| 1 | SCHEDULE \"A\" PART-I: BUILDING/STRUCTURESNote: This schedule is not pre-priced by MES and the rate indicated as \"Rs 0.00\" under Col 5 signifies this fact only |
| 2 | Design and Construction of Training Sheds with Pre-Engineered Building steel structure of size (minimum) as mentioned in Architectural drawings with supporting structure, connected accessories, cladding enclosure with suitable supporting structure, complete all as specified, excavation and earth work, foundation as per Manufacturer design, etc., complete with permanent specifications all as shown on drawings and as specified and directed. The building shall have plinth height 75cm above the NGL. |
| 3 | SCHEDULE ‘A’ PART-II & PART-III Note: These Schedules are Prepriced by MES and the Estimated rate indicated under Column 5 signifies this fact only. |
| 4 | Total amount of Sch \"A\" Part-II (Site Clearance, Excavation and Earthwork) |
| 5 | Total amount of Sch \"A\" Part-III (Internal Electrification) |
| 6 | SCHEDULE \"A\" PART-IV (MISCELLANEOUS B/R AND E/M WORKS) Note: This Schedules is not Prepriced by MES and the Estimated rate indicated as \"0.0\" under Column 5 signifies this fact only. |
| 7 | S&F Modular type Socket 6 Amps 3 pin round socket with child safety shutter (ISI Marked) AC 230 Volts, shrouded terminal, smooth plug removal and insertion complete all as specified and directed |
| 8 | Supply, installation, testing and commissioning of high bay light maximum 100W LED, minimum system lumen output of 15000lm. The luminaire should have colour temperature of 6000K and THD<10% CRI>70. The luminaire shall meet IP65 rating, IK07 and luminaire housing should made of pressure die-cast aluminium and integrated PC Lens. The luminaire, should have the features of high voltage surge protection upto 4KV, integrated potted LED driver offers comfortable softlight, high durability, Driver safety requirement standards as per IS 15885-2-13 including chain and clamps for hanging of luminaire complete all as specified and as directed. |
| 9 | S&F MCCB enclosure for frame 1 optimum and solid neutral link for 3 pole MCCB, factory made fixed flush with wall suitable for mounting MCCB 3 pole 430 volts, front openable cover complete all as specified and directed. |
| 10 | M&L Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6 mm thickness buried directly in ground (earth pit not less than 2.25mfr deep below normal ground level) with top edge of earth plate not less than 1.5 mir below normal ground level connected to and inci galvanised earth lead wire of 4.00mm dia by means of nuts & bolts, check nuts and washers of galvanised incl PCC pit of 1:2:4 type B-1, cover reinforced with XPM weight not less than 4 Kg/Sqm and 6mm dia bar handle, earth pit angle iron frame of size 25mm x 25mm, excavation and earth work in any type of soil, charcoal dust, salt, light grade Gl watering pipe 20mm dia with funnel and wire mesh and medium grade Gl protection pipe of 15mm bore from top edge of earth plate upto main distribution board complete all to as shown in electrical plate No 3 of MES Sch 2009 (Part 1) connected main switch board all as specified and testing on completion. |
| 11 | Supply, fixing and laying in trenches or fixing or passing through pipe 1100 Volts grade heavy duty LT UG cable, 4 core 16 Sqmm, with XLPE insulated stranded Aluminium conductor served with an inner sheathing of PVC tape, Armoured with galvanised steel wire and overall sheathed including cable gland, lugs, jointing material etc, jointing, connecting, testing and commissioning complete all as specified and directed. |
| 12 | M&L Double Walled Corrugated DWC HDPE Pipe of outer dia 50mm and inner dia 38mm including 90 degree bends with coupler and rubber ring laid in trenches of size 50 mm suitable for cable protection of size 2 core 10 sqmm to 3.5 core 50 sqmm cable complete all as specified and directed. |
| 13 | M&L Boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed. |