green in colour complete all as specified and as directed.Note :(i) Four run of 10.0 Sqmm + one run of 10.0 Sqmm as a earth wire cable + one run of PVC conduitshall be measured as an one Unit. |
| 38 | Supply and fixing concealed in wall VTPN DB double door type, 6 way 415V, 50Hz , IP 43 protection, including provision for fixingMCB TPN as incommer andoutgoing circuits MCB SP/TP complete,fill empty way with blanking plates complete all as specefied and directed. |
| 39 | S&F MCCB 4 pole 415V, 50Hz, 10KA of capacity 100 Amp. |
| 40 | S&F MCB TPN 63 Amps 50Hz, 10KA ,415 Volts, C curve |
| 41 | S&F MCB SPN, 6to 32Amps 240 Volts , 10KA, C curve |
| 42 | S&F MCB SP, 6to 32Amps 240 Volts , 10KA, C curve |
| 43 | M & L for earthing complete with galvanised steel earth plate electrode 60cm×60cm× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron strip 32 x 6 mm by meams of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown electrical plate No.3, connected to earthing test point all as specified and directed and testing on completion.Note- i) Rate quoted deemed to be include excavation and earth work in any type of soil with PCC workcomplete all as specefied and directed.ii) GI earth strip upto 7.5 m shall be deemed to be included in the quoted lumpsum and beyond 7.5 m shall be measured and paid separately under relavent item. |
| 44 | Internal Water Supply |
| 45 | S&F Bib taps two way, cast copper alloy fancy typechromium plated screwed down for size of15 mm inner dia, suitable fo 16 mm outer dia CPVC pipes complete all as specified and as directed. Note: The maximum flow rate will be 03 LPM |
| 46 | S&F health faucet chromium plated , fancy type with steel flexible complete of size of15 mm dia suitable for 16 mm dia outer dia CPVC pipes complete all as specified and as directed.Note: The maximum flow rate will be 03 LPM |
| 47 | Sewage Disposal |
| 48 | M& L for SRFC factory mademanhole cover square/rectangular/ circlar shape for using cover to maholescomplete all as specified and as directed. |
| 49 | External Water Supply |
| 50 | Cutting existing DI/MS pipe lene of 150 mm dia for alterations or additions necessarily done in position without taking down and inserting Tee of 150 x 150 x 100 mm and including Tee for tapping all as specified and directed. |
| 51 | Material and Labour for laying of Ductile Iron pipe with spigot and socket end centrifugally cast(spun) class K-7 of 100 mm dia pipe conforming to IS-8329 including testing and commissioning all as specified andas directed. |
| 52 | Material and Labour for laying of Ductile Iron pipe with spigot and socket end centrifugally cast(spun) class K-9 of 100 mm dia pipe conforming to IS-8329 including testing and commissioning all as specified andas directed. |
| 53 | Supply & installation of 415 V, 3 phase Horizontal centrifugal closed coupled pump set having discherge 586LPM at 70 Mtr head with TEFC squeirrel cage induction motor insulation class F,inlet/outlet of 65 x 50 mm and bronze impeller having motor effieiency of IE3 and mechanical seal inclusive PCC foundation complete all as specified and directed directed. |
| 54 | S & F LT Panel board made out of CRCA sheet 2 mm thick Indoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, danger notice plate, strickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 Aluminium bus bar with heat proof colour code, insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 200 A capacity complete with powder coating, necessary internal electric connection as requiredwith and inclusive of following items: (Fresh Water Pannel).Incoming:(a) LT 440 volts3 phase, 4 wire 50 cycles, 25kA, Adjustable type MCCB of 100 Amp rated complete with overload protection, no-volt thermal based release.-01 Nos |
| 55 | Outgoing:(b) Supply and fixing MCCB 4 pole, 16KA 63 Amp, 50 Hz, 240/415 Volts complete -03 Nos(02 for pumps and 01 for spare),(c) Supply and fixing MCB C-Curve, 16 Amp TPN, 50 Hz, 240/415 Volts complete -01 Nos( for pumpshouse bldg).d) Star Delta starter for 3 phase approx 20 HP pumpset with pump protection relays - 02 Nos.(e) LED Indicating Lamps for ech phase with colour coed Red Yellow Blue for R, Y and B Phases-01 set of 03.f) Intelligent Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs of main incommer |
| 56 | M&L for valve chamber of internal size 1.0x1.0x1.0m comprising of 50mm thick PCC 1:5:10 type E2 foundation, 200mm thick brick wall in CM 1:6, 15mm thick plastering in CM 1:4 internally and externally up to 50mm be;ow GL,100mm thick PCC 1:3:6 type B1 as in copings,3mm thick MS sheet cover with suitable hinges and locking arrangement, painting steel surfaces with two coats of synthetic enamel paint over a coat of primerincluding necessary earth work and excavation in any type of soil complete all as directed. |
| 57 | Taking down old existing CI/GI mains(including all fittings) with spigot and socket ends and fittings for re-use in the work and removing unserviceable pipes and fittings from site complete all as specified and directed for the 100mm bore of pipe complete all as directed. |
| 58 | External Electrification |
| 59 | Supply laying & testing cable XLPEinsulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor 11000 volts grade, of size 3 core 185 sqmm complete all as directed. (For Proposed Bldg - 750 RM and Re-routing - 900 RM). |
| 60 | Supply laying & testing cable XLPEinsulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor 11000 volts grade, of size 3 core 240 sqmm complete all as directed. (For re-routing). |
| 61 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessery machining including HDPE pipe of 150mm dia suitable for 0.4 Mpa working pressure. |
| 62 | Supply and fix cable jointing kit for 11kV grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 120 to 185 sqmm complete all as directed. |
| 63 | Supply and fix cable jointing kit for 11kV grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 240 sqmm complete all as directed. |
| 64 | Supply and fix cable jointing kit for 11kV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm complete all as specified. |
| 65 | Supply and fix cable jointing kit for 11kV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm complete all as specified. |
| 66 | Supply installation testing commissioning of outdoor type 11 KV Compact Sub Station with non extensible manually operated 1 No SF6 insulated VCB with metering cubicle/relays/protections, HT Cable/Bus bar, 1 Notransformer 1000 KVA,11KV/433, oil filled& associated LTside having of ACB 1600A 50KA 02 No (one for main LT panel and one spare) complete all as specified and as directed below: |
| 67 | HT Side:11kV, 630A, 21kA/1 sec, non-extensible breaker in min 2.5mm stainless non ferrite and non magnetic robotically welded steel tank with copper busbar, compact switchgear consisting of one no. Fixed manual Vacuum Circuit Breakers (VCB) with direct incoming connection in SF6 insulated selaed for life gas tank with IP67 degree of protection with integrated current protectionwhich shall be connected to HV side of above transformer using 1C x 3R x 95 Sqmm Cable with site replacable bushings alongwith air insulated metering module for bus side metering. The breaker shall have self powered microprocessor based numerial over current and earth fault relay protection with charged open / closing mechanism, on/off indcators, mechanical operation counters etc. Interconnection between HT switchgear and transformer shall be using 1Cx3x95 sq.mm Al. unarmorured XLPE Cable.a) Relay shall be self powered of Ashida/C&S/equiv Make. ( 50,50N,51,51N) with RS485 communication port - 01 Nob) Protection CT shall be 80/1A 2.5VA 5P10. - 01 Setc) Standard Manometer (SF6 Gas Pressure Indicator) - 01 Nod) Fault Passage Indicator (FPI) for incoming only - 01 Noe) Voltage presence indicator (VPIS) for incoming Healthy Indications - 01 Setf) Manual push button for breaker ON/OFF - 01 Setg) Mechanical Indication for Breaker & LBS ON/OFF/EARTHED - 03 Nosh) Operating handle - 01 Noi) All incoming modules of the breaker shall be capable for cable termination of 3C x 300 sq.mm Al XLPE Cable. |
| 68 | Transformer:1000 KVA 11kV/433V Dyn11 Oil Filled (ONAN) Hermetically sealed distribution transformer with corrugated radiator wall (without conservator type design) & Top mounted normal porcelain bushing for HT, LT with Off circuit tap changer a) Off Circuit Tap Changer (OCTC), Tapping range +5% to -5% in a steps of 2.5% (4 Steps/5 Positions)b) Temp. Rise Shall be 40/45 Deg. C for Oil/Winding resp. Over an ambient of 50Deg.C Tempc) Insulation Class: Ad) Losses ( Subject to IS 1180 Efficiency Level 2/ Star 2 as per latest Amendment 4) Max. Total Loss @ 50% Loading: 2620 W and Max. Total Loss at 100% Loading: 7000 W.e) % Impedance (%Z) shall be 5.00% (Subject to IS Tol.)f) Rating & Diagram (R&D) Plate (Fitted on Transformer)g) Oil Temp. Indicator (OTI)with alarm and trip contacth) Winding Temp. Indicator (WTI)with alarm and trip contacti) Rated temp Class of Transformer Compartment K10 upto 1000kVA |
| 69 | LT Side:LT PANEL- 2400 A Aluminium Busbar (100% for Phase & 50% for Neutrals) Current density 1amp/sqmm, having IP2X, Fabrication using 1.5/2mm CRCA sheet steel complete with internal wiring consisting of followinga) INCOMERFrom transformer b) 1600Amps 4P 50Hz 50KA Fixed Manual Type Air Circuit Breaker (ACB) with microprocessor based Ekip Dip release for Overload (O/L), Short circuit (S/C) & Earth Fault (E/F) protection. - 02 Nosc) LED type Indicating Lamp - RYB, ON-OFF-TRIP. - 01 Setd) LT side metering CT 1600A/ 5A, 5VA, Cl:1.0 - 01 Sete) Digital Multifunction Meter (MFM), CL-1.0 Accuracy with RS485 Port - 01 No |
| 70 | OUTDOOR ENCLOSURE:Outdoor type enclosure having construction of Galvanised Sheet Steel having 1.5mm thickness for Non-load bearing & 2 mm for Load bearing partition sheets & Door with HRCA 4 mm base frame. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP23 degree of protection for Transformer compartment. The enclosure exterior shall be Powder Coated (Colour Light gray and dark gray ). Each compartment will be provided with the door and pad locking arrangement. The Compartment illumination lamp with door operated switch shall be provided for MV & LV compartment. As per IEC 62271-202.INTERCONNECTION AND EARTHING:Interconnection Between HT switchgear & Transformer using 1Cx3Rx95 Sq.mm XLPESingle Core AluminumUnarmored Cable & Interconnection between Transformer & LT switchgear using Aluminum Busbars with aluminum flexible. Internal earthing connections by using 50X6mm GI strips including Transformer Neutral.Note: CompactSub-Station is outdoor plinth mounted type, Erection, Commissiong and Civil work for package substation and the foundation making is deemed to be included in quoted rates. |
| 71 | Supply and install outdoor type APFC panel of capacity 450 KVAR with 8 steps (2x100 + 4x50 + 2x25)with MD-XL capacitor and 500A 36KA microprocessor controlled 4 pole MCCB as incomer complete all as specified and directed. |
| 72 | Supply, installing, testing and commissioning of Main LT Panel made out of CRCA sheet 3.15 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, strickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 2400 A capacity complete with powder coating, necessary internal electric connection as required and provision of the following : (Main LT Panel). |
| 73 | Incoming:a) 1250 Amps 4P 50Hz 50KA Fixed Manual Type Air Circuit Breaker (ACB) with microprocessor based Ekip Dip release for Overload (O/L), Short circuit (S/C) & Earth Fault (E/F) protection, with necessary CTs, meters and cable boxes. - 1 No.Outgoing:a)Air circuit breaker 630 Amps, 50 kA, fixed manual type, 4 Pole, microprocessor based, with adjustable type overload protection, short circuit protection, with necessary CTs, meters and cable boxes. - 4 No (BBT 1 & 2, APFC panel & 01 Spare) b) LT 440 volts3 phase, 4 wire 50 cycles, 36kA, MCCB of 160 Amp rated microprocessor based complete with overload protection- 02 No (AMF Panel & FF panel). c) Intelligent Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs. d)LED indicating lamps with colour Red, Yellow, Blue of 03 Sets. |
| 74 | Supply, installing, testing and commissioning of LT Distribution Panel boardmade out of CRCA sheet 3.15 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, strickering of Switcher gear about termination of switch gear, cable connector for connecting multi cables located in cable chamber terminated form the switchergear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 250 A capacity complete with powder coating, necessary internal electric connection as required and provision of the following: (DG Panel) |
| 75 | Incoming:a) LT 440 volts3 phase, 4 wire 50 cycles, 36kA, MCCB of 160 Amp rated microprocessor based complete with overload protection- 01 No Outgoing:a) LT 440 volts3 phase, 4 wire 50 cycles, 16kA, Adjustable type MCCB of 40 Amp rated complete with overload protection, no-volt thermal based release.- 04 Nos. (Fresh water panel, Goods lift - 02 Nos and spare)b) LT 440 volts3 phase, 4 wire 50 cycles, 16kA, Adjustable type MCCB of 32 Amp rated complete with overload protection, no-volt thermal based release.- 11 Nos. (13 passenger lift - 03 Nos, Booster pump panel - 04 Nos, Common area VTPN - 02 Nos, Street light and spare)c) Intelligent Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs d) LED indicating lamps with colour Red, Yellow, Blue - 01 Set |
| 76 | Supply and fixing of Compact Air Insulated design Rising main system, aluminium conductor 630 Amp 40KA(3 phases +100 %Neutral + Integral Ground Earth) 4 Nos Al bus bars and System voltage 415 Volt, AC supply, rated frequency 50 / 60Hz, with made of 1.6 mm thick sheet GI enclosure duly painted with powder coating (RAL-7032), Indoor ( IP 54 ), with provision of taping at every floors, end cover, vertical support, flange end, brackets, spring hangers, braided flexible, suspension bracket etc complete comprising of followings: |
| 77 | Supply of 630A, 4P, 40kA, IP 54Aluminium Compact Air Insulated Type Rising Main Straight Length |
| 78 | Supply of 630A End Feed Unit with 36KA/4Pole of 630A MCCB |
| 79 | Supply of 63A Plug in box with 63A,15KA ,4PoleMCCB, |
| 80 | Supply of 125A Plug in box with 125A,4Pole,36KAMCCB, |
| 81 | S&F Loop in loop out box 155x210x92 mm of FRP made with IP 65 protection of thermoplasic circuit breaker boxes with metric knockouts for cable entry and exit, of IP 66/ IP 67 for cable entry for cable exit with MCB 6 Amps, 10 kA, C Curve with terminals as bus terminals for cable with necessary fixing arrangemets and with cable glands, etc all as specified. |
| 82 | Supply and fixing LED Solar street light fitting 20 Watt with galvanized steel pole in built, lithium ion battery, solar panel, charge controller with dusk down sensor incl necessery earth and foundation work complete all as specified. |
| 83 | Supply and lay cable XLPE FRLS Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 3.5 core 500 sqmm sizecomplete all as specified and directed.Note:- (a) Earth work, sand cushioning, concrete cable covers, GI pipe protection for road crossings will be measured and paid separately. |
| 84 | Supply and lay cable XLPE FRLS Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 3.5 core 300 sqmm sizecomplete all as specified and directed.Note:- (a) Earth work, sand cushioning, concrete cable covers, GI pipe protection for road crossings will be measured and paid separately. |
| 85 | Supply and lay cable XLPE FRLS Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 3.5 core 240 sqmm sizecomplete all as specified and directed.Note:- (a) Earth work, sand cushioning, concrete cable covers, GI pipe protection for road crossings will be measured and paid separately. |
| 86 | Supply and lay cable XLPE FRLS Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 3.5 core 120 sqmm sizecomplete all as specified and directed.Note:- (a) Earth work, sand cushioning, concrete cable covers, GI pipe protection for road crossings will be measured and paid separately. |
| 87 | Supply and lay cable XLPE FRLS Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 3.5 core 35 sqmm sizecomplete all as specified and directed.Note:- (a) Earth work, sand cushioning, concrete cable covers, GI pipe protection for road crossings will be measured and paid separately. |
| 88 | Supply and lay cable XLPE FRLS Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 3.5 core 25 sqmm sizecomplete all as specified and directed.Note:- (a) Earth work, sand cushioning, concrete cable covers, GI pipe protection for road crossings will be measured and paid separately. |
| 89 | Supply and lay cable XLPE FRLS Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 4 core16 sqmm sizecomplete all as specified and directed.Note:- (a) Earth work, sand cushioning, concrete cable covers, GI pipe protection for road crossings will be measured and paid separately.( item caters for fire fighting also) |
| 90 | Supply and fix street light panel 415 V, three phase 6KW with digital 24 Hrs timer switch along with 32A TP contactor and 40A TP MCB fitting inside steel encloser including necessery arrangements for mounting on pole/wall or as directed. |
| 91 | M & L for PVC insulated and FR PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volt, conforming to IS 694, 1.5 sqmm 3 core drawn through PVC pipe with clamping materials complete all as specified . |
| 92 | Earthing |
| 93 | Earthing complete with Galvanised Steel Earth Plate Electrode 600 X 600 X 6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of Plate not less than 1.50 m below normal ground level connected to 32x6mm [Earth Lead] and GI pipe 50 mm, Medium Grade for earthing lead protection to the extent of maximum 7.5m, Earth Plate Electrode surrounded by 150mm thick packed layers of Charcoal and Common Salt filled in alternate layers, connected to the Plate by means of GI Bolts & Nuts complete all as per Electrical Plate No. 3 of SSR Part – I, connected to panel / DB including testing on completion including main earthing, Charcoal, Common Salt, PCC [1:2:4, Type B1] Pit with RCC 1:2:4, Type B1 Cover, 50 mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS frame made with 40 X 40 X 6 mm Angle Iron, MS Funnel with 20 mm bore, medium grade GI Watering pipe, wire mesh, earth work excavation, return filling, removal of surplus soil etc. complete all as specified |
| 94 | Earthing complete with Galvanised Steel Earth Plate Electrode 600 X 600 X 6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of Plate not less than 1.50 m below normal ground level connected to 4mm dia GI wire [Earth Lead] and GI pipe 15 mm, Medium Grade for earthing lead protection to the extent of maximum 7.5m, Earth Plate Electrode surrounded by 150mm thick packed layers of Charcoal and Common Salt filled in alternate layers, connected to the Plate by means of GI Bolts & Nuts complete all as per Electrical Plate No. 3 of SSR Part – I, connected to panel / DB including testing on completion including main earthing, Charcoal, Common Salt, PCC [1:2:4, Type B1] Pit with RCC 1:2:4, Type B1 Cover, 50 mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS frame made with 40 X 40 X 6 mm Angle Iron, MS Funnel with 20 mm bore, medium grade GI Watering pipe, wire mesh, earth work excavation, return filling, removal of surplus soil etc. complete all as specified (For street light pole) |
| 95 | ADD PLUG POINT |
| 96 | M&L for Point Wiring complete with 1100 Volts, FRLS Grade, 2.5 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor Cable, confirming to IS - 694 drawn through and including medium duty PVC Conduit, 20 mm dia including all accessories concealed in Walls / Roofs / Floors / Ceiling etc. and Pressed Metal Flush Box made out of GI Sheet of suitable size and required module frame with top cover, for fixing switches, fittings, regulators, blanking plates etc. concealed in walls, including 1100 Volts, FRLS Grade, 2.5 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor cable as earth continuity conductor with colour coding and connecting to Earth Dolly for for 5/6 A modular socket point on independent board complete. |
| 97 | Fire fighting System |
| 98 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, Free Standing Floor Mounted, Dust and Vermin proof PLC controlled panel board (Main for fire pumps), Compartmentalised, indoor type, fabricated with 2.0 mm thick CRCA Sheet and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 coat with matt finish after due preparation of surfaces. The panel shall consist of 500 Amps rating TPN bus bars of high conductivity Aluminium Alloy and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size, including instrumentation such as Ampere Meter, Volt Meter, Phase Indicating LED Lamps [RYB], Selector Switches etc with double stud hinged door, front openable with locking arrangement including interlocking with switch gears and suitable for 1100 Volts Grade, 3 Phase, 415 Volts, 4 Wire, 50 Hz, AC Supply and degree of protection shall be IP 54. The panel shall be fixed with angle iron frame made of angles of size 50 X 50 X 6mm at Corners, embedded 600 mm below ground level in PCC 1:2:4, Type B–1 using 20mm grade stone aggregate, 600 mm above ground level complete including connecting up with existing incoming and outgoing cables etc. and comprising the following: |
| 99 | [a] MCCB, 400 Amps, 4 Pole, 35 KA, 415 Volts, 3 Phase, AC, 50 Hz, Adjustable type complete with Overload Protection, No-Volt thermal based release – 1 Nos [Incoming][b] MCCB, 160 Amps, 3 Pole, 16 KA, 415 Volts, 3 Phase, AC, 50 Hz, Adjustable type complete with Overload Protection, No-Volt thermal based release –02 Nos (01 Nos Electric fire pump + 01 No spare).[c] MCCB, 63 Amps, 3 Pole, 16 KA, 415 Volts, 3 Phase, AC, 50 Hz, Adjustable type complete with Overload Protection, No-Volt thermal based release –03 Nos (02 Nos Jockey pump + 01 Spare).[d] Star delta starter suitable for electric driven fire fighting pump 01 No & Star delta starter for jockey pump - 02 No.[e] Auto/ Manual start wrt pressure switch with indications.[f] LED Voltmeter & Ammeter of suitable capacities with selector switches & CTs. |
| 100 | Supplying and laying ductile pipe with flanged type centrifugally cast(spun) class K-9 of 150 mm dia pipe conforming to IS-8329 including provision of specials, such as tees, elbows,bends reducers, taper pieces, including testing and commissioning. |
| 101 | S&F LED EXIT sign/light double sided with battery back up for min 2 hrs complete with all accessories as directed. |
| 102 | Supply and install Fire Extinguisher CO2 Type light weight squeeze grip type confirming to IS:15683 of capacity 4.5 kg all as specified and directed.Note: (i) Fire extsinguisher should equiped with hose of appropriate size and open-close should be with the help of wheel type valve.(ii) Fixing arrangement to wall will be included in the quoted rates. |
| 103 | supply and install Fire Extinguisher ABC Type light weight squeeze grip type confirming to IS:15683 of capacity 6.0 kg all as specified and directed.Note: (i) Fire extiguisher should equipped with hose of appropriate size and open-close should be with the help of wheel type valve.(ii) Fixing arrangement to wall will be included in the quoted rates. |
| 104 | Supply and install Fire Extinguisher Mechanical Foam Type light weight squeeze grip type confirming to IS: 15683 of capacity 9.0 kg all as specified and directed. Note: (i) Fire extinguisher should equiped with hose of appropriate size and open-close should be with the help of wheel type valve.(ii) Fixing arrangement to wall will be included in the quoted rates. (iii) Appropriate size of sign board should be hanged from wall/roof near all fire pints. |
| 105 | Supply and install Fire Extinguisher wet chemical Type light weight squeeze grip type confirming to IS: 15683 of capacity 9.0 Kg all as specified and directed. Note: (1) Fire extinguisher should equiped with hose of appropriate size and open-close should be with the help of wheel type valve.(2) Fixing arrangement to wall will be included in the quoted rates. (3) Appropriate size of sign board should be hanged from wall/roof near the all fire pints. |
| 106 | M&L for designing testing installing commissioning of fixed type wet chemical fire suppression system at 01 nos kitchen/cook house in 1st floor for approx 5 x 1 mtr size kitchen hood incl complete automatic fire detection system comprising of pressure switch, heat detection sensor, manual release switch, discharge nozzle, wet chemical cylinders, alarm, exit sign, fire cable, hooter, control panel etcall as specified and directed.Note: Design/calculations and dwarings of system is to be submitted and approved by accepting officer before placing order. |
| 107 | Supply and install water mist cum compressed air foam system (CAFS) based fire extinguisher of 50Ltr capacity, trolley mounted, having EN: 3-7 approval with PESO approved pressure vessel complete all as directed. |
| 108 | Fire Alarm |
| 109 | Supply and fix 2 core 1.5 sqmm FRLS armoured copper cable as per IS:1554to wall/ roof/ false ceiling/ floors with necessary clamps/ saddles all as specified and directeed. |
| 110 | ELECTRIC CHIMNEY |
| 111 | Design, commissioning , testing of electric chimney for kitchen of 60 x 60 x 30 inches stainless steel sheet with oil filter 20 gauge sheet 304 GI ducting, angle frame, threding rods, nuts bolts alongwith damper suitable blower with starter suitable 15 stoves and panelling for all items fixing outer GI sheet ducting box type bottom to top (1st floor to 13 floor) 22 gauge GI Sheet and top bend corner with blower motor connecting GI sheet box type 13 floor outer ducting panel, 3 HP XL fan 960 RPM, 3 Phase Automatic running motor with starter complete all as specified and directed |
| 112 | S&F Cable PVC insulated sheathed LT 1100 V grade with copper conductor of size 3 core 10 sqmm multi stranded conductor laid in ground fixed to wall roof etc with suitable calmps spacers bolts nuts etc all as spcidied and as directed |
| 113 | AVIATION LIGHT |
| 114 | S & F Aviation obstruction light LED type filament-less bulb with 10 Watt bulb complete including standard fixing arrangements all as specified and as directed. |
| 115 | M & L for PVC insulated and FR PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volt, conforming to IS 694, 1.5 sqmm 3 core drawn through PVC pipe with clamping materials complete all as specified |
| 116 | S&F Loop in loop out box 155x210x92 mm of FRP made with IP 65 protection of thermoplasic circuit breaker boxes with metric knockouts for cable entry and exit, of IP 66/ IP 67 for cable entry for cable exit with MCB 6 Amps, 10 kA, C Curve with terminals as bus terminals for cable with necessary fixing arrangemets and with cable glands, etc all as specified. |
| 117 | Supply and fix street light panel 220 V, single phase 6KW with digital 24 Hrs timer switch along with 32A TP contactor and 40A SPN MCB fitting inside steel encloser including necessery arrangements for mounting on pole/wall or as directed. |
| 118 | PVC CONDUIT |
| 119 | Supply and fix Rigid non-metallic PVC conduit of size 20 mm dia exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc including GI wire for wiring of TV/telephone cable concealed in wall or clamped on wall all as specified and directed. |
| 120 | Supply and fix Rigid non-metallic PVC conduit of size 32 mm dia exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc including GI wire for wiring of TV/telephone cable concealed in wall or clamped on wall all as specified and directed. |
| 121 | Supply and fix telephone/data sockets(Jack type) RJ 45 with shutter 1 module complete with all acessories like flushed box and cover plate all as directed. |
| 122 | Supply and fix TV co-axial socket 1 module complete with all acessorieslike flushed box and cover plate all as directed. |
| 123 | COOLING APPLIANCES |
| 124 | Supply and fix refrigerator, electric driven (single phase), approx capacity 450 Litres, double door with smart inverter compressor BEE star rated complete all as specified and directed. |
| 125 | Supply and fix deep freezer glass top 405/425ltrs capacity having double door single phase 240 volt, 50 Hz complete all as specified and directed |
| 126 | Supply and installed water cooler electric driven (single phase) having approx storage capacity of 120 litres and nominal cooling capacity of 60 litre per hour. |
| 127 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 Vto 250 V with output voltage stabilized at 230 Vwith accuracy of ± 2.5% and of capacity 2.0 kVA or as directed. |
| 128 | Lift |
| 129 | Design supply, install testing & commissioning passengers lift, speed 1.5 metre/sec, lift with single speed motor 415 volts, 3 phase, AC 50 Hz supplyconforming to IS 14665, suitable to serve S + 13 upper floors carry 13 passengers (544kg)with AC Variable Voltage & Variable Frequency drive (VVVF drive) complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, centre opening doors with door drive (electric motor driven mechanism), sliding stainless steel doors, automatic rescue device (ARD) system, 3D infra red sensor in full height of door & built in announcing system without hand set (03 Nos, one each in car, Machine room & near Ground floor landing door) complete all as specified (S+13 floors) |
| 130 | Design, supply, install, testing & commissioning firemen lift (1000Kg), speed 1.5 metre/sec with single speed motor, 415 volts, 3 phase AC 50 Hz supply, conforming to IS-14665 and as amended, suitable to serve S+13 upper floors with AC Variable Voltage & Variable Frequency Drive (VVVF drive) complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, centre opening doors with door drive (electric motor driven mechanism), sliding stainless steel doors, automatic rescue device (ARD) system, 3D infra red sensor in full height of door & built in announcing system without hand set (03 Nos, one each in car, Machine room & near Ground floor landing door) complete all as specified all as specified (S+13 floors) |
| 131 | M & L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated location for loop earthing etc. with GI strip 32x6mm. |
| 132 | DG SET |
| 133 | Supply installation testing and commissioning of Silent engine generating set with acoustic enclosure as per CPCB norms IV 415 volts 125 KVA 3 phase 0.8 power factor 50 Hz, 1500 RPM self excited self regulated brushless AC generator including acoustic enclosure suitable for ambient condition and conforming to condition under IS 4722, BS 5514/ 2613 /5000 with and including the following:-(i) The capacity of Generator set shall be net after all due de-rating factors as per relevant ISI design.(ii) Rate quoted shall be deemed to be inclusive of cable and terminations form Generator to the AMF Panel, with necessary holes to wall including making good to disturbed surfaces so as to match with the existing finishes all as specified and directed.(iii) The quoted rate shall be deemed to be inclusive of first fill of oil and final successful acceptance test.(A) Alternator :-Standard design alternator rated at 125 kVA net output at site after considering de-rating as per site conditions at 0.8 (lag) power factor AC,3 - phase 4 - wire 415 volts 50 Hz, 1500 RPM, self excited self regulated screen protected drip proof IP 23 enclosure brushless design with winding in pole faces, insulating class \"H\" and voltage regulation of+/- 1% at rated voltage from no load to full load. The alternator shall be conforming to BS 2613/5000 and shall be imposition to generate supply with frequency regulation with in +/- 1% tolerance. The alternator will be suitable for tropical climate and shall generally conform to BS - 2613/5000/ IS – 4722.i) Insulationclass - \"H‘ii) Temperature rise Class - \"H‘iii) Excitation : Self Excited |
| 134 | iv) Regulation performance: The voltage is kept constant with +/- 1%, manual voltage adjustment within +/- 5%v) Frequency regulation +/- 1%(B) Diesel Engine: - Adequate capacity of Diesel engine as approved by GE basing on manufacturers technical details water cooled to drive independently above alternator and after considering de-rating as per site conditions after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylinder multi stroke direct injection, cold starting 1500 RPM, as per relevant ISI/BS - 5514 with an overload capacity of 10% for one hour in 12 hours continuous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as underi)Fly wheel with housing.ii) Cooling system :- Moulded radiator with fan & beltsiii) Cooling Water pump : - Centrifugal type belt driveniv) Exhaust System :- Exhaust System complete with exhaust piping ofsuitable size with MS pipe light grade up to & outside and 1meter away from the enclosure, covered with asbestos rope and aluminium foil of 28 SWG complete with in the enclosure for safe exhaust without transforming vibration to the wall of the enclosure. Exhaust gas turbo charger type. Exhaust manifold, Silencer : Residual type Bellowsv) Fuel System :- Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by electronic governor for 1% speed /frequency regulation, Fuel filters,Fuel hoses.vi) Lubricating oil System : Lubricating oil filter Lubricating oil pump |
| 135 | vii) Air Intake System :Air intake ManifoldAir cleaner dry typeviii) Governor :- Electronic Governorix) Starting System :- Electric Self starter with maintenance free battery including battery charging alternatorx) Batteries :- Batteries of maintenance free of capacity as recommended by the manufacturer complete with copper conductor multi stranded leads of suitable length fromself starter to the battery terminals complete with initial charge and initial fill of electrolyte all as specified and Starter gear ring Start and stop push button, Ignition key / Switch Handling and operation : Salient features of accessories shall be as under: Radiator with blower fan Corrosion inhibitor coolant Paper element filters for fuel, Lubricating oil and by pass Electronic governor controlled direct fuel injection system Fly wheel housing and fly wheelxi) Generator Monitoring Panel : - Comprising of all standard items as mentioned under this schedule or as per standardpractice ignition key switch and start / stop arrangement, indications for Engine parameters, hour run meter, RPM meter, Engine oil pressure indicator, water/coolant Temperature indicator, Battery volt display.xii) Safety Controls : - Engine low lubricating oil pressure high water Temperature and over speeding of engine.xiii) Coupling arrangement : - Flexible coupling, fly wheel to suit flexible coupling.xiv) Accessories :- AVM Pads built in enclosure and for entire unit on platform.xv) Base Frame : - Should be provided as OEM norms |
| 136 | C) AMF Panel :- Factory made control panel made out of CRCA sheet dust and vermin proof, within DG enclouser of 415 volts 3 -phase4 - wire AC 50 Hz, including powder coated, copper bus bar of one and half times the rated load 125 KVA alternator complete with internal wiring with PVC insulated single core copper conductor multi stranded wire of 1100 volts grade of suitable capacity, fuses, name plates consisting of 4 pole MCCBs and Contactors of capacity as recommended by the manufacturer. Detachable cable gland plates, all controls, multifunction meter for indicating voltage, current, frequency, kWH, pf, etc.Controls :-a) Load on Indicationb) Load off indicationc) Engine start push buttond) Engine stop push buttone) Fault accept / reset push buttonf) Battery Charger : (i) Transformer (ii) Rectifier (iii) Resistance (iv) DC Volt meter (v) DC Ammeter (vi) Charger rate selector switch |
| 137 | D) acoustic Enclosure:-Manufactured by OEM suitable for 125 KVA DG Set (i) NAL approved as per CPCB - IV(ii) It Should be as per latest rules and regulations of Ministry of Environment and Forest and Pollution control board(iii) The generating setbatteries and control panel should be inside the enclosure.(iv) Construction Details/specification are as follows:a) Outer body :- CRCA Sheet of 1.6mm thickb) Doors :- CRCA sheet of 1.6 mm thickc) Sound Insulation :- As per OEM Normsv) The acoustic should be composite in construction and fully assembled integral unitvi) The batteries should be placed inside the enclosure beside the DG Set on a suitable insulatedplat formvii) The DG Set should be provided with external Emergency stop push button |
| 138 | viii) The enclosure should be suitably illuminated by LED Lamp fittings.ix) The noise level should be 75 dba at 1m under free field conditions.x) The acoustic enclosure parts shall be of powder coated after pre treatment process. The powder coating shade should be Gen set Green. The base frame should be painted with epoxy based black shadeE) The coated rate includes excavation, removing of soft soil and PCC, Cement Concrete foundation, filling and mass concrete type B2 (1:2:4) using 40 mm graded aggregate of suitable size for placing of DG Set as per OEM recommendation complete all as specified and directed. |
| 139 | ARBORICULTURE |
| 140 | Supply & Planting Local Grass carpet( GRIHA approved ) including preparation of ground upto 30cm deep and filling soft soil, cow dung and watering etc complte all as specified and as directed.(NOTE :- Loose soil and cow dung will be measued separately). |
| 141 | Supply & Planting Ashoka Plantincluding preparation of ground upto 30 cm deep and filling soft soil, cow dung and watering etc complete (loose soil and cow dung will measue separately). |
| 142 | Supply & Planting Royal Palm treeincluding preparation of ground upto 30 cm deep and filling soft soil, cow dung and watering etc complete (loose soil and cow dung will measue separately). |
| 143 | Supply & Planting Neem treeincluding preparation of ground upto 30 cm deep and filling soft soil, cow dung and watering etc complete (loose soil and cow dung will measue separately). |
| 144 | Supply & Planting Jamun/Ravi treeincluding preparation of ground upto 30 cm deep and filling soft soil, cow dung and watering etc complete (loose soil and cow dung will measue separately). |
| 145 | Supply of vermicompost /cow dunk of best quality complete as per gardening practice as directed |
| 146 | Supply of Best quality soil ( sweet earth) for plantation complete all as spcified and as directed. |
| 147 | PILE FOUNDATION |
| 148 | Boring for bored cast-in-situ piles 900mm dia. in any type of soil/clay/ mud using DMC (Direct Mud Circulation) method of boring and getting out and disposal of spoil out side MD land complete all as specified and as shown on drawings and as directed |
| 149 | Boring for bored cast–in–situ piles 900mm diainhard rock/ weathered / fractured rock using DMC (Direct Mud Circulation) method of boring and getting out and disposal of spoil out side MD land complete all as specified and as shown on drawings and as directed |
| 150 | Carrying out initial compressive load test on 900mm dia. pile as per IS 2911 Part-IV, complete all as specified and as directed. |
| 151 | Carrying out initial lateral load test on 900mm dia. pile as per IS 2911 Part-IV, complete all as specified and as directed. |
| 152 | Carrying out low strain integrity test on bored cast in situ piles of 900mm diaincluding analysing the result as per ASTM D 5882 and as directed. |
| 153 | Carrying out routine compressive load test on 900mm dia. pile as per IS 2911 Part-IV, complete all as specified and as directed. |
| 154 | Carrying out routine lateral load test on 900mm dia. pile as specified in IS, complete all as specified and as directed. |
| 155 | SCHEDULE \"A\" PART-XVIII: Outsourcing Services for Operation of Lifts for the First Year of the two year Defect Liability Period: |
| 156 | Outsourcing of services for operaion of passenger lifts (5 Nos. i.e. 3 Nos. Passenger Lifts & 2 Nos. Firemen Lifts) any type and make to serve S+13 floors, during First Year of the two year Defect Liability Period by providing services of Two Lift Operators (Semi Skilled) per Shift in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge (Shift Details: 365 Days x 1 Building x 2 Shifts x 2 Operators=1460 Shifts). |
| 157 | SCHEDULE \"A\" PART-XIX: Outsourcing Services for Operation of Lifts for the Second Year of the two year Defect Liability Period: |
| 158 | Outsourcing of services for operaion of passenger lifts (5 Nos. i.e. 3 Nos. Passenger Lifts & 2 Nos. Firemen Lifts) any type and make to serve S+13 floors, during Second Year of the two year Defect Liability Period by providing services of Two Lift Operators (Semi Skilled) per Shift in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge (Shift Details: 365 Days x 1 Building x 2 Shifts x 2 Operators=1460 Shifts). |
| 159 | SCHEDULE \"A\" PART-XX: Outsourcing Services for Operation of Lifts and Comprehensive maintenance of Lifts for the First Year after Defect Liability Period: |
| 160 | Outsourcing of services for operaion of passenger lifts (5 Nos. i.e. 3 Nos. Passenger Lifts & 2 Nos. Firemen Lifts)any type and make to serve S+13 floors, during First Year after expiry of Defect Liability Period by providing services of Two Lift Operators (Semi Skilled) per Shift in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge (Shift Details: 365 Days x 1 Building x 2 Shifts x 2 Operators=1460 Shifts). |
| 161 | Comprehensive mainenance of passenger lift, 3 Nos., with capacity of 13 passengers (884 Kg) to serve S+13 floors complete including ARD and all connected components of lift during First Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge. |
| 162 | Comprehensive mainenance of fireman lift, 2 Nos., with capacity of 1020 Kg to serve S+13 floors complete including ARD and all connected components of lift during First Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge. |
| 163 | SCHEDULE \"A\" PART-XXI: Outsourcing Services for Operation of Lifts and Comprehensive maintenance of Lifts for the Second Year after Defect Liability Period: |
| 164 | Outsourcing of services for operaion of passenger lifts (5 Nos. i.e. 3 Nos. Passenger Lifts & 2 Nos. Firemen Lifts)any type and make to serve S+13 floors, during Second Year after expiry of Defect Liability Period by providing services of Two Lift Operators (Semi Skilled) per Shift in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge (Shift Details: 365 Days x 1 Building x 2 Shifts x 2 Operators=1460 Shifts). |
| 165 | Comprehensive mainenance of passenger lift, 3Nos., with capacity of 13 passengers (884 Kg) to serve S+13 floors complete including ARD and all connected components of lift during Second Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge. |
| 166 | Comprehensive mainenance of fireman lift, 2 Nos., with capacity of 1020 Kg to serve S+13 floors complete including ARD and all connected components of lift during Second Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge. |
| 167 | SCHEDULE \"A\" PART-XXII: Outsourcing Services for Operation of Lifts and Comprehensive maintenance of Lifts for the Third Year after Defect Liability Period: |
| 168 | Outsourcing of services for operaion of passenger lifts (5 Nos. i.e. 3 Nos. Passenger Lifts & 2 Nos. Firemen Lifts)any type and make to serve S+13 floors, during Third Year after expiry of Defect Liability Period by providing services of Two Lift Operators (Semi Skilled) per Shift in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge (Shift Details: 365 Days x 1 Building x 2 Shifts x 2 Operators=1460 Shifts). |
| 169 | Comprehensive mainenance of passenger lift, 3 Nos., with capacity of 13 passengers (884 Kg) to serve S+13 floors complete including ARD and all connected components of lift during Third Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge. |
| 170 | Comprehensive mainenance of fireman lift, 2 Nos., with capacity of 1020 Kg to serve S+13 floors complete including ARD and all connected components of lift during Third Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge. |
| 171 | Notes for Outsourcing Services Items:(i) The lift shall be operated daily in two shifts as directed by the Engineer-in-Charge.(ii) The timings for two shifts of 8 hours each daily i.e. First shift shall be from 0630 hours to 1430 Hours and Second Shift shall be from 1430 Hours to 2230 Hours.(iii) In case of non-function of passenger lift, the Goods Lift installed in the same building shall be operated as directed.(iv) The work shall be supervised by adequately qualified supervisor with relevant experience of minimum 5 years items under BoQ shall be deemed to be including the same.(v) The unit rate is deemed to include for maintaining log books, record of repair/replacement of perished/unserviceable, minor adjustments, minor repairs of all accessories, cleaning/up keeping of lift and surrounding area as directed by the Engineer-in-Charge.(vi) One emergency light and necessary tools shall be available in a tool box with the operator in the shift for smooth functioning of lifts.(vii) Conveyance and communication system like mobile phone etc. shall be provided by the Bidders/Service providers to all Lift Attendants/Supervisors.(viii) The Bidders shall ensure house keeping, environmental cleanliness of area all round the lift and the area shall be kept absolutely neat and clean. The lift attendant shall clean the Lift car cabin, all landing floors and tiles all round lift doors with necessary cleaning material such as cotton cloth and cleaning solution etc. |
| 172 | (ix) The Bidders shall abide by the latest Labour rules and minimum wages Act.Wages paid by the bidders to the persons employed shall not be less than the minimum wages fixed by the state/central government from time to time whichever is higher. The Bidders shall also insure the workmen employed on the job.(x) The Bidders is responsible for insurance, EPF, ESI, Bonus, Labour welfare cess et., as applicable and shall be paid to the workmen as per existing Labour rules/ Acts/ regulations and rate quoted shall be deemed to be included for the same.(xi) Dress Code: The bidders shall provide the workmen with Dark Blue Colour uniform {formal pant & T-shirt} with labels showing/ printed i.e. “Name of the firm and designation” on front and on the back of the T-shirt along with protective clothing/gear. The bidders shall also provide shoes to the workers and the persons shall not be allowed to enter the work site without wearing shoes.(xii) INSURANCE: The Bidders shall be responsible for all Accidents/Injuries happening to the workmen. Any accident causing minor/fatal injury, partial disability due to any untoward incident or non-adherence to safety and IE regulations or fault in maintaining of internal electric supply system or on account of any mishandling/ wrong operation/ lack of knowledge of safety precautions or on account of any circumstances beyond his/ their control, the bidders shall be solely responsible for settling all claims of compensation to the deceased, falling which department will have a right to recover any sum indicated/ claimed by Labour commissioner/court authorities. No claim whatsoever will be entertained in this regard. No compensation is payable by the department on this account. Bidders shall provide first aid boxes to meet any emergency situations.(xiii) The rate quoted by the bidders shall be deemed to be including Basic rate (Minimum Wages as notified by Government of India/ State Government/ Local body, whichever is higher), employers contribution towards Employees Provident Fund (EPF) liability, contribution towards Employees State Insurance Corporation (ESIC), contribution towards Bonus. Overhead and profit and labour welfare cess (LWC) as applicable depending upon the manpower requirement. This will create onus on the Bidders to applicable depending upon the man power requirement. This will create onus on the bidders to ascertain the relevant rates and quote accordingly. The rates quoted shall be inclusive of all taxes, cess, levies are applicable including GST. Note: The Manpower deployed shall be changed for every 11 months period. The rate quoted deemed to be inclusive for the same. |
| 173 | (xiii) The rate quoted by the bidders shall be deemed to be including Basic rate (Minimum Wages as notified by Government of India/State Government/Local body, whichever is higher), employers contribution towards Employees Provident Fund (EPF) liability, contribution towards Employees State Insurance Corporation (ESIC), contribution towards Bonus. Overhead and profit and labour welfare cess (LWC) as applicable depending upon the manpower requirement. This will create onus on the Bidders to applicable depending upon the man power requirement. This will create onus on the bidders to ascertain the relevant rates and quote accordingly. The rates quoted shall be inclusive of all taxes, cess, levies are applicable including GST. Note: The Manpower deployed shall be changed for every 11 months period. The rate quoted deemed to be inclusive for the same. |
| 174 | Notes for Comprehensive Maintenance Items:(i) Comprehensive maintenance consists of preventive and breakdown services including replacement of material and labour for major/minor spare parts and consumables like topping of Oils/grease/door rollers/ relays/door belts/gate lock contacts and hardware like bolts and nuts including load testing of lift for satisfactory performance once in a year complete and rate quoted by the tenderer includes for the above Lifts.(ii)Preventive maintenance consists of carrying out routine check by skilled personnel as specified in Particular specifications and as directed by Engineer-in-Charge and lubricating to all moving parts, topping parts, topping up of oils as per Lubrication Chart including Material and labour for all consumable and major/minor spare parts.(iii)Breakdown maintenance consists of attending to the faults that may occur and carrying out necessary repairs to electrical, control circuits and mechanical components including materials & labour for all minor & major spare parts and consumables of the lift that may occur during the operation.(iv) Fortnightly, quarterly maintenance registers shall be maintained and signed by the site engineer and contractor.(v) Load testing shall be arranged by the contractor to the Lift for which repairs were carried out as and when directed by Engineer-in-Charge.(vi) All maintenance works shall be carried out by well qualified tradesmen and supervisor of OEM.(vii) The quoted rate shall be deemed to be included the above aspect and for consumables such as timely toping up oils, acrylic covers, fuses, grease, waste cotton, stationery and other miscellaneous items and all minor & major spare parts. |
| 175 | (viii) The tenderer shall submit MoU from the original manufacturer of the lift for comprehensive maintenance to undertake comprehensive maintenance during and after Defects Liability Period directly or through their nearest authorized/accredited agencies service personnel.The MoU shall be submitted at least 06 months prior to issue of completion certificate of main contract as per Work Order No I. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail