| 1 | PART-A (Electrical)Wiring Points:- Wiring point for light point/ fan point /exhaust fan point/ call bell point with 1.5 sq. mm.FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit ,with Modular type switch, Modular Plate, suitable G.I. Box and earthing the point with 1.5 sqmm FRIS PVC insulated copper conductor single core cable etc. as required.( Group C) P.S. No. 1.10.3 |
| 2 | Wiring point for twin control point with 1.5 sq. mm.FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit ,2 way Modular type switch, Modular Plate, suitable G.I. Box and earthing the point with 1.5 sqmm FRIS PVC insulated copper conductor single core cable etc. as required. P.S. No. 1.11 |
| 3 | wiring for circuit / submain wiring along with earth wire the following sizes of FRLSH PVC insulated copper conductor ,single core cable in surface /recessed medium class PVC conduit as required.2X 1.5 sqmm + 1 X 1.5 sqmm earth wire P.S. No. 1.14.1 |
| 4 | wiring for circuit / submain wiring along with earth wire the following sizes of FRLSH PVC insulated copper conductor ,single core cable in surface /recessed medium class PVC conduit as required.2X 2.5 sqmm + 1 X 2.5 sqmm earth wire P.S. No. 1.14.2 |
| 5 | wiring for circuit / submain wiring along with earth wire the following sizes of FRLSH PVC insulated copper conductor ,single core cable in surface /recessed medium class PVC conduit as required.2X 4 sqmm + 1 X 4 sqmm earth wire P.S. No. 1.14.3 |
| 6 | wiring for circuit / submain wiring along with earth wire the following sizes of FRLSH PVC insulated copper conductor ,single core cable in surface /recessed medium class PVC conduit as required.2X 6 sqmm + 1 X 6 sqmm earth wire P.S. No. 1.14.4 |
| 7 | wiring for circuit / submain wiring along with earth wire the following sizes of FRLSH PVC insulated copper conductor ,single core cable in surface /recessed medium class PVC conduit as required.2X 10 sqmm + 1 X 6 sqmm earth wire P.S. No. 1.14.5 |
| 8 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. P.S. No. 2.24.1 |
| 9 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with testing and commissioning etc. as required. P.S. No. 2.23.2 |
| 10 | Supplying and Fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface size or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 A &. 15/16A socket outlet and 15/16 A piano type switch , connections painting etc. as required. P.S. No. 1.3 |
| 11 | Supplying and Fixing following Modular type switch/socket on the existing box /cover including , connections etc. as required. (a) 5/6 A.Switch. P.S. No. 1.24.1 |
| 12 | (b) 3 pin 5/6 A socket outlet P.S. No. 1.24.4 |
| 13 | Supply and fixing of 6 Amp. to 32 Amp. MCB.(10KA) P.S. No. 2.10.1 |
| 14 | Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 amps \"C\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. P.S. No. 2.18 |
| 15 | Supplying and drawing ci-axial TV Cable RG-6 grade 0.7 mm solid copper conductor PE insulated shielded with fine tinned copper braid and protect with PVC sheath in the existing surface / recessed steel/PVC conduit as required. P.S. No. 1.19 |
| 16 | Supplying and fixing of TV antenna socket outlet modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. P.S. No. 1.24.7 |
| 17 | Supplying and fixing of 25mm dia of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. P.S. No. 1.21.2 |
| 18 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings). P.S. No. 1.31 |
| 19 | Supply and Fixing 3pin 5 A. Ceiling rose on the existing junction box/wooden block including connection etc.as required. P.S. No. 1.33 |
| 20 | Supply and Fixing of Call bell /Buzzer sutable for single phase 230 volt.complete as required. P.S. No. 1.38 |
| 21 | Extra For fixing the louvers /Shutters complete with fram for a exhoust fan of all size. P.S. No. 1.51 |
| 22 | Supply and Fixing PVC batten /angle holder including connection etc.as required. P.S. No. 1.58 |
| 23 | Supply & fixing 8 way SPN ,(single pole and neutral) , sheet steel ,MCB distribution board , 240 V ,on surface / recess , complete with tinned copper bus bar ,neutral basbar , earth bar , din bar, interconnections, powder painted including earthing etc. as required.(But without MCB /RCCB/Isolator) P.S. No. 2.3.2 |
| 24 | Supply & fixing 12 way SPN ,(single pole and neutral) , sheet steel ,MCB distribution board , 240 V ,on surface / recess , complete with tinned copper bus bar ,neutral basbar , earth bar , din bar, interconnections, powder painted including earthing etc. as required.(But without MCB /RCCB/Isolator) P.S. No. 2.3.3 |
| 25 | Supply & fixing 4 way TPN ,horizontal type three pole and neutral , sheet steel ,MCB distribution board , 415 V ,on surface / recess , complete with tinned copper bus bar ,neutral busbar , earth bar , din bar, interconnections, powder painted including earthing etc. as required.(But without MCB /RCCB/Isolator) P.S. No. 2.4.1 |
| 26 | Earthing with G.I. earth plate 60 mm X 600 mm X 6 mm thick including accessories ,and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc with charcoal/ coke and salt as required. P.S. No. 5.4 |
| 27 | Supply & laying 25 mm X 5mm G.I. Stripe at 0.50 metre below ground level for earth conductor earth electrode , including connection /termination with copper thimble etc.as required. directed at site. P.S. No. 5.9 |
| 28 | Supplying and making end termination with brass Compression Gland and aluminium lugs for Following size of PVC insulated and PVC sheathed /XLPE aluminium conductor cable of 1.1 kv glandas requireda-10sq mm 2 core P.S. No. 9.1.2 |
| 29 | b-25sq mm 3-1/2 core P.S. No. 9.1.20 |
| 30 | d-70 sq mm 3-1/2 core P.S. No. 9.1.23 |
| 31 | Supply, installation, Testing and Commissioning of 1200mm sweep, BEE 5 star rated, ceilling fan with Brush Less direct current (BLDC) moter ,class of insulation ;B 3 no. blades ,30 cm long down rod, 2nos canopies , shackle rope, copper wiring , power facter not less than 0.9 , service value (CM/M/W) minimum 6.00 , AIR delivery miniimum 210 Cum/Min, 350 RPM (tolerance as per IS : 374 -2019), THD less than 10% ,remte or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise =75 degree C(max), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz , single phase AC Supply ,earthing etc.comple as required. P.S. No. 19.1 |
| 32 | Supply and fixing of 32 mm dia X 2.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting. P.S. No. 12.34 |
| 33 | Manufacturing, Supply Installation testing and commissioning of 200 A.MainPanel. The Panel shall be fabricated out of 2.0mm thick CRCA sheet steel, painted with Powder coated paint of shade as per the direction of Enginee In-Charge after proper sheet treatment process of sheet steel. The Bus bar of Panel shall be of High grade Electrical grade High Conductive Aluminum alloy of appropriate cross section as per rating. The calculation of continuous rating of Bus Bar shall be submitted. The Bus Bar shall be supported by non hygroscopic SMC/DMC Bus Bar supports which shall be mounted on proper interval to ensure bear the jerks of short Circuit as fault level require. The Fault level of Panel shall be 50kA for 1sec. All Indicating Lights shall be LED type and all wiring shall be done from PVC Insulated copper flexible wire. The Panel shall be completed in all respect and shall consist of following material. Incoming 200 A FP MCCB 01 No. Outgoing 63 A FP MCCB 03 Nos.P.S. No. 22.1.2.b.ii |
| 34 | Supply and fixing of LED Tube light with Metal heavy duty Box type batten Light fitting 1x22 watt suitable for upto 1x22 watt LED Polycarbonate tube light Complete Including tube suitable for both surface & suspended complete in all respect.CAT-AAA 2620 system lumens, 120Im/W, PF>0.95, THD<10% CRI>80 sheet thickness 0.8mm, Tube with aluminium heat sink <300 V Over voltage protection , 2.5 KV internal suger protection with 5 Year waranteeCat-AAA P.S. No. 23.07 |
| 35 | Supply and fixing of LED Tube light with Metal heavy duty Box type batten Light fitting 2x22 watt suitable for upto 2x22 watt LED Polycarbonate tube light Complete Including tube suitable for both surface & suspended complete in all respect.CAT-AAA 2620 system lumens, 120Im/W, PF>0.95, THD<10% CRI>80 sheet thickness 0.8mm, Tube with aluminium heat sink <300 V Over voltage protection , 2.5 KV internal suger protection with 5 Year warantee.Cat-AAA P.S. No. 23.09 |
| 36 | Supply and fixing of LED Street light fitting with Mandatory driver set heavingdie cost aluminium body with toughend glass/UV suitable stabilized PC cover and lenses suitable for 60 watt to72 watt and confiming to IP 66 and IK 07 and above protection heaving company LOGO Engraved complete in all respect including labour. CAT-AAA 16800-18000 system lumens, high power LED with lenses>120Im/W, PF>0.95, THD<10% at full load CRI>70 potted driver set in metal housing (not circuilory ) phase to phase protection at 440V &> 300 V auto cut and restart feature, 4 KV internal suger protection with 5 Year warantee.Cat-AAA P.S. No. 23.15 |
| 37 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. including excavation and refilling The armouring of the cable shall be properly connected with the earth conductor by clamps etc. a-25sq mm 3-1/2 core P.S. No. 20a.1.10 |
| 38 | b-70 sq mm 3-1/2 core P.S. No. 20a.1.13 |
| 39 | S/f of of Extended computer Board including 2 Nos. 6 Amp. Switch & 2 Nos. 6 Amp. Socket complete without Submain. Havells or equivalent (A/R) |
| 40 | S/F of 7 Watt LED Bulb Havells or equivalent. (A/R) |
| 41 | Supply Metallic body fresh air fan 200 mm. sweep. Havells or equivalent. (A/R) |
| 42 | Supply and fixing of 63 Amp. FP MCB (36 KA) C-Series Complete Havells /Equvelent make (A/R) |
| 43 | S&F of 40 Amp. SP MCB (A/R) |
| 44 | S&F of 40 Amp. DP MCB (A/R) |
| 45 | Supply and fixing of 200 Amp.FP Changeover Switch with frame complete in all respect. (A/R) |
| 46 | Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as pe direction of the Engineer-Incharge.a-10sq mm 2 core (Q/R) |
| 47 | b-16sq mm 2 core (Q/R) |
| 48 | c-25sq mm 3-1/2 core (Q/R) |
| 49 | d-35 sq mm 3-1/2 core (Q/R) |
| 50 | e-70 sq mm 3-1/2 core (Q/R) |
| 51 | Supply and laying of of 1800 mm x 900 mm x 12 mm thick chequered rubber matting of quilty. (Q/R) |
| 52 | Providing and fixing of circular/Hexagonal cast iron or MS sheet box for ceiling fan clamp of internal dia 140mm , 73mm height top lid 1.5mm thick ms sheet with its top surface hacked for proper bonding top lid shall be screwed into the cast iron/ms sheet box by means of 3.3mm dia ROUND HEADED SCREWED ONE LOCK at corner as required (DSR Civil-2023, 10.18) |
| 53 | PART-B (Fire Fitting)Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required. P.S. No. 17.1.3 |
| 54 | Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required. P.S. No. 17.1.2 |
| 55 | Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required. P.S. No. 17.1.1 |
| 56 | Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required. P.S. No. 17.1.6 |
| 57 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. P.S. No. 17.5.2 |
| 58 | Supplying, installation, testing & commissioning sector panel suitable for 4 zone, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required. P.S. No. 17.1.9.1 |
| 59 | Supplying and making end termination with brass Compression Gland and aluminium lugs for Following size of PVC insulated and PVC sheathed /XLPE aluminium conductor cable of 1.1 kv glandas required. 25sq mm 3-1/2 core P.S. No.9.12 |
| 60 | Supply and laying of 25sq mm 3-1/2 core aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. including excavation and refilling The armouring of the cable shall be properly connected with the earth conductor by clamps etc. P.S. No. 20a.1.10 |
| 61 | CO2 type Fire Extinguisher 4.5Kgs. Capacity, made from brand new seamless cylinder, as per IS: 7185 and CCE approval, fitted with Discharge hose and horn and Wheel / Squeeze Grip type valve with initial Charge as per IS: 15683:2006 specification, bearing ISI Mark. (Omex/Ceasefire/Atasi) (A/R) |
| 62 | PREMIUM Powder Fire Extinguisher (Stored Pressure type) Capacity 09 Kg duly ISI marked conforming to IS: 15683:2018, with IS 4308, ISI marked ABC MAP 90% powder complete with squeeze grip release valve, discharge pipe locking arrangement, pressure gauge, operation manual and bracket. Operating Temperature: -30ºC to + 60ºC. (A/R) |
| 63 | Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as pe direction of the Engineer-Incharge. a -16sq mm 3-1/2 core (Q/R) |
| 64 | b -25sq mm 3-1/2 core (Q/R) Please Enable Macros to View BoQ information |