| 1 | SH: I -Design, Supply, Installation, Testing & Commissioning of Automatic Gas Suppression System comprising PESO approved clean agent cylinder(s) (42 bar or above) complete as per minimum materials and accessories as per SCC page no. 147 & 148 and Technical Specifications with UL/VdS approved valve assembly, supervisory switch for pressure monitoring, pressure gauge with burst disc, electronic/solenoid control head, pressure operated control head, safety cap, flexible hose, NRV, pressure switch and mounting strap; required nos. of UL/VdS listed nozzles, complete piping network and manifold designed with OEM’s UL/VdS approved software for room dimensions and pressure calculations; gas release control panel with abort and manual release stations; smoke detection system, MS pipe; 2C x 1.5 sqmm FRLS cabling, batteries and accessories; filling of clean agent FK-5-1-12 gas (zero ODP, colourless, odourless) at UL/VdS approved filling stations; including submission of OEM-approved cylinder sizing, nozzle layout, piping design and pressure calculations prior to installation – complete as required for protection of rooms of given volumes (including spaces above and below false ceiling wherever applicable). All rooms shall have independent system. 100% reserve cylinders shall be considered for equipment room of ATC building only. |
| 2 | IT Server Room (G.F) : Surface Area : 17.40 Sq. Mtr., Height:CV: 1.70 Mtr., RV: 2.60 Mtr., FV:0 Mtr. Total Volume: 74.82 cub Mtr. |
| 3 | FTI Room : Surface Area : 15.75 Sq. Mtr., Height:CV: 1.20 Mtr., RV: 2.77 Mtr., FV:0 Mtr. Total Volume: 62.53 cub Mtr. |
| 4 | EPBAX Room : Surface Area : 14.50 Sq. Mtr., Height:CV: 1.20 Mtr., RV: 2.57 Mtr., FV:0 Mtr. Total Volume: 54.67 cub Mtr. |
| 5 | IT Server Room First Floor (ATC): Surface Area : 18.00 Sq. Mtr., Height:CV: 1.70 Mtr., RV: 2.60 Mtr., FV:0 Mtr. Total Volume: 77.40 cub Mtr. |
| 6 | Battery & UPS Room First Floor (ATC): Surface Area : 25.00 Sq. Mtr., Height:CV: 1.70 Mtr., RV: 2.60 Mtr., FV:0 Mtr. Total Volume: 107.50 cub Mtr. |
| 7 | AMSS Room 2nd Floor: Surface Area : 21.60 Sq. Mtr., Height:CV: 1.20 Mtr., RV: 2.50 Mtr., FV:0 Mtr. Total Volume: 79.92 cub Mtr. |
| 8 | Equipment Room 3rd Floor (ATC) (with 100% Reserve Cylinder) Surface Area : 100.00 Sq. Mtr., Height:CV: 0.60 Mtr., RV: 3.10 Mtr., FV:0 Mtr. Total Volume: 370.00 cub Mtr. |
| 9 | Battery Room: Surface Area : 16.20 Sq. Mtr., Height:CV: 1.20 Mtr., RV: 2.60 Mtr., FV:0 Mtr. Total Volume: 61.56 cub Mtr. |