| 1 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation of poles, stays, laying of pipes etc and getting out in hard/dense soil (including Road Cutting) complete all as specified and directed. |
| 2 | Returning, filling in, including spreading, levelling watering and well ramming in layers not exceeding 25cm in soil complete all as specified and directed. |
| 3 | Removing excavated material to a distance exceeding 250m but not exceeding 500m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed. |
| 4 | Supply and fixing in repairs heavy grade GI pipe 80 mm dia bore with all fittings, laid in trenches/walls, including applying two coats of synthetic enamel paint (red colour) on the external surface over one coat of red oxide primer, complete all as specified and directed by the Engineer-in-Charge. |
| 5 | Supply and fixing in repairs heavy grade GI pipe 50 mm dia bore with all fittings, laid in trenches/walls, including applying two coats of synthetic enamel paint (red colour) on the external surface over one coat of red oxide primer, complete all as specified and directed by the Engineer-in-Charge. |
| 6 | Demolition of Existing concrete supporting block of pumps and motor, exceeding 15 cm of thickness above and below ground level all specified and directed by Engineer-in-Charge. |
| 7 | M&L cement concrete 1:2:4, type B-2 ( using 40 mm graded stone aggregate) asinsupport of Base frame with MS bolts placed in concrete and hardstanding finishing even and fair without extra cement all as specified. |
| 8 | Taking out damaged and unserviceable MS pipe sections from existing fire lines (suction and delivery), and supply and fixing heavy-duty ISI-marked MS pipe, including welding, welding of flanges, nuts and bolts, complete all as specified and directed by the Engineer-in-Charge, for the following sizes: |
| 9 | MS pipe 100mm bore |
| 10 | MS pipe 150mm bore |
| 11 | S&F in replacement of sluice valve (ISI Marked) 150 mm, both ends flanged, with high-tensile stainless-steel spindle, body conforming to IS-14826, ISI marked, PN-1.6, including all jointing materials such as rubber/fibre board, nuts, bolts, washers etc., complete all as specified. |
| 12 | S&F in replacement of sluice valve (ISI Marked) 100 mm, both ends flanged, with high-tensile stainless-steel spindle, body conforming to IS-14826, ISI marked, PN-1.6, including rubber/fibre board joints, nuts, bolts, washers etc., complete all as specified. |
| 13 | S&F in replacement of Non-Return Valve (NRV) 100 mm (ISI Marked), both ends flanged, with high-tensile brass spindle, ISI-marked body, including all joints with rubber/fibre board, nuts, bolts, washers etc., complete all as specified. |
| 14 | Construction of brick masonry valve chamber in repair of size 1 x 1 x 1 m3 (internal dimension) (above GL 3.30 metre) suitable for fixing of sluice valves, 15cm thick foundation using PCC 1:4:8 type D-2 over 15cm thick hardcore of broken stone, 23cm thick brick walls built in cement and mortar 1:4, 15mm thick internal and external plaster including top of floor in cement and sand mortar 1:3, 15mm thick, finished even and smooth, without using extra cement,5 mm thick plate cover on 50mm x 50mm x 6mm MS angle frame embedded in PCC 1:2:4 type B-1 coping, having rectangular, hinged, opening of size 150 x 100mm with locking arrangements , hold fasts, etc, applying one coat of red oxide primer and two coats of synthetic enamel paint to all steel surfaces and earth work in any type of soil including disposal of debris outside MD land complete all as specified. |
| 15 | Supply and fixing in replacement of fire hydrant valve, single-headed, gun-metal construction, suitable for 80 mm dia pipe, including rubber packing, nuts, bolts and all necessary fittings, complete all as specified and directed by Engineer-in-Charge. |
| 16 | Supply and fixing in replacement of fire hydrant valve, double-headed, gun-metal construction, suitable for 100 mm dia pipe, including rubber packing, nuts, bolts and all necessary fittings, complete all as specified and directed by Engineer-in-Charge. |
| 17 | Supply & fixing in repair Fire Brigade inlet connection 2 way gun metal including rubber packing, nut bolt complete all as specified and as directed by Engineer-in-Charge. |
| 18 | M & L in replacement for fabrication of external fire hose cabinets of with 2mm thick CRCA sheet, corrosion resistance and powder coated supported angle iron 50 x 50mm x 6mm size, front opening facility with front double door fixed with 6mm clear wired glass sections and rubber gaskets, locking arrangement and fixing provn of hose reel of 30mtr- 2 No\"s and fire hydrant nozzle - 2 No\"s headed inside the cabinet including powder coated finishing, grouting fixing etccomplete all as specified and as directed by Engr-in-Charge. |
| 19 | Supply & Fixingin replacement of external fire hose cabinet, rubberized fabric reinforced rubber lined fire hose (RRL Hose)including gun metal male and female instantaneous type of coupling hoseconforming to IS636 typeII and coupling conforming to IS 903-1975 in all respect30 metre long complete all as specified and as directed by Engr-in-Charge. |
| 20 | Supply and Fixing in replacement branch pipe nozzle gun metal 63 mm instantaneous inlet, made threaded outlet, 15 mm bore nozzle long type. |
| 21 | Supply and Fixing in replacementHose reel , corrosion resistance, withrubberhose 30 mtr long including tapping 25 mm from 150 mm pipe line MS pipeby welding complete all as specified and as directed by Engr-in-Charge. |
| 22 | Supply and Fixingin replacement Gun Metal Gate Valve (ISI Marked) heavy duty suitable for 25 mm dia bore pipe lines complete all as specified and as directed by Engr-in-Charge. |
| 23 | Supply & Fixin replacement gun metalAir release valve(ISI Marked) 25 mm size complete all asspecified and as directed by Engr-in-Charge. |
| 24 | S & F in replacement rotational moulded polyethylene water storage tank 2000 Ltr capacity, (cylindrical vertical with closed top) including all connections for inlet, outlet, overflow and washout pipes etc hoisted and fixed in position at G+2 building on terrace including making PCC foundation old thickness not less than 200mm base for water tank complete all as specified. |
| 25 | Supply and fix in replacement foot valve ball type of size 200mm dia complete all as specified and as directed by Engineer-in-Charge. |
| 26 | Supply and fix in replacement foot valve ball type of size 100mm dia complete all as specified and as directed by Engineer-in-Charge. |
| 27 | Comprehensive maintenance of all fire hydrant both single and double type, centrifugal pump set of 70 HP -2 No\"s, 75 HP-2 No\"s 15HP booster pump -8 No\"s, fire hose, reel drum, gate valve, lugs, rubber washer of hydrant , pressure switch and other connected accessories including greasing and oiling for smooth operation of all hydrant, butterfly valves, pump, motor gland packing, sluice valve, hose reel, fire brigade connection , Hose box and keys and connected accessories including supply and replacement of unserviceable minor part like inlet blank cap, chain , rubber seal, seal, O ring, washers, gland packing such that there should noleakage of water during pressure test of minimum 3.5 Kg/cm2 and easy fixing of male nozzles toanyone of the hydrant valves mentioned above all as specified and directed by Engineer-in-Charge. Note :- Pressure test should be done in presence of user reprenstative and obtain signed that all fire hydrant are in serviceable condition. |
| 28 | S&F in replacement of MK2, FASD starter of capacity suitable for 15 HP pump set, 415, 3 phase including connection of motor cable to starter and testing all as specified and directed. |
| 29 | -Ditto- of item No 28 but suitable for 70/75HP pumpsets |
| 30 | M&L for disconnecting centrifugal pump from motor, suction and delivery pipe line ofany Make, model and taking downpacking for removing and insertion of new shaft sleeves replacementsor remove Bearing of replacement of mechanical seal and other connected parts using bearing puller gear and fix new bearing and greasing allparts, coupling pumpto motor and check forproper shaft alignments such that novibration produce duringoperation of following capacity pumps. NOTE : Pump Bearing will be paid separately. |
| 31 | Pump coupled with 75 HP motor |
| 32 | Pump coupled with 70 HP motor |
| 33 | pump coupled with 15/30 HP motor |
| 34 | Supply of high performance Bearing suitable for motor and pump of capacity 70/75 HP, 701 HP Make:SFC/NBC |
| 35 | Supply of high performance Bearing suitable for motor and pump of capacity 15 HP, 20 HP, 30 HP Make:SFC/NBC |
| 36 | S&F in repair AC-3 type contactor with control voltage of 230V AC with integrated auxillary or Add on block contacts with 1 or 2 No and NC including connection of control wiring to contactor and testing of starter after repairing :- |
| 37 | Contactor rating of 12A |
| 38 | Contactor rating of 18A |
| 39 | Contactor rating of 25A |
| 40 | Contactor rating of 40A |
| 41 | Contactor rating of 70A |
| 42 | S&F in repair Thermal over load relay with adjustable setting with integrated auxillary or Add on block contacts with 1 or 2 NO and NC including connection of control wiring to Over Load Relay and testing of starter after repairing |
| 43 | Over Load Relay of capacity suitable for 70/75HP motor |
| 44 | Over Load Relayof capacity suitable for 30HP motor |
| 45 | Over Load Relayof capacity suitable for 15HP motor |
| 46 | M&L for disconnecting motor power cables of various sizes from electrical motor of different capacities and decoupling from the pump sets, removing and taking down carefully and transporting to authorised workshop, dismantling stator and rotor carefully and rewinding stator assembly with supper enamelled copper winding wire of suitable gauge matching to existing gauge and cleaning of slots, core with carbon tetra chloride solution and apply two coats of insulation varnish and keep stator assembly in heating chamber to improve insulation strength, reassemble motor completely and transportation to site, coupling pump to motor and check for proper shaft alignments such that no vibration produce during operation coupling to pump with exact alignment, connect power cables to motor and testing of followingcapacity motor :- |
| 47 | 75/70 HP |
| 48 | 20 HP |
| 49 | 15HP |
| 50 | Material and Labour for repairs/maintenance of automatic/manual fire pump starter control panel, automatic operation based on pressure sensor , protection against dry run of pump, in replacement, indoor type, Aluminium bus bar with colour coded heat shrinkable sleeves , IP 43 protection class, factory fabricated , cubical panel, wall mounted , self supported, made out of 2mm thickCRCA sheet with locking arrangement, one sides openable, dust vermin proof suitable for 3 phase 4 wire 415 Volt 50 Hz AC including suitable size copper insulated conductor control wiring, current transformer, 3 phase indication lamps for incoming on/off, pump on/off indication,3line multi function digital multi meter andpowder coating connecting the cable with necessary cable glands, lugs etc for all incoming & outgoing cables proper arrangement for ventilation, making necessary alterations to existing GI pipe forholding pressure gauge, sensor and gate valve for on/off sensor and accommodating the following items all as directed & specified by engineer-in-charge. Panel consist of following items (a) 415V, 63 A main MCCB 4P Ics = 100%Icu, Rupturing capacityof 36 KA-1 no\"s.(b) FASD starter suitable for 15 HP motor - 01 No\"s(c) Pipe mounted pressure switches pressure gauge - 02 Nos and control wiring from sensor topanel for auto on/off of pump.(d) Flush Mounted multifunction meter with 3 line LED display of accuracy class 1-1 No\"s Make : L&T Model No 4405 series or equivalent model.(e)All other necessary sensors, wiring, accessories required for auto/manual operation of above panel should be include in quoted rates. |
| 51 | Material and labour for painting of externalfire hose cabinets, Fire lines etc withone coats of synthetic enamelpaint colour red on external surfaces, one coat of red oxide primer after preparation of surfaces complete all as specified and directed by Engineer-in-charge. |
| 52 | Supply and fixingin replacement of damaged glass wired glass panes 6 mmthicksuitable for existing fire cabinet outdoor/indoor type complete all as specified and directed by Engineer-in-charge. |
| 53 | Provision of full rehearsal/drill of fire fightingpractice by opening the sluice valves, hydrant and landing valves, fixing of hose reel, checking serviceability of fire brigade inlets and other work required for thepractice including required manning and instructed by Engineer-in-Charge and provisioning of washers for hydrants.Note : Penalty at therate of Rs. 5000 perbuilding per month shall be imposed on the contractor in fire fighting practice is not carried out during a month. |
| 54 | Taking down existing Fire Control Panel and Supply &Installation, Testing & Commissioning of microprocessor-based, networkable analogue addressable 2-loop Fire Alarm Control Panel (expandable up to 128 nodes), with 7\" touchscreen LCD, 02 Nos network cards, suitable to accommodate addressable intelligent wireless devices via translator, each loop capable of 127 devices + 127 base sounders/beacons, with minimum 10,000 event log history, 3 access levels, EN-54/LPCB approved devices compatible, supporting minimum 5000 cause & effect entries and up to 20,000 inputs & 20,000 outputs across network, complete with EPROM, programmable relay controls for sprinkler and hydrant pumps, 240V AC supply, automatic charger, 24V sealed lead-acid batteries for 24 hrs standby + 24 hrs emergency, BACNET/MODBUS/LONWORK connectivity, provision for cloud storage, plug-in loop driver expansion, 5.25A/10.25A PSUs as per EN-54-4, RS-232 serial port, including all accessories and connections, complete all as specified and directed. |
| 55 | Supply, Installation Testing & Commissioning of Analogue Addressable Multi-Sensor which is fully Compatible with Analogue Addressable Protocol, having removable high performance chamber withTwin fire LED\"s allow 360 degree viewing, user selectable modes 1% to 4.5% obs/ft.Incorporated Optical and dual Heat elements, lock mechanism (sensor tobase),Electrically addressed, approved by LPCB &VdS,all as directed by Engineer-in-Charge. |
| 56 | Taking downold unserviceable MCP and Supply, Installation Testing & Commissioning of Analogue Addressable Manual Call Point with Integral Short Circuit Isolator, Analogue Addressable Protocol having status LED for Alarming & standby mode,Electrically addressed,approved by LPCB, all as directed by Engr-in-Charge. |
| 57 | Taking down unserviceableWall sounder & Supply, installation Testing & Commissioning of Addressable loop Powered wall Sounder Beacon, variable Sound Output 90 - 102dB(A) (+2 dB(A) output at 1 metre, High Intensity LED technology, 51 User Selectable Tones (all tones EN 4-3 compatible), all asdirected by Engineer-in-Charge. |
| 58 | Supply and laying in replacement2 core x 1.5 Sqmm Multistranded twisted Copper cable, FRLS armoured laid throughexist conduits fixed on wall/ceiling/floor complete all as directed by Engineer-in-Charge. |
| 59 | Taking downoldunserviceable PVC Conduit and Supply & fixing of PVCConduitheavy duty , 25 mm dia size, for passing cable includingsaddle clips, andall connected accessories all as directed byEngr-in-Charge. |
| 60 | Supply and fix in repair response indicator ofsuitable size including necessary wiring from the detector to RI all as specified and directed by Engineer-in-Charge. |
| 61 | Repairs/routine maintenance of fire detection and alarm system, including testing and servicing of microprocessor-based fire alarm control panels installed at Sailor Block, New SOMA, Medical Store Dental Block (02 Nos) and Nursing Accommodation; attending all system faults, carrying out operational testing, checking of circuits, and providing labour for replacement of unserviceable components as specified. System comprises 05 Nos fire alarm units with the following devices:(a) Response Indicator(b) Audio Alarm (Hooter)(c) Manual Call Point(d) Multisensor DetectorComplete all as specified and as directed. |
| 62 | S&F in replacement of unserviceable hydrant valve wheel, complete all as directed. |
| 63 | Supply only hydrant key made of brass, conforming to ISI standards, complete as specified. |
| 64 | S&F in replacement of canvas fire hose pipe with male/female coupling, IS-36 type, 63 mm dia, 15 m length, complete all as specified and directed. |
| 65 | Supply only fire beater made of MS, size 12\" to 18\", suitable for extinguishing fire on ground, complete all as directed. |
| 66 | Supply and fix wall-mounted iron hammer suitable for breaking glass panels of fire cabinets, complete all as specified. |
| 67 | S&F pressure gauge, 4\" dial, 0–14 kg/cm² rating, complete all as specified and directed. |
| 68 | S&F pressure switch, universal type, suitable for fire pump control installations, complete all as specified. |
| 69 | Supply and fix in replacement of smoke detectors, ceiling-mounted, automatic reset type, complete all as specified and directed. |
| 70 | Supply and fix old-pattern unserviceable-type PVC blank cap suitable for fixing on fire hydrant stand post, complete all as specified |
| 71 | Supply & Fix in replacement of Batteries, capacity 12V, 7Ah, dry type, including removal of old batteries and installation of new ones, complete all as specified and directed by Engineer-in-Charge. |