Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | EXTERNAL ELECTRTIFICATION ITEMSExcavation in soft / loose soil in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out complete. |
| 2 | Returning filling with earth obtained from excavation including spreading watering and consolidation in layers not exceeding 25 cms thick complete. |
| 3 | Removing surplus soil to a distance not exceeding 50 m and depositing at a level not exceeding 1.5 m above the starting point complete. |
| 4 | M&L for spreading of loose stone aggregate of nominal size 40 mm inside fencingof RMU /transfromer manually without damaging any equipments, cable or parts spreading & levelling of finished gravel uniformaly in layers not exceeding 15 cm thick as required. |
| 5 | M&L for mild steel work (structural) as in cross arm bracing supports, clamps fabricated from structural steel section including nuts, bolts, washers, welding, bending, drilling holes for bolts in any size or shape as required andone primer coat with red oxide primer one under coat & one finishing coat of aluminium paint complete. |
| 6 | S&F pin type porcelain vitreous browninsulator 150 mm high including one galvanised mild steel spindle, two GI washers and one GI nut suitable for 11000 volts grade complete. |
| 7 | S&F in renewal MCCB 4 pole 160 Amp 36 KA (Icu=Ics) thermally adjustable between 70% to 100% complete. |
| 8 | S&F in renewal MCCB 4 pole 200 Amp 36 KA (Icu=Ics) thermally adjustable between 70% to 100% complete. |
| 9 | S&F in renewal MCCB 4 pole 250 Amp 36 KA (Icu=Ics) thermally adjustable between 70% to 100% complete. |
| 10 | S&F in renewal MCCB 4 pole 400 Amp 50 KA (Icu=Ics) thermally adjustable between 70% to 100% complete. |
| 11 | S&F in renewal MCCB 4 pole 630 Amp 50 KA (Icu=Ics) thermally adjustable between 70% to 100% complete. |
| 12 | S&F in renewal MCCB 3 pole 160 A, 36 KA (Icu=Ics) with microprocessor release adjustable between 40% to 100% complete. |
| 13 | S&F in renewal MCCB 3 pole 250 A, 36 KA (Icu=Ics) with microprocessor release adjustable between 40% to 100% complete. |
| 14 | S&F in renewal MCCB 3 pole 400 A, 36 KA (Icu=Ics) with microprocessor release adjustable between 40% to 100% complete. |
| 15 | S&F in renewal MCCB 3 pole 630 A, 36 KA (Icu=Ics) with microprocessor release adjustable between 40% to 100% complete. |
| 16 | S&F in renewal MCCB 4 pole, 100 A, 16 KA (Icu=Ics) thermally adjustable between 70% to 100% complete. |
| 17 | S&F in renewal MCCB 4 pole 16 KA 125 Amp 16 KA (Icu=Ics) thermally adjustable between 70% to 100% as per exisisting make/model etc complete. |
| 18 | S&F danger notice plate of size, for HT, 25 cm x 20 cm 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts as required. |
| 19 | S&F in renewal outdoor type off load, triple pole, gang operated double break, rotating type, horizontal mounting air break switch, 11 KV, 200 amps consisting of hot dip galvanized channel iron base having 3 Nos 11 KV post insulators per phase, copper or copper alloy high pressure heavily tinned contacts plated MS arcing horn capable of breaking the magnetizing current with horizontal connecting bar GI pipe as down rod levers coupling and operating handle with locking arrangements manufactured as per IS : 9921 with and including operating rod of 25 mm bore medium grade GI pipe of suitable length to operate from ground level complete. |
| 20 | S&F in renewal outdoor type off load, triple pole, gang operated double break, rotating type, horizontal mounting air break switch, 11 KV, 400 amps consisting of hot dip galvanized channel iron base having 3 Nos 11 KV post insulators per phase, copper or copper alloy high pressure heavily tinned contacts plated MS arcing horn capable of breaking the magnetizing current with horizontal connecting bar GI pipe as down rod levers coupling and operating handle with locking arrangements manufactured as per IS : 9921 with and including operating rod of 25 mm bore medium grade GI pipe of suitable length to operate from ground level complete. |
| 21 | Supplying and making indoor cable end terminal joint heat shrinkable type suitable for 3 core 11 KV (E) grade XLPE insulated cable of size 95 sqmm complete. |
| 22 | Supplying and making outdoor cable end terminal joint heat shrinkable type suitable for 3 core 11 KV (E) grade XLPE insulated cable of size 95 sqmm complete. |
| 23 | Supplying and making straight through cablejoint heat shrinkable type suitable for 3 core 11 KV (E) grade XLPE insulated cable of size 95 sqmm complete. |
| 24 | S&F in renewal XLPE insulated armoured and PVC shethed heavy duty electric cable with aluminium conductor 1100 volt grade laid in trenches passing through pipes/ ducts of following cross sectional area:- |
| 25 | 10 sqmm 2 core |
| 26 | 10sqmm 4 core |
| 27 | 25 sqmm 4 core |
| 28 | 50 sqmm 3.5 core |
| 29 | 70 sqmm 3.5 core |
| 30 | 95 sqmm 3.5 core |
| 31 | 120 sqmm 3.5 core |
| 32 | 185 sqmm 3.5 core |
| 33 | 240 sqmm 3.5 core |
| 34 | 400 sqmm 3.5 core |
| 35 | Note for item No 24. Cables where XLPE insulation is exposed, shall be provided with heat shrinkable sleeves to avoid the cracking of insulation and cost of the same is deemed to be included in the item. |
| 36 | Supplying, laying, testing and commissioning in renewal FRLS (both inner & outer sheath), XLPE insulated, screened, PVC sheathed, galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor ISI marked 6.35 KV(UE)/11 KV (E) of size 95 sqmm 3 core as per IS : 7098 (Part - 2) / 1985 laid in trenches/ducts/ through pipe complete. |
| 37 | Supplying and laying synthetic Rubber insulated mat 2.5 mm thick class \"B\"to withstand 45 KV dielectric strength ISI marked as per IS-15652:2006 having size2 m x 1 m.for electrical shock safety upto 11 KV voltage complete. |
| 38 | Dismantling cross arms, clamps etc. |
| 39 | Dismantling insulators any type any size. |
| 40 | S&F drop out lift fuse link 11 KV, 100 amps consisting of channel galvanized iron base, having 2 Nos 11 KV postinsulators per phase including fuse carrier of SRBP tube with heavily tinned non ferrous metal parts & spring loaded phosphor bronze contact manufactured as per IS: 9385 complete. |
| 41 | Supply and laying or fixing of DWC HDPE pipe alongwith all accessories like socket, bend, couplers etc ISI marked as per IS-16205 (Part-24) including cutting/jointing laid in trenches (Excavation not included), wall, floor etc as required for cable protection for following sizes:- |
| 42 | 50 mm outer dia and 38 mm inner dia |
| 43 | 63 mm outer dia and 50 mm inner dia |
| 44 | 90 mm outer dia and 75 mm inner dia |
| 45 | 120 mm outer dia and 103 mm inner dia |
| 46 | 160 mm outer dia and 135 mm inner dia |
| 47 | Opening / stripping off the step down transformer, 11 KV/0.443 KV, draining off oil, lifting the core & coil assembly, washing and cleaning dust, dirt & sludge deposit etc from all parts removing damaged / defective parts requiring renewal (as mentioned in subsequent items), making internal connection, servicing of tap changer and reassembling the transformer after repair work, providing new cork sheet gasket packing 5 mm thick, nuts, bolts washers etc as required, transportation, loading, unloading from sub station to workshop & back including its installation at original place, testing & commissioning complete for the following capacities:- |
| 48 | 63 KVA to 250 KVA |
| 49 | 315 KVA to 500 KVA |
| 50 | Renewal of high voltage coil, wound with double paper insulated copper conductor of same guage including necessary insulating materials and baking the coil in vacuum furnace complete upto 500 KVA capacity complete. |
| 51 | Reconditioning of copper wound low voltage coil including necessary insulating materials, and baking coil in vacuum furnace complete upto 500 KVA capacity complete. |
| 52 | M&L for topping up of deficient oil level of transformers with filtered and dehydrated transformer oil (conforming to IS: 435) and to withstand dielectric strength 60 KV or above (when tested with 2.5 mm gap electrode) complete. |
| 53 | Material, equipment and labour for filtration / dehydration of insulating oil of transformer in position, without disrupting power supply to achieve dielectric strength 55 KV or above (when tested with 2.5 mm gap electrode) complete. |
| 54 | Labour and equipments for shifting of transformer upto 500 KVA capacity after disconnection from one location to another for restoration of supply during failure of transformer of any location or redistributution of load as required including connection and commissioning of shifted transformer and disconnection & setting aside existing transformer complete. |
| 55 | Labour and tools for cleaning the sub station open areas, removing grass, shrub, roots, stone / brickbats etc by surface excavation not exceeding 30 cm deep, leveling the area and keeping it maintained to the entire period of contract.Note:- Digital photographs with dates of cleaning to be maintained. |
| 56 | S&F in renewal wooden planks made of wooden boards minimum 30mm thick of required size for staging purpose in 2/4 pole structure to facilitate the maintenance work. |
| 57 | S&F in renewal transformer breather assembly oil seal type made of heavy duty transparent plastic body having top & bottom cover made of aluminium or mild steel of capacity 250 grams filled with silica gel complete. |
| 58 | S&F in renewal transformer breather assembly oil seal type made of heavy duty transparent plastic body having top & bottom cover made of aluminium or mild steel of capacity 500 grams filled with silica gel complete. |
| 59 | Renewal of silica gel of transformer breather assembly of any capacity as required. |
| 60 | M&L for spray painting of transformer11 KV/ 0.443 KV with two coats of synthetic enamel grey paint over a primer coat after preparation of old painted surface complete for the following capacities:- |
| 61 | 63 KVA to 250 KVA |
| 62 | 315 KVA to 500 KVA |
| 63 | 750 KVA |
| 64 | S&F in renewal HV bushing of 12 KV grade with gasket suitable for transformer of following capacities:- |
| 65 | 63 KVA to 100 KVA |
| 66 | 160 KVA to 250 KVA |
| 67 | 315 KVA to 500 KVA |
| 68 | S&F in renewal LV bushing of 1.1 KV grade with gasket suitable for transformer of following capacities:- |
| 69 | 63 KVA to 100 KVA |
| 70 | 160 KVA to 250 KVA |
| 71 | 315 KVA to 500 KVA |
| 72 | S&F in renewal HV brass set stem of 12 KV grade suitable for transformer of following capacities:- |
| 73 | 63 KVA to 100 KVA |
| 74 | 160 KVA to 250 KVA |
| 75 | 315 KVA to 500 KVA |
| 76 | 750 KVA |
| 77 | Supplying and fixing in renewal LV brass set stem of 1.1 KV grade suitable for transformer of following capacities:- |
| 78 | 63 KVA to 100 KVA |
| 79 | 160 KVA to 250 KVA |
| 80 | 315 KVA to 500 KVA |
| 81 | 750 KVA |
| 82 | S&F in renewal oil level indicator clean prismatic type with necessary gasket etc suitable for transformer up to 500 KVA capacity complete. |
| 83 | Supplying, installing, testing and commissioning outdoor cubical type MV Panel board design verified with switchgear and controlgear assemblies as per IS/IEC-61439 (Part - 1 & 2) of 2020 suitable for 415V, 3 phase, 4 wire 50 Hz supply system fabricated from 3 mm thick CRCA sheet powder coated RAL 7032 shade, dust, weather & vermin proof, degree of ingress protection IP-54 having TPN copper busbar of rating 1.5 times of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and conrol wiring with min 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase indication lamps including Digital multifuctional display meter with built in selector switch to measure voltage, current, PF & frequency mounted on suitable PCC foundation with following controls:- |
| 84 | Incoming (a) One number On load Change Over Switch TPN, 250 A.(b) Two numbers MCCB 4 pole, 250 A, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%. |
| 85 | Outgoing |
| 86 | (a) One number MCCB FP 200 A, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. (b) One number MCCB FP 160 A, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%.(c) Two numbers MCCBFP 100 A, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. (d) One number MCCBFP 63 A, 16 KA (Icu=Ics) thermally adjustable between 70% to 100%. |
| 87 | Supplying, installing, testing and commissioning outdoor cubical type MV Panel board design verified with switchgear and controlgear assemblies as per IS/IEC-61439 (Part - 1 & 2) of 2020 suitable for 415V, 3 phase, 4 wire 50 Hz supply system fabricated from 3 mm thick CRCA sheet powder coated RAL 7032 shade, dust, weather & vermin proof, degree of ingress protection IP - 54 having TPN copper busbar of rating 1.5 times of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and conrol wiring with min 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase indication lamps including Digital multifuctional display meter with built in selector switch to measure voltage, current, PF & frequency mounted on suitable PCC foundation with following controls :- |
| 88 | IncomingOne number MCCB 4 pole 250 A, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. |
| 89 | Outgoing |
| 90 | (a) Two numbers MCCBFP 160 A, 16 KA (Icu=Ics) thermally adjustable between 70% to 100%.(b) Three numbers MCCBFP 100 A, 16 KA (Icu=Ics) thermally adjustable between 70% to 100%. (c) One number MCCB FP 63 A, 16 KA (Icu=Ics) thermally adjustable between 70% to 100%. |
| 91 | Supplying, installing, testing and commissioning outdoor cubical type MV Panel board design verified with switchgear and controlgear assemblies as per IS/IEC-61439 (Part - 1 & 2) of 2020 suitable for 415V, 3 phase, 4 wire 50 Hz supply system fabricated from 3 mm thick CRCA sheet powder coated RAL 7032 shade, dust, weather & vermin proof, degree of ingress protection IP - 54 having TPN copper busbar of rating 1.5 times of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and conrol wiring with min 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase indication lamps including Digital multifuctional display meter with built in selector switch to measure voltage, current, PF & frequency mounted on suitable PCC foundation with following controls :- |
| 92 | Incoming One number MCCB 4 pole 250 A, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%. |
| 93 | Outgoing: |
| 94 | (a) One number MCCB FP 160 A, 16 KA (Icu=Ics) thermally adjustable between 70% to 100%. (b) Four numbers MCCBFP 100 A, 16 KA (Icu=Ics) thermally adjustable between 70% to 100%. (c) Two numbers MCCBFP 63 A, 10 KA (Icu=Ics) thermally adjustable between 70% to 100%. |
| 95 | Supplying, installing, testing and commissioning outdoor cubical type MV Panel board design verified with switchgear and controlgear assemblies as per IS/IEC-61439 (Part - 1 & 2) of 2020 suitable for 415V, 3 phase, 4 wire 50 Hz supply system fabricated from 3 mm thick CRCA sheet powder coated RAL 7032 shade, dust, weather & vermin proof, degree of ingress protection IP - 54 having TPN copper busbar of rating 1.5 times of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and conrol wiring with min 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase indication lamps including Digital multifuctional display meter with built in selector switch to measure voltage, current, PF & frequency mounted on suitable PCC foundation with following controls :- |
| 96 | Incoming(a) One number On load Change Over switch TPN 160 A. (b) Two numbers MCCB 4 pole 16 KA 160 A (Icu=Ics) thermally adjustable between 70% to 100%. |
| 97 | Outgoing |
| 98 | (a) Three numbers MCCBFP 100 Amp, 16 KA (Icu=Ics) thermally adjustable between 70% to 100%. (b) Two numbers MCCBFP 63Amp, 16 KA (Icu=Ics) thermally adjustable between 70% to 100%. |
| 99 | Renewal of\"ON LOAD\" Change over switch 400 Amps TPN front handle operated to be fixed within Panel. |
| 100 | S&F in renewal of digital voltmeter 3.5 digit |
| 101 | S&F in renewal of digital ammeter 3.5 digit. |
| 102 | S&F in renewal of RYB LED Indicator. |
| 103 | Periodical servicing of air circuit breaker of any make, model, upto 1250 A through authorised service centre of OEM after disconnecting the electrical connection, replacing unserviceable parts as per existing make/model/ capacity including cleaning and greasing fixed and moving parts complete. Note:- Rate shall deem to include petty items viz. bolts, nuts, washers, lugs, thimble, wires etc required for efficient and smooth functioning of the ACB. However, spare parts if any mentioned below is found u/s will be measured separately against relevant item of the schedule. |
| 104 | Supply only following spare parts of air circuit breaker as per existing make for renewal:- |
| 105 | Shunt release |
| 106 | Under voltage release |
| 107 | Earth fault release |
| 108 | Remote fault indicator |
| 109 | Micro switch for indication |
| 110 | Lockable trip push botton |
| 111 | Lock for ACB in isolating position |
| 112 | Lock for ACB in any position |
| 113 | Racking interlock |
| 114 | Door interlock |
| 115 | Mechanical operation counter |
| 116 | Mounting kit for front mounted counter |
| 117 | Spring charge indication micro switch |
| 118 | Racking pad lock assembly |
| 119 | Periodical servcing of 11 KV RMU of any make, model through authorised service centre of OEM cleaning fixed/ moving contacts, blowing out dust and applying the proper lubrication/ greasing on all moving parts, tighting of all joints, nuts, bolts, washers, removing the moisture and replacement of defective parts as per existing make/ model/ capacity including testing through primary injection complete. |
| 120 | Periodical servicing of 11 KV VCB Panel (SF6 type) upto 800A, any make, model through authorised service centre of OEM comprising of following:-(a) Taking out trolley from Panel, cleaning & servicing fixed & moving contacts after blowing out dust and applying the proper lubrication/ greasing and refitting and testing complete.(b) Servicing and testing of IDMT relay any type/make/ model installed in VCB panel, setting parameters and testing it through secondary current injection test and submitting test result complete. |
| 121 | Providing labour and tools for defect identification in 11 KV XLPE cables laid in trenches with help of electronic fault locater machine, comprising of surge generator pulses, ECHO fault locator with high frequency distance calculator as required. |
| 122 | Supplying and making straight through cable joint heat shrinkable type suitable for 3.5 core 1.1 KV (E) grade XLPE insulated cable of following sizes:- |
| 123 | 50 to 95 sqmm |
| 124 | 120 sqmm to 185 sqmm |
| 125 | 240 sqmm to 400 sqmm |
| 126 | M&L for painting of11.0 m long swaged poles withcross arm/clamps with aluminium paint one under coat and one finishing coat over a coat of red oxide primer after preparation of steel surfaces including making ofalternate colour bands red & white 30 cms width upto a height of 1.5 m from pole coping with synthetic enamelled paint & writing pole numbers on round base of 125 mm dia with yellow synthetic paint complete. |
| 127 | Servicing of air break switches 11 KV in existing position including renewal of worn out nuts, bolts, washers etc & providing petrolleum jelly for smooth operation complete. |
| 128 | S&F in renewal metal oxide surge arrestor suitable for maximum system voltage 12 KV and arrestor rated voltage 10 KV, maximum continuous operating voltage 7.6 KV, nominal discharge current 10 KAp line discharge class 2 high current withstand 100 KAp maximum residual voltage at NDC lightning current 30 KVp temperature over voltage capability for 10 sec 17.5 KVp & creepage distance 300 mm conforming to IEC 60099-4 & IS: 3070 specifications complete. |
| 129 | M&L for chemical earthing with GI pipe electrode 3.0 m long having outer pipe dia 80 mm & inner pipe dia 50 mm duly filled with highly conductive and anti corrosivecompound of required quantity having chemical composition Bentonite 40%, copper sulphate 20%, Gypsom 5%, Graphite 10%, Alum 5%, Zinc sulphate 10%, Aluminium sulphate 10% burried in ground by digging a bore of 150 mm dia surrounded by soil friendly backfill compound non soluble in water including connection with galvanised earth strip 32 x 6 mm, making PCC pit of size 0.3 m x 0.3 m x 0.3 m (inner size) in mix 1:3:6 type C1 with RCC 1:2:4type B-1, 40 mm thick cover reinforced with 6 mm dia MS bars 3 Nos both ways with lifting hook made out of 6 mm dia bar and testing on completion to achieve value not more than 1.0 ohm complete. (Note - GI strip size 32x6 mm upto 7.5 m included in the item). |
| 130 | Renewal of worn out ACSR conductor used as busbars in four pole/ two pole structure including PVC sleeves, lugs, nuts, bolts, washers etc as required. |
| 131 | Professional services to repair servo voltage stabilizer 100 to 400 KVA at site including renewal of unserviceable parts as required. Note:- Spare parts shall be measured separately as supply only under relevant item of the schedule. |
| 132 | Supply only genuine spare parts for servo voltage stabliser suitable for and upto 400 KVA as required. |
| 133 | Servo card |
| 134 | Servo motor |
| 135 | Control wiring |
| 136 | High/ low voltage cutout |
| 137 | Control transformer |
| 138 | Relay |
| 139 | Toggle switch |
| 140 | Push button |
| 141 | Digital Voltmeter |
| 142 | Digital Ammeter CT operated |
| 143 | FIRE FIGHTING ITEMSS&F in repair 150 mm dia Butterfly Valve complete. |
| 144 | S&F ABC powder fire extinguisher Mono Ammonium Phosphate (MAP 90 based portable stored pressure) of following capacities:- |
| 145 | 6.0 Kg |
| 146 | 4.0 Kg |
| 147 | S&F carbon dioxide (CO2) type fire extinguishers confirming to IS 2878-1976 and cylinders fully charged of capacity 4.5 Kg complete. |
| 148 | S&F foam fire extinguishers, portable type 9 litre capacity hanged on wall with bracket complete as required. |
| 149 | Supply and fixing 45 ltr mechanical foam type fire extinguisher filled with AFFF Foam (6%), applicable fire class A&B, Gross Weight 87 Kg, Empty weight 37Kg, Can Height 1285mm, Diameter 300 mm,Controllable Discharge mechanism, Discharge Time 40-180 Sec, Jet Range 10 Meters, Average Discharge is 90%, Fitted with EPDM Hose with SS spring of 300mmto avoid kink (3 meter long) & Air aspirated Nozzle,CO2 gas Cartridge of 300 gm. (Confirms to IS 4947),Can Construction : Deep drawn & CO2 Mig welded,External Pure polyester (UV Resistant) and Internal Epoxy polyester powder coated, Brass forged cap, construction as per IS 13386:1992 and ISI Marked complete. |
| 150 | S&F in renewal installation of relay input in fire control panel complete |
| 151 | S&F in renewal of Manual call point with hammer and chain, MS box duly painted in red colour including connections etc as required |
| 152 | S&F in renewal of electronic Hooter with high qualtiy speaker complete |
| 153 | M&L for maintenane and cleanig of sump complete, removing the mud from the sump after pumping the water out and white washing one coat on walls of sump after scrapping, complete. |
| 154 | S&F in renewal Pressure Gauge ranging from 0 to 20 kg/ sqcm ISI marked complete |
| 155 | S&F in renewal of Pressure Switch 0-200 PSI (0-14 Kg) range as required |
| 156 | S&F in renewal of 25 mm air release valve gun metal having 25 mm BSP threaded male inlet complete |
| 157 | M&L for maintenance of foot valve, repairing of Main Pump, Jockey Pump and diesel pump complete with repalcement of worn out parts such as gasket, nuts, bolts etc complete. |
| 158 | S&F in repairs of Pendent type quartzoid bulb sprinkler heads with temperature rating of 68 degree complete |
| 159 | S&F in repairs of shut off nozzle for the hose reel drum complete |
| 160 | M&L for painting of MS pipe including fittings like elbows, tees, flanges, tapers etc of fire extinguisher above ground level after scrapping the old paint etc complete. |
| 161 | S&F 30 M long RRL thermoplastic hose and ABS nozzle complete |
| 162 | M&L for overhauling of Hydrant valve with instantaneous stainless steel couplings of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type-A) with blank cap and chain as required. |
| 163 | M&L for overhauling of Hose reel drum with MS construction spray painted in post office red colour complete. |
| 164 | Repair of fire alarm control panel by replacing Card, IC & recaliberation to make it functional. |
| 165 | S&F in repair of power contactor MNX 40/50, 3 phase 415 volts, 50 Hz with all connecting accessories complete. |
| 166 | SF in renewal tubular batteries 12 V, 88 AH including copper terminal lugs complete. |
| 167 | M&L for Servicing of 63 mm dia Yard Hydrant Valve including change of washer, coupler etc. |
| 168 | Renewal of mechanical seal, shaft & bearing ofKirloskar make Jockey Pump 15 HP complete. |
| 169 | S&F in repairs of Conventional Optical Smoke detector including the base plate which blinks green in normal condition and becomes steady red in fire condition with 360 degree viewing angle complete |
| 170 | M&L for Professional services to repair shadowless modular OT light (4 Nos) and conventional OT light (5 Nos) of any make/ model at Command Hospital & Base Hospital Lucknow including renewal of unserviceable parts as required.Note:- Spare parts shall be measured separately as supply only under relevant item of the schedule. |
| 171 | Supply only following spare parts of shadow less OT light as per existing make for renewal:- |
| 172 | Halogen bulbs, 12 volts, 50 watts suitable for OT light. |
| 173 | Halogen medical reflector 24V, 150 watts suitable for shadowless light fitting. |
| 174 | Thermostatic mixing valve provided for constant water temperature with defined setting of adjustable timing of 1, 3, 5, 10 minute complete |
| 175 | Electric photo sensor suitable for two bay surgical surb sink for hads free operation with built in range of adjustment complete |
| 176 | Solenoid valve 24 volt suitable for two bay surgical scurb sink for hands free operation with built in range of adjustment complete |
| 177 | Foot switch suitable for hermatically sealed door of modular OT of make Metaflux complete |
| 178 | Runner wheel MF5 suitable for hermatically sealed door of modular OT of make Metaflux complete |
| 179 | Guide roller set MF5 suitable for hermatically sealed door of modular OT of make Metaflux complete |
| 180 | Side sealing gasket suitable for hermatically sealed door of modular OT of make Metafluxcomplete |
| 181 | Teath belt suitable for hermatically sealed door of modular OT of make Metaflux complete |
| 182 | Photo cell suitable for hermatically sealed door of modular OT of make Metaflux complete |
| 183 | Motor 370 watts suitable for hermatically sealed door of modular OT of make Metafluxcomplete |
| 184 | SDA 04 controller suitable for hermatically sealed door of modular OT of make Metafluxcomplete |
| 185 | S&F in repairs espagnolet electromagnetic lock mounted on track and on both side key switch suitable for hermatically sealed door having width 3500 mm. |
| 186 | S&F in repairs microprocessor controlled sensor suitable for electromechanical sliding door having width 3500 mm and total weight 250 Kgs and slow speed 20-120 mm/sec,starting speed 20-220 mm/sec,opening speed 800 mm/sec and closing speed 500 mm/sec operated on 3 phase 415 volts 50 Hz supply |
| 187 | Supply and fix in repair1.5 sqmm single core, copperwire, multistranded, PVC insulated, unsheathed, 1100 volts grade complete. |
| 188 | Supply and fix in repair 2.5 sqmm single core, copper wire, multistranded, PVC insulated, unsheathed, 1100 volts grade complete. |
| 189 | Repair/ maintenance of Hot food trolly of any size, replacing unserviceable parts, cleaning it internally and externally including oiling and greasing of moving parts tightening nuts, screws, welding broken parts wherever required and machining job complete. Note:- Spare parts of hot food trolley shall be measured separately as supply only under relevant item of the schedule. |
| 190 | Supply only following spare parts of hot food trolley as required for renewal:- |
| 191 | Heating Element 2 KW as per existing. |
| 192 | Heating Element 1.5 KW as per existing. |
| 193 | Thermostat as per existing. |
| 194 | Wheel assembly with wheels, rubber treated pin, as per existing. |
| 195 | Blower motor 0.50 HP with stand as per existing make and model |
| 196 | Stainless steel handle of 150 mm long dia 20 mm as per existing. |
| 197 | Stainless steel sheet of 5 mm thickness and 2x2 size of grade 304. |
| 198 | S&F in renewal Hot food trolly with 06 container and Lidcover of stainless steel body including heating elements, roller wheelhandle etc all as specified. Note:- Old hot food trolly to be deposited in MES Store yard |
| 199 | Repair/ maintenance of heat blower of any capacityreplacing unserviceable parts, cleaning it internally and externally complete. Note:- Spare parts of heat blower shall be measured separately as supply only under relevant item of the schedule. |
| 200 | Supply only following spare parts of heat blower :- |
| 201 | Selector switch (showing three locations i.e cool, warm and hot as per existing make and model |
| 202 | Selector cum thermostat switch for heat blower as per existing make and model |
| 203 | Heating element upto 2000 watt of porcelain laminated tungston wire as per existing make and model |
| 204 | Indicating lamp(R,Y,B)as per existing make and model |
| 205 | Supply only glass wool of required density |
| 206 | S&F in repairs air purifierPCBdigital type for air purifier as per existing model and make |
| 207 | Servicing/maintenance/ cleaning of Air purifier/ filter of any capicity & make and size from various ward of CH CC area cleaning properly internally and externally and servicing complete |
| 208 | Checking of unserviceable online UPS of any rating among 6/10/60 KVA and find the faulty part and renewal of unserviceable spare part in present of MES rep. Note:- Unserviceable parts of UPS shall be measured as supply only against the relevant item of the schedule. |
| 209 | Supply only following spare parts of UPS :- |
| 210 | Inverter board 6/10/60 KVA |
| 211 | IGBT Driver Board 6/10/60 KVA |
| 212 | Sealed maintenance free dry type battery of capacity 12V, 100 AH complete |
| 213 | Sealed maintenance free dry type battery of capacity 12V, 26 AH complete. |
| 214 | S&F in repairs of Power supply unit with 25 AH SMF battery of 2 x 12 volts for 15 Mins back up complete |
| 215 | M&L for repair and servicing of RO Plant of capacity 1000 LPH and replacement of unserviceable spare parts as required to make it functional.Note:- 1. Minor spares costing upto Rs 500/- to be replaced by the contractor and the rate for the same deemed to be include in the above quoted rate. 2. Major unserviceable spare parts shall be measured as supply only under relevant item of the schedule. |
| 216 | Supply only following spare parts of RO plant :- |
| 217 | Membrane block assembly complete |
| 218 | U.V Rod of suitable capacity |
| 219 | Blue filter of size 20 inch |
| 220 | Blue filter of size 10 inch |
| 221 | Multi Port Control valve |
| 222 | UPVC Ball valve of 15/20mm |
| 223 | Disconnecting all water and electrical connection of the water softener plant by removing all Nuts and bolts and reassemble the same after changing the resin of the cylinder of softener And cleaning of the pipe line connected to boiler with softener for the smooth functioning complete |
| 224 | S&F GI pipe medium grade with all fittings and fixed complete to wall/ceiling or laid in floor /walls etc. of the following sizes complete. |
| 225 | 15 mm bore |
| 226 | 20 mm bore |
| 227 | 25 mm bore |
| 228 | S&F in repairs economizer on the existing position complete. |
| 229 | S&F in repairs of water pump - Triplex type of boiler on the existing position complete. |
| 230 | Supply & mixingcrystal salt suitable for water Softening plant complete. |
| 231 | S&F in repairs of metallic Hose pipe of size 1” of 30” long complete. |
| 232 | Supply & fixing in repairs of V - belt size A-56/as per existing at site complete |
| 233 | Supply & fixing in repairs of V - belt size B - 124/as per existing at site complete. |
| 234 | Supply and fixing in repairs of pump seal for boilers of size 50 mm bore complete |
| 235 | S&F Piston Pump for Boiler existing at site complete. |
| 236 | S&F CNAMS Relay for Boiler existing at site complete. |
| 237 | S&F power contractor of 40/50 Amps 415V, 50 HZ complete. |
| 238 | Supply & mixing of softening compound (Chemical Resin T-40 NA) for removal of iron, calcium and magnesium from water to avoid scaling inside hot water pipe line complete. |
| 239 | Supply only following spare parts of Mechnical Laundary :- |
| 240 | Burner nozzle 6.0 GPH |
| 241 | Piston (HTN-1) |
| 242 | Photocell 8203 |
| 243 | Pressure switch PM1 |
| 244 | Flame coke |
| 245 | Digital temperature ammeter Range 0ºC to 250ºC |
| 246 | Dismantling and disconnecting all water connection and electrical connection of Washer Extractor capacity 60 kg make existing at site and reassemble the same for repair after removing nuts and bolts including oiling, greasing and alignment of inner basket, alignment of shaft, pulley alignment, contact set of contactor cleaning, servicing and cleaning of pneumatic kits, air filter cleaning, cleaning the drain system and turning work and reassemble the same for the smooth functioning of the machine complete. |
| 247 | 60 Kg |
| 248 | 30 Kg |
| 249 | S&F drain pipe for existing capacity and make as required. |
| 250 | Dismantling and disconnecting all water connection and electrical connection of Dryingtumbler capacity of 60 Kg make existing at site and reassemble the same for repair after removing nuts and bolts including Oiling, cleaning, servicing and greasing, balancing and alignment of cylindrical basket, balancing of blower, shaft turning, cleaning and servicing of steam radiator for the smooth functioning of the machine complete. |
| 251 | S&F in replacement of strip heater complete. |
| 252 | Dismantling and disconnecting all water connection and electrical connection of flat work Ironer with double roll make existing at siteand Reassemble the same for repair after removing nuts and bolts including Oiling, cleaning, servicing and greasing, balancing and alignment improvement of chest and rollers, servicing and cleaning of Pneumatic kits, servicing of electrical panel and variable frequency drive for the varying of speed of motor complete. |
| 253 | Supply and Fixing in repair CI \"Y\" strainer of size 50 mm diain condensing/chilledwater line complete dia including modification of pipe line for fixing the strainerand replacement of flanges and nuts & bolts, packing etc as required. |
| 254 | Periodical servicing of air compressor including renewal of Engine oil, key of shaft complete. |
| 255 | S&F in repairs of water solenoid motorized Pneumatic valve 100 mm of outlet complete. |
| 256 | S&F in repairs of water solenoid motorized Pneumatic valve 50 mm of inlet complete. |
| 257 | S&F in repairs of 25 mm Pneumatic angle valve complete |
| 258 | S&F in repairs of 20 mm Pneumatic angle valve complete |
| 259 | S&F in repairs of touch screen of control panel of washer extractor machine of model/make as per existing at site complete |
| 260 | M&L for dismantling of defective induction motor after disconnecting the electric connection from the existing machine of any size and opening the motor cover, removing burnt coil, cleaning , rewinding with super enamelled copper wire of existing size , insulating , varnishing , heating , baking , re assembling including transportation from existing location to workshop and back, refixing of electrical connections, testingafter repair , refixing of following capacities:- |
| 261 | 2 HP |
| 262 | 5 HP |
| 263 | 10 HP |
| 264 | 15 HP. |
| 265 | Supply only spare parts of motors :- |
| 266 | Bearing 6313 SKF (2RS) for AWX-30 kg complete |
| 267 | Bearing 6314 SKF (2RS). |
| 268 | Bearing 6315 SKF (2RS) complete |
| 269 | Bearing 6316 SKF (2RS) for AWX 60 kg. |
| 270 | Bearing6317 SKF (2RS) for AWX 60 kg. |
| 271 | Motor termianl of existing size |
| 272 | Supply only TDS Checking kit with accessories complete. |
| 273 | M&L for Periodical maintenance and servicing of steam boiler 650 or 800 kg/hr any make through authorised service centre,cleaning, desclaing, removing gaskets and defective parts including oiling, greasing for smooth functioning complete. Note:- Unserviceable parts shall be measured as supply only. |
| 274 | Supply only spare parts of boiler 650 or 800 Kg/hr |
| 275 | Optimizer on the existing position complete |
| 276 | Contactor MNX 250 A, capacity 415 volt AC. |
| 277 | Water switch. |
| 278 | Air Regulator 2 way. |
| 279 | Relays 4 to 8 A |
| 280 | Oil filter. |
| 281 | Professional services for rectification of defects on site in mechanical laundry machines viz Extractor / Dryer and flat Ironer etc of any capacity/make/model through authorised service centre of OEM as required.Note:- Items replaced shall be measured seprately under relevant items of the schedule. |
| 282 | Supply only spare parts for Extractor/Dryer/Flat Ironer :- |
| 283 | Iron steam resting pad complete |
| 284 | MPD for drying tumbler complete |
| 285 | Finial cover of vaccum finishing table for linen pressing |
| 286 | Angle valve pneumatic 2” |
| 287 | Pneumatic actuator valve for 30 to 60 kg extractor machine |
| 288 | SMPS 6.5 A for 30 to 60 kg extractor |
| 289 | Supply, laying & fixing UPVC pipes of pressurerating 10 kgf/cm2 laid in trenches of size 15mm bore with all necessary fittings such as bends, elbows, tees, nipple, union, caps & plugs in ground/ on fioor including taking out of unserviceable pipe. Note :- (Rates are inclusive of Excavation, earth work, clamps, nuts, bolts, washers and welding works in this job) |
| 290 | Supply, laying & fixing UPVC pipes of pressurerating 10 kgf/cm2 laid in trenches of size 20 mm bore with all necessary fittings such as bends, elbows, tees, nipple, union, caps & plugs in ground/ on fioor including taking out of unserviceable pipe. Note :- (Rates are inclusive of Excavation, earth work, clamps, nuts, bolts, washers and welding works in this job) |
| 291 | Supply, laying & fixing UPVC pipes of pressurerating 10 kgf/cm2 laid in trenches of size 40 mm bore with all necessary fittings such as bends, elbows, tees, nipple, union, caps & plugs in ground/ on fioor including taking out of unserviceable pipe. Note :- (Rates are inclusive of Excavation, earth work, clamps, nuts, bolts, washers and welding works in this job) |
| 292 | Dismantling defective valve and Supply & fix gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed of size 15mm dia |
| 293 | Dismantling defective valve and Supply & fix gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed of size 20 mm dia |
| 294 | Dismantling defective bib tap and Supply & fix bib taps, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed of size 15 mm dia |
| 295 | Dismantling defective bib tap and Supply & fix bib taps, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed of size 20 mm dia |
| 296 | Material & Labour for repair to wiring of electrical controlpanel of each connected equipments of any capacity at STP of CHCC including opening the nuts & bolts, rubbers, washers and tight / replace of worn out cable lugs, connectors, screws, including replacement of unserviceable parts such as nuts & bolt washers, screws, rubber, are inculde in this job and proper functioning of equipments & testing complete of electrical panel complete. Note : Spare parts reqd for replacement will be paid separately. |
| 297 | S&F in repair MS pipes of80 mm dia medium grade with flanged ends including fittings viz bend, elbow, Tee, Rubber gasket, joints etc any tank of STP/Lift well, making header, riser and painting with two coats of synthetic enamel paint of existing colour complete. Note :- Rates are inclusive of excavation, earth work, clamps, nuts, bolts, washers, welding works etc. |
| 298 | S&F in repair MS pipes of100 mm dia medium grade with flanged ends including fittings viz bend, elbow, Tee, Rubber gasket, joints etc any tank of STP/Lift well, making header, riser and painting with two coats of synthetic enamel paint of existing colour complete. Note :- Rates are inclusive of excavation, earth work, clamps, nuts, bolts, washers, welding works etc. |
| 299 | S&F in repair CI wafer type butterfly 80 mm dia valve, PN1.6,hand lever operated with SS shaft / Disc PTFE gland packing CCS stud and bolts and locking arrangement complete. |
| 300 | S&F in repair CI wafer type butterfly 100 mm dia valve, PN1.6,hand lever operated with SS shaft / Disc PTFE gland packing CCS stud and bolts and locking arrangement complete. |
| 301 | S&F in repair CI butterfly valve full open with operating handle of size 50/65 mm dia including replacement of old nuts & bolts, packings modification of flanges |
| 302 | Labour and tools for taking out the silt & foreign object, Cleaning & Removing sludge from raw sewage collection tank complete upto depth of 15 Mtr any capacity STP complete |
| 303 | Labour and tools for cleaning & removing sludge from Fine bar screen and Oil/ grease chamber complete |
| 304 | Labour and tools for cleaning & removing sludge from MBBR chamber complete |
| 305 | Labour and tools for cleaning & removing sludge from Tube settler chamber complete |
| 306 | Labour and tools for cleaning & removing sludge from Chlorine contact chamber/ Treated water tank complete |
| 307 | Labour and tools for taking out the silt & foreign object, Cleaning & Removing sludge from treated water pond including surrounding surface dressing & cleaningaway all grass vegetation saplings, shrubs, under root and trees pruning and removing rubbish upto a distance 50 mtr outside from the premiss area complete of any capacity STP |
| 308 | Supply of Poly Electrolyte (PE) in powder foam Catonic type grade CN530 or equivalent at all STP location |
| 309 | Supply of Poly Aluminium Chloride (PAC) in powder foam at STP in CHCC location |
| 310 | Supply of liquid chlorine sodium hypochlorite ( Grade - I ) drinking water with 10 % chlorine contents in seald LDPE Container with test certificate and manufacture date mark not more than 02 week ago at STP in CHCC location |
| 311 | Supply of Aerobic Bio Culture for mixing in MBBR chamber and raw sewage collection tank at STP in CHCC location |
| 312 | M&L for taking out outlived MBBR media of sewage treatment plant and supply and fill fresh MBBR media - small cylindrical shaped polyethylene carrier having specific gravity and refilling after cleaning complete material as per existing complete |
| 313 | M&L for taking out outlived tube settler media of STP in CHCC and Supply and fix newPac media or tube settler in tube settler tank as per existing specified size complete |
| 314 | M&L for replacement of sand filter media of sludge drying bed |
| 315 | M & L for paintingof old M S pipe, valves, angle frame, Air blower, motor and pump, Electrical Panel complete STP of any size , secondary/ teritiary type at STP/lift well at CHCC and applying two coats of paint as per existing color with one coat of primer. |
| 316 | Supply and fixing in repairs pressure guage analog type suitable for pressure range 0 to 10 Kg/Cm2 complete |
| 317 | Material and Labour for taking out raw sewage pump & motor set of any capacity, lifting from raw sewage collection sump of STP plant/lift well at CHCC location upto 15 meter depth of rating 3 phase 440 Voltsfor repair or remove blockage and re-installation/ Re-fixing/ lowering in the sewage sump/lift well complete. Note :- (i)Spare Parts will be measured and paid separately under appropriate items. (ii) Stud Nut Bolt, Washer & welding work are included in this job not paid separately. |
| 318 | Dismantling unserviceable raw sewage/lift well motor or submersible motor of following capacities and transporting to contractor workshop for rewinding the same with super enameled water proof copper winding wire of suitable gauge to match the existing copper wire including taping, varnishing, insulating, re-assembling the motor and transporting back to site after complete repairs and reinstallation at existing location and electric connection and testing on full load for satisfactory performance. |
| 319 | 10 HP / 12.5 HP |
| 320 | 7.5 HP |
| 321 | 55 HP |
| 322 | 3 HP |
| 323 | Suply only spares for pump motors :- |
| 324 | Thrust bearing block complete of raw sewage/lift well pump capacity from 2 HP to 10 HP of any make. |
| 325 | Gun metal bushes for raw sewage pump capacity from 2 HP to 10 HPas per manufacturer\"s design and specification. |
| 326 | Sand guard of raw sewage/lift well pump capacity from 2 HP to 10 HP. |
| 327 | Stainless steel metal impellers of raw sewage/lift well pump capacity from 2 HP to 10 HP |
| 328 | Shaft sleeve of raw sewage/lift well pump capacity from 2 HP to 10 HP |
| 329 | Gasket and O-ring of raw sewage/lift well pump capacity from 2 HP to 10 HP |
| 330 | Mechanical seal of motor or pump end of raw sewage/lift well pump capacity from 2 HP to 10 HP |
| 331 | Groove ball bearing of motor or pump side of raw sewage/lift well pump capacity from 2 HP to 10 HP |
| 332 | Shaft protection sleeve of raw sewage/lift well pump capacity from 2 HP to 10 HP |
| 333 | Bowl, cast iron of raw sewage/lift well pump capacity from 2 HP to 10 HP |
| 334 | Bearing sleeve complete of raw sewage/lift pump capacity from 2 HP to 10 HP |
| 335 | Cable grommet (guard) of raw sewage/lift well pump capacity from 2 HP to 10 HP |
| 336 | Coupling of submersible & pump with key motor complete of raw sewage pump capacity from 2 HP to 10 HP |
| 337 | Suppy only oil for raw sewage pump |
| 338 | Sample collection of Raw sewage water from STP (secondary / teritiary type) at CHCC in sterlized bottle and get it tested from any Govt Recognized Lab bimonthly for following tests :(a) Total suspended solid. (b) Total dissolved Solids (c) PH value(d) BOD (e) COD (f) Phosphorus (g) Nitrate (h) Focal Coliform & Total coliform in MPNNote :-Test report for Raw sewage water from STP shall be submitted and cost of the same is deemed to be inclueded in the quoted rate. |
| 339 | Sample collection of treated water from STP (secondary / teritiary type) at CHCC in sterlized bottle and get it tested from any Govt Recognized Lab bimonthly for following tests :(a) Total suspended solid. (b) Total dissolved Solids (c) PH value(d) BOD (e) COD (f) Phosphorus (g) Nitrate (h) Focal Coliform & Total coliform in MPNNote :-Test report for treated water from STP shall be submitted and cost of the same is deemed to be inclueded in the quoted rate.Note2.BOQ item No. 01 to 339 consist of 02 Jobs viz External electrification and Fire Fighting. If any item of same nature and description is noticed and quoted rates found different then payment for the item for which less rate have been quoted shall be made among the twoitems. Descretion of Engineer in Charge shall be final and binding. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail