| 1 | Comprehensive Service/Repair/maintenance and programming for the Automation of intelligent addressable fire alarm control panel at 06 locations in AF stn Kumbhirgram including checking testing and cleaning of Loop card ,Main board, LCD display, Multisensor, sounder, MCP, Zone monitor Module, UV&IR detector, Remote Response indicator, Loop Isolator, Amplifier and Loud speakers carrying out normal repairs for the trouble free and efficient functioning of the entire fire alarm system by providing one engineer to visit four times for one location during contract period all as directed by Engineer in charge.Note:- (i) Cost of new components shall be paid for separately under relevant items of schedule.(ii) Serviciability report submitted to MES duly user signature. |
| 2 | Supply onlyin repair 12 V, 7 AH battery for Inverter supply for back up to all FACP panel complete all as specified and as directed. Make: Exie / Power sonic and equivalent |
| 3 | Supply onlyin repair of Indoor addressable detectors complying with and type certified to EN-54 Addressable type multisensor detector with heat and smoke combination photoelectric / optical with base with self built intelligence and taing down old one complete all as specified and as directed.Make: GST |
| 4 | Supply onlyin repair of electronically addressable intelligent resettable type manual call point with mounting base complying with EN 54 standard and LPCB approved with the specifications as appended below:-a) Power- 24V, ≤ 0.6 mA (Standby Current) ≤1.8mA (Alarm Current)b) Class A ,c) Initiating Mode- Pressing the action plate manually Resuming Mode- Manually Resumed by a special Key,d) Ingress Protection IP-43 & Material-ABSMake: GST |
| 5 | Supply onlyin repair remote response indicator to provide visual indication complete all as specified and directed.Make:- GST |
| 6 | Supply onlyin repair of fire alarm sounder / sirens electronic type horizontal single stage continuous normal operation for at least 50 minutes with sound level 65 db to 120 db measured at 1.5 m from GL with sound output variation of +5db up to 500m range complete all as specified and directed. Make: GST |
| 7 | Supply only in repair Zone Monitor Module for intelligent Fire alarm control panel Make GST Model GST 200-2/1 complete all as specified and as directed. |
| 8 | Supply only in repair Interface Board F2.908.828 (RoHS) for intelligent Fire alarm control panel Make GST Model GST 200-2/1 complete all as specified and as directed |
| 9 | Supply only in repair Display boardfor intelligent Fire alarm control panel Make GST Model GST 200-2/1 complete all as specified and as directed |
| 10 | Supply and fix in repair of two core copper conductor of size 1.5 sqmm FRLSH flexible cable complete all as specified and directed.Make: Havells / KEI/ Polycab |
| 11 | Supply only SMPS card of 220V/27V-100W-R for intelligent Fire alarm control panel Make GST Model GST 200-2/1 complete all as specified and as directed. |
| 12 | Supply only in repair of transformer 220V/27V-100W-R for intelligent Fire alarm control panel Make GST Model GST 200-2/1 complete all as specified and as directed. |
| 13 | Servicing and reconfiguration with new SIM insert in SIMATIC S7-1200 diailer controllers GSM modem panel software for SMS service at 06 nos different location to RTU Panel mimic type installed at fire section in AF stn Kumbhirgram, including testing complete all as specified and directed.Note: 1. seven nos new SIM card with one year validity inclusive in quoted rate. (Sim card service provider decidied by user)2. SMS to be delivered at four numbers at same time from one dailer panel including one sim inserted in RTU Panel mimic type installed at fire section (03 Nos to be provided by user) |
| 14 | Supply and fixing of in repair cordless dynamic type microphone ultra high frequency response complete all specified and directed. |
| 15 | Supply, install, testing and commissioning intelligent addressable fire alarm control panel with original licensed software complying with EN 54 standard & LPCB approved and battery back up to one hours with the specifications as appended below :-(a) Power- AC230 v, 50 Hz, 0,5A.(b) 99 devices.(c) 99 detectors and minimum one loop.(d) Relay - Fire Alarm/F.P.E./Fault/Sounder.(e) Network - RS-485 interface (Max 32 Panels) & network card.(f)PC port -RS- 232 interface & communication card. all as directed by Engr-in-Charge. Make: GST |
| 16 | Supply and fixing of SIMATIC S7-1200 diailer controllers programmable panel with LED indicator for insert of sim card to forward the massage and control the fire panel complete all specified and directed. Make Simens Simatic S7-1200 |