| 1 | Tube Light LED 4’. (NS) |
| 2 | RECESSED PVC CONDUIT PIPE WIRING SYSTEM WITH MODULAR SWITCHES: Wiring in PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5sq. mm, 1100volts grade to be laid in heavy gauge PVC conduit pipe 20mm/ 25mm dia. (ISI Marked) recessed in wall etc., complete with powder coated/anodized concealed metal boxes (1.6mm thick with Brass lugs) required for suitable number of modules (Modular accessories) for having Step type electronic fan regulator (two module)100watts, bell push, 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10Amp. Switches, 16/20Amp. switches with indicator etc. and covered with Frame Plate etc., PVC connector (For Fan Box and Call Bell), Steel Hooks, Sheet metal fan box (1.6mm thick shape hexagonal), Circular junction Boxes (Four-way PVC 1½\" deep for walls and CI 3\" deep for ceiling), bonding to earth with PVC insulated copper conductor single core FR cable (ISI marked) 1sq. mm, 1100volts grade (For 6Amp. wall socket & plug control point) and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):- (i) a) Wiring fan point (Without fan box).CSR item No. 34.02 (i) (a) |
| 3 | Wiring light point. CSR item No. 34.02(ii) |
| 4 | Wiring call-bell point CSR item No. 34.02(iii) |
| 5 | Wiring 6Amp. wall socket point. CSR item No. 34.02(iv) |
| 6 | Wiring 16/20Amp. power plug control point.CSR item No. 34.02(vi) |
| 7 | RECESSED TV, TELEPHONE & NETWORKING SOCKETS OUTLET POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTREM Supply and erection of TV socket, Telephone socket and Networking socket points in powder coated/anodized concealed metal boxes recessed in wall required for suitable number of modules (Modular accessories) for having TV sockets, Telephone sockets RJ11 & Networking socket RJ45 (one module), covered with Frame Plate and other petty material etc., including the cost of above material, cutting and filling up to chases (with finishing the surface)(a)Wiring TV socket point (one module).CSR item No. 34.01 xi (a) |
| 8 | RECESSED AIR CONDITIONER SUPPLY TERMINAL POINT (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES): Wiring air conditioner supply terminal point recessed in wall etc., complete with powder coated/anodized concealed metal boxes required for suitable number of modules (Modularaccessories) for having 25Amp. combined/ universal Socket (shuttered) and modular motor starter 25Amp. (2Module), covered with Frame Plate and other petty material etc. including the cost of above material, cutting and filling up of chases (with finishing the surface):- Wiring AC supply terminal point having 1No. 25Amp. universal Socket (shuttered) erected at AC height and 1No. Motor starter 25Amp. erected at switchboard height. CSR item No. 34.01 (ix ) |
| 9 | PVC INSULATED FR COPPER CONDUCTORCABLES:Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desiredby the Engineer-in-charge: - (ii) Overall size 1.5sq.mm (Un- sheathed). CSR item No. 34.09 (ii) |
| 10 | Overall size 2.5sq.mm (Un- sheathed). CSR item No. 34.09 (iii) |
| 11 | Overall size 4sq.mm (Un- sheathed). CSR item No. 34.09 (iv) |
| 12 | MINIATURE CIRCUIT BREAKERS: Supply and erection of Miniature Circuit Breaker MCB\"s forcircuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:- (ii) MCB Single Pole 6-32amp. (10kA, Curve- C)\". CSR item No. 34.16 (A) (ii) |
| 13 | RCBO\"s: Supply and erection of RCBO (ResidualCurrent Breaker Overload) for Earth leakage, overload and short circuit protection suitable for 240/415 volts 50cycles AC supply with breaking capacity of 10kA as per IEC 61009 in the existing MCB distribution board as per PWDGeneral Specifications including connections with suitable size of thimbles/lugs:-RCBO Double Pole 63amp., Sensitivity30mA. CSR item No. 34.16 (B) (iv) |
| 14 | SHEET METAL DOUBLE DOOR DISTRIBUTIONBOARDFOR MCB\"s/ RCBO\"s/ RCCB’s: Supply and erection of sheet metal Double Door Distribution Boards IP 43-IK09 metal door (dust protected) as per IS 8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper bus bars, shrouded neutral bars, earth bars, cement spill protector, color codedinterconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting miniature circuit breakers/ RCBO\"s/ RCCB\"s in the distribution board (For SP&N distribution board with provision DP MCB\"s/ RCCB\"s/ RCBO\"s as incomer and SP MCB\"s as outgoings and for TP&N horizontal distribution board with provision TPN/ FP MCB\"s/ RCCB\"s/RCBO\"s as incomer and SP MCB\"s as outgoings) as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc.:-. CSR item No. 34.17 (iv) |
| 15 | Earthing with G.I. wire/ rope in G.I. pipe partly recessed and partly on surface complete with 150cm long 50mm dia. G.I. earth pipe (Cutting threads and 36 Nos. holes, 1cm dia. to make a mesh around the GI Pipe) and with G.I. reducing socket including erection of the same, 10.50 meter (34.44 feet) below ground level with 20Kg. charcoal & salt mixture etc., up to 14 meter in length (including boring &refilling). (a) Earthing with 8 S.W.G. (4mm dia.) G.I. wire in 15mm dia G.I. pipe with G.I. reducing socket 50mm x 15mm (up to 14Metre in length). screws and of given overall dimensions and to be fixed with G.I. bolts and nuts/rag bolts and nuts etc. complete with all accessories including connections with suitable size of thimbles, bonding to the existing earth and painting etc. as desired by the Engineer-in-charge at site: - (iii) Bus Bar Chamber 100amp., 415volts Overall Dimensions (300mm x 345mm x120mm) nominal. CSR item No. 34.13 (xiii) (a) |
| 16 | DISMANTLING WIRING POINTS & FITTINGS: Dismantling old wiring points including necessary repairs to wall etc:- (i) Fan, light or call bell point . CSR item NO. 34.39 (i) |
| 17 | (ii) Wall socket, power plug point . CSR item NO. 34.39 (ii) |