| 1 | ELECTRICAL PARTWiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required: Group C |
| 2 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \"C\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. |
| 4 | 2 x 1.5 sq. mm.+ 1x 1.5 sq. mm earth wire |
| 5 | 2 x 2.5 sq. mm.+ 1x 2.5 sq. mm earth wire |
| 6 | 2X4 sq. mm + 1X4 sq. mm earth wire |
| 7 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 8 | Supplying and fixing following size/ modules, Gl box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 9 | 1or 2 Module (75mmX75mm) |
| 10 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections butexcluding modular plate etc. as required. |
| 11 | 6 pin 15/16 A socket outlet |
| 12 | 15/16 A switch |
| 13 | Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 14 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 15 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 16 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 35 sq. mm |
| 17 | Laying and fixing of one number PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 18 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm |
| 19 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 20 | 3½ X 35 sq. mm (32mm) |
| 21 | 3½ X 25 sq. mm (28mm) |
| 22 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 23 | way (4 + 12), Double door |
| 24 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 25 | 4 way (4 + 12), Double door |
| 26 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc.as required. |
| 27 | For 4 way, Double door TPN MCBDB |
| 28 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc. as required. |
| 29 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing andcommissioning etc. as required. |
| 30 | Single pole |
| 31 | Triple pole |
| 32 | Triple pole and neutral |
| 33 | Supplying and fixing of light class G.I. pipe of 80 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required. |
| 34 | Supply of1.1 KV grade XLPE insulated, PVC seathed,Aluminium conductor armouredpower cables conforming to IS 7098 ( Part - 1) 2011 and ISI markedof following sizes. |
| 35 | 3.5 x 35 sq mm A2XFY cable. |
| 36 | 3.5 x 25 sq mm A2XFY cable. |
| 37 | Supply and fixing of 1phase,50 Hz, 750 mm Sweep (1400 rpm),watts-250W, Air delivery-23000CMH, Industrial, heavy duty, Sturdy metallic body, Wall fan with powerfull air circulating motor for contineous operation, Floating arrangement for changing the position of oscillation, motor protection and thermal over load protection device with auto re set,to be fixed with suitable arrengement on the MS structure, nut-bolt connection, testing and commissioning etc. as required. (750 mm Thunder storm pro wall of Orient or equivalent.) |
| 38 | Supply and fixing from shed top rafter (6m - 7.5m) and hangingwith down rod of 140 watts, 25000 Lumen output, LED High Bay light luminarier, 180 lm/W, IP-65, IK-08, Lifewith driver inside a PDC houing energy efficient light fitting complete to ensure uniform distributionlight. including supply and fixing of suitable down rod /GI anglefor fixing at rafter/parlin of structural shed (hight-15m approx), connection,testing, commissioning as required. ( BY712P LED250S 5700 WB H PSU of Philips or equivalent.) |
| 39 | Supply and Fixing of Road lighting luminaire with SPD and IP 66 protection including L shape GI pipe, clamp, nut bolt and all accessories for fixing wall/trust mounting, connection alongwith 3x1.5 sq.mm FRLS PVC insulated copper conductor single core wire, testing, commissioning as required. (BRP331 LED54 CW R5N PC PSU S1 V1 of Philips or equivalent.) |
| 40 | Supply and Fixing of 200W LED Floodlight luminaire with system efficient and wide beam optics light fittings complete including all accessories MS angle, clamp, nut, bolt etc. for fixing/mounting in pole/trust, connection, testing, commissioning as required. (BVP283 LED240 CW FG SY5WB 200W SPD V1 of Philips or equivalent.) |
| 41 | Supply and Fixing of 4ft run length Essential Smart Bright luminaire comprises of extruded aluminum housing offering superior finish long life and high transitivity polycarbonate diffuser resulting in high efficacy and uniform lighting.suitable for surface, Clamp, nut bolts and all accessories for fixingwall trust mounting, connection, testing, commissioning etc as required(BN170C LED20S-6500 PSU L120 ) of Philips or equivalent.) |
| 42 | Supplying and fixing of following rating and following pole, 240/415 V, 10 kA, \"C\" curve,miniature circuit breaker in existing DB complete with connections, testing and commissioning etc. as required.make- Legrand oreqv |
| 43 | 63A, FP |
| 44 | 63A, TP |
| 45 | CIVIL PARTClearing jungle including uprooting of rank vegetation, grass, brush wood and saplings of girth upto 30 cm measured at a height of 1 m above ground level and removal of rubbish upto a distance as per the instruction of EIC outside the periphery of the area. |
| 46 | Demolishing brickwork manually/ by mechanical meansincluding stacking of serviceable materials and disposal of unserviceable materials within CMERI Institute campus in cement mortar. |
| 47 | Dismantling asbestos/GI profile sheet roofing including ridges, hips valleys and gutters etc and stacking within CMERI Institute campus as per the direction of EIC. |
| 48 | Dismantling steel work in single sections including dismembering and stacking within within CMERI Institute campus as per the direction of EIC in: Channels, angles, tees and flats. |
| 49 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead within CMERI Institute campus as per the direction of EIC and lift upto 1.5 m, as directed by Engineer-incharge.All kinds of soil |
| 50 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 51 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size) |
| 52 | Providing and laying in position ready mixed cement concrete for plain cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana/ Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering and finishing as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in in design mix shall be payable separately. In case the cement content design mix is more than 110% of the minimum specified cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works upto plinth level : Concrete of M15 grade with minimum cement content of 240 kg /cum |
| 53 | 62 mm thick cement concrete flooring with concrete hardener topping, under layer 50 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate, 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacture’s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete. |
| 54 | Centering & shuttering including strutting, propping etc & removal of form for lintels, beams, cantilevers etc. |
| 55 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 56 | Providing and laying in position ready mixed cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum |
| 57 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. |
| 58 | Providing and laying in position ready mixed cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works above plinth level upto floor V level Concrete of M25 grade with minimum cement content of 330 kg /cum |
| 59 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 60 | 12 mm cement plaster of mix 1:4 (1 cement: 4 coarse sand) |
| 61 | 15mm cement plaster on rough side of mix 1:4 (1cement: 4coarse sand) |
| 62 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 63 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes |
| 64 | Providing and fixing 1 mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings i.e. hinges, aldrop etc.complete, including applying a priming coat of approved steel primer. Using M.S. angels 40x40x6 mm for diagonal braces |
| 65 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : One or more coats on old work |
| 66 | Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm) |
| 67 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / panelling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portion Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15) |
| 68 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 5 mm thickness (weight not less than 12.50 kg/sqm) |
| 69 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour :New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre |
| 70 | Filling the gap in between aluminium frame & adjacent RCC/ Brick/ Stone work by providing weather silicon sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete. Upto 5 mm depth and 5 mm width |
| 71 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-Charge) of total coated thickness 0.50 mm (base metal of minimum 0.45 mm thickness with total coating thickness of 0.05mm) with zinc coating 120 grams per sqm as per |S: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 72 | Providing and fixing precoated galvanised steel sheet roofing accessories of total coated thickness 0.50 mm (base metal of minimum 0.45 mm thickness with total coating thickness of 0.05 mm) with Zinc coating 120 gram per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screws complete : Ridges plain (500 - 600mm) |
| 73 | Providing and fixing Shutter Type: Motorised Rolling Shutter of with following technical specifications: Performance CharactersticsProfile Type: RS83ADProfile Height: 83mmRoller Curtain: The shutter curtain is constructed from double skinned aluminium laths. Each lath is retained by interlocking with each other.Surface: Aluminium with one coat of grey epoxy primer by sprayMaterial Thickness: 2 x 1.1mmStructure Shape: CurvedSupport Brackets: Mild Steel with one coat of grey epoxy primer by sprayShaft Shaft: is manufactured from mild steel tube of suitable outside diameter and wall thickness to suit the shutter application and is unsprungFinish: One coat of grey epoxy primer by spraySide Guides: 2.0mm thick heavy duty Omega Galvanised Steel with integrated seals fitted to the lips of the guides to prevent metal-to-metal contact thus ensuring a smooth & quiet operationFinish: One coat of grey epoxy primer by sprayBottom Profile:Bend-resistant double-skinned extruded Aluminium profile for additional strength .The bottom rail is fitted with extruded rubber bottom seal that will seal against the floor when the door is fully closed.Finish:One coat of grey epoxy primer by sprayLocking arrangement:Not ApplicableSeals: Standard on side guides and bottomHood Cover: Pressed galvalume steel hood box complete with reinforced bracket as required to suit the shutter width.Finish: One coat of grey epoxy primer by sprayCE Certified CRS Compact Gear P.R.C. Make Indirect Drive OperatorDrive Unit: Indirect drive operator, System power supply wired with industrial plugSafety mechanism: Patented safety mechanism for chain failure with inbuilt limit switchesControl Switch: Three station push button with deadman controlEmergency manual operation: Emergency operation by means of chainMotor Cover: Pressed galvalume steel motor cover with one coat of grey epoxy primer by spray |
| 74 | Providing and fixing roof top wind driven fully automatic turbo ventilator (material-Aluminium) of throat diameter 24\", body diameter 30\" all complete. |
| 75 | Providing and fixing Polycarbonate Ventilator Base Plate, thickness of the Sheet 1.21 mm and size 1700 MM X 1200 MM with necessary fittings. |