| 1 | Preventive and comprehensive maintenance/Annual maintenance contract of complete fire detection and alarm system(s) installed at ADC and CTVS Centre in reliable, safe and efficient manner using latest techniques & expertise consultancyby regularly examining the sensor/detector, Main fire alarm control panels, Repeater panels, Hooters, MCP, Sirens etc of various type / capacity / make, including making the non-functional parts of fire alarm system into fully functional condition, attending day to day complaint / fault(s) in general shift of 08 hrs every day incl Sunday and holiday, including quarterly cleaning of the detectors and monthly joint testing/inspection of the complete fire alarm system, including replacement of minor items such as wire, lugs, nut, bolts, screws, electronic circuit, chip etc complete all as specified and directed by Engr- in- Charge.Note : (i) The contractor will have to employ minimum 01 Nos of Fire technician & 01 No Helper every day incl Sunday and holiday to attend day to day complaints as well as periodical / routine maintenance and joint inspection / testing of fire alarm system(s) installed at various locations / areas and submit the feedback on daily basis to the Engineer-in-Charge/ concerned JE E/M.(ii) The tradesmen/Technician (s) should be having minimum 3 years work experience of respective trade.(iii) In case, additional manpower other than mentioned here-in-above, will be required for smooth functioning of fire alarm system or attending day to day complaints or periodical / routine maintenance or joint inspection / testing of fire alarm >>>>> |
| 2 | system(s) installed at various locations / areas, the contractor shall arrange the same without any extra cost to Deptt.(iv) The comprehensive / preventive / periodical maintenance includes monthly joint inspection / testing of entire fire alarm system(s), in presence of rep of user. The joint inspection / test report duly signed by contractor and MES representative will be submitted along with RAR/payment. If contractor fails to complete the joint inspection / testing of fire alarm system(s), the compensation / penalty of Rs. 1000.00 (Rupees One Thousand only) per day shall be recovered from the contractor’s dues.(v) The complete fire alarm system(s) will be handed over to contractor in existing condition and no claim on this effect will be accepted at any stage. Hence, the bidder is advised to visit the site to assess the quantum of work to be carried out in this contract and quote their rates accordingly.(vi) The cost of all kind of repair /servicing/ replacement of defective equipment/devices and other minor parts/spares or cell/ batteriesas and when required for making the entire fire alarm system(s) fully functional, is deemed to be included in quoted rates and no extra cost shall be paid to the contractor on this effect. However, the Cost of majorequipment / devices shall be measured & paid separately under relevant item of this Schedule.(vii) All the complaint / fault (s) will be addressed within 02 hrs from the time of receipt of complaint. If, contractor or his tradesmen fails to attend the complaint within 02 hrs from the time of receipt of complaint verbaly or telephonically, the >>>> |
| 3 | compensation/penalty of Rs. 500.00 (Rupees Five Hundred only)per complaint per hr for first 04 hr and after that Rs. 1000 (Rupees one thousand only ) per complaint each day (i.e 24 hrs ) shall be recovered from the contractor’s dues.(ix) The contractor shall provide all the necessary T&P, uniform and stationery such as Attendance Register, Periodical Maintenance Register, logbook etc to the technician without any extra cost to Dept. |
| 4 | M&L in replacement of Detectors Complying with addressable type smoke detector all as per existing make and model complete all as specified and directed by Engr- in- Charge. |
| 5 | M&L in replacement of Detectors Complying with Addressable type multisensor detector with heat and smoke combination as per existing make and model complete all as specified and directed by Engr- in- Charge. |
| 6 | M&L in replacement of Addressable control module as per existing make and model complete all as specified and directed by Engr- in- Charge. |
| 7 | M&L in replacement of Addressable Monitor module as per existing make and model complete all as specified and directed by Engr- in- Charge. |
| 8 | M&L in replacement of Addressable manual call point resettable type as per existing make and model complete all as specified and directed by Engr- in- Charge. |
| 9 | M&L in replacement of remote response indicator as per existing make and model complete all as specified and directed by Engr- in- Charge. |
| 10 | M&L in replacement of short circuit isolator/fault isolator module as per existing make and model complete all as specified and directed by Engr- in- Charge. |
| 11 | M&L in replacement of loop poweredsounder as per existing make and model complete all as specified and directed by Engr- in- Charge. |
| 12 | S&F in replacement UV/IR flame detector for fire alarm system with multispectral sensitivity with UV band coverage in the range of 185 nm to 260 nm and IR band coverage of 3000 nm to 5000 nm, detection range of upto 30 meter, response time less than 3 seconds or less to detect a 1 sqft flame at 30 m, multiple outputs such as relay contacts for fire alarm, fault and auxilliary alarm, DC 24 V , 1.8 W, IP66 for dust and water ingress, should meet standards such as zzis/ IEC 60079, false alarm immunity with stainless steel or robust metal housing with suitable conduit entry all as spfd and as directed. |
| 13 | M&L in replacement, testing and commissioning of 99 zones digital main wireless fire alarm panel with large LED display all radio emitter through radio waves, alarm 110 db, displays diffrent zones of smoke sensors transmitted by radio emitter, 24 volts DC (Rechargable batteries) including 3 pin socket point 5 ampsfor connected for charging with 12 Hours battery back up with Addressing methodof digitals nos, display on screen with indoor use, made in MS body, fixed on wall with metal stand with base or as per existing make and model complete all as specified and directed by Engr- in- Charge. |
| 14 | M&L in replacement of intelligent analog emitter with microprocessor based controller based on radio waveswith supported manual call point and hooter with 110DB output in MS body, works on 220 volts used for repeating signals to main control panel or as per existing make and model complete all as specified and directed by Engr- in- Charge. |
| 15 | M&L in replacement of intelligent analog wireless smoke detector based on radio waveswith senitivity as per NFPA 72, specification EN54 Pt7, monitoring continuosly self checking, detection principle photo electric light scatter, including operating voltage of 9 volts DC (Alkaline batteries), unique address embedded in detector, moulded ABS body in white colour or as per existing make and model complete all as specified and directed by Engr- in- Charge. |
| 16 | Supply & fix, testing and commissioning of micro controller based 2 loop Addressable type fire alarm panel made with CRCA sheet with control switch for Reset, silence, Lamp-test and Evacuate, also with visual LED indication of control unit and loop line, 30 devices can be connected to each loop, user friendly programming etc complete all as specified and directed. |
| 17 | M&L in replacement, testing and commissioning of 10 zones fire alarm panelwith 230 V AC input, 24 V DC output with battery backup, zone EOL resistor for circuit integrity, maximum load per zone according to detector specifications, 10 independent zones for fire detection and alarm monitoring and each zone equipped with two indicators for clear fire/ fault status, support for mutiple alarm notification options including external sounders, programmable silence, reset and test modes to meet operational requiremnts, built in power supply with battery charger and backup for uninterrupted supply all as per IS 2189:1999 and as spfd and directed by Engr in Charge. |
| 18 | Supply & fixing in replacement of two core FRLSPVC insulated, unsheathed, multi stranded, copper conductor cable of size1.5 sqmm complete all as specified and directed by Engr- in- Charge. |
| 19 | Supply and fixing intelligent ceiling mounted 6 volts LED emergency exit light slim type specially used for providing direction and emergency backup up to 4 hours all as specified and directed by Engr- in- Charge. |
| 20 | Supply & fixing in replacement of rigid non metallic PVC conduit of 25 mm dia inclusive all types fitting accessories likes, bends, tees, elbows, reducers, lock nuts, saddles, pipes hooks etc complete all as specified and directed by Engr- in- Charge. |