| 1 | Total amount of Sch \"A\" Sec-I ( BUILDING WORKS ) Lump sum price worked out by the contractor for \" BUILDING WORKS \" as listed in schedule \"A\" Part-I |
| 2 | Total amount of Sch \"A\" Sec II (SITE CLEARANCE, SITE DEVELOPEMENT & MISC. EARTH WORKS) Lump sum price worked out by the contractor for \" SITE CLEARANCE &Earth Works \" as listed in schedule \"A\" Part-II |
| 3 | Total amount of Sch \"A\" Sec III (INTERNAL ELECTRIFICATION WORKS) Lump sum price worked out by the contractor for \" INTERNAL ELECTRIC SUPPLY WORKS \" as listed in schedule \"A\" Part-III |
| 4 | Total amount of Sch \"A\" Sec IV(ROAD, PATH AND CULVERTS WOKS) Lump sum price worked out by the contractor for \" ROAD/PATH/CULVERT WORKS \" as listed in schedule \"A\" Part-IV |
| 5 | Total amount of Sch \"A\" Sec V(EXTERNAL WATERSUPPLYWORKS) Lump sum price worked out by the contractor for \" EXTERNAL WATERSUPPLYWORKS \" as listed in schedule \"A\" Part-V |
| 6 | Total amount of Sch \"A\" Sec VI(EXTERNAL ELECTRIC SUPPLY & LIGHTENING PROTECTION WORKS) Lump sum price worked out by the contractor for \" EXT ELECTRIC SUPPLY & LIGHTENING PROTECTION WORKS \" as listed in schedule \"A\" Part-VI. |
| 7 | Total amount of Sch \"A\" Sec VI(AREA DRAINAGE WORKS) Lump sum price worked out by the contractor for \" AREA DRAINAGE WORKS \" as listed in schedule \"A\" Part-VI. |
| 8 | Schedule \"A\"Section-VIII (Misc Items of Works) Note :This schedule is not pre-priced by MES and the pre-priced rate indicated as \"Rs 0.00\" under Col. 5 siginifies this fact only. |
| 9 | INTERNAL ELECTRICAL SUPPLY WORKSEarthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below groundlevel) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, checknuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion, complete all as specified and directed. |
| 10 | Supply and fixing Flame proof distribution board 415V, 6 Way for mounting MCBs/RCBO\"s ELCB etc. as per IS specification and CMRI approved of factory made fabricated out of cast aluminium alloy LM-06 gray appoxy powder coated finish, fitted with DIN Channel neutral link, Earth links and 200 Amps rated bus bar. The DB shall be having with IP-65 protection. The DBs shall also be consisting and including the following:- (a) MCB 4 pole,63A415 volts AC 50Hz 40 Amps - 01 No. (b) MCB single pole 16 A, 240 volts AC 50 HzAmps - 6 Nos. |
| 11 | Supply and Fix flame proof flexible metalicconduitwith rubber gaskiton both end of length 300mm long and20 mm dia as per IS/IEC:60529:2001 all as specified and directed. |
| 12 | M&L forFlame proof submain wiring with two single core 2.5 sq mm FRLSH PVC insulated, unsheathed,cable 1100V grade heavy duty, copper conductor multistranded,drawn in and includingsteel stove enameled black conduit heavy duty ISI marked of size 20mm dia as per IS:3837-1976surface type including allflame proof conduct fittings and accessories such as tees junction boxes, bends duly tested by CMRI Dhanbad , including drawing continuous earth wire PVC insulated unsheathed 1100V grade cable withstranded copper conductor of size 1.5 Sqmm and connected to earth dolly complete conforming to IS-694 all as specified and directed by Engrs-in-Charge. |
| 13 | Supply and Fixing of 100W LED flame proof Flood Light with System Lumen Efficacy≥100 Lm/W operating Voltage between 140-270 Vac, LED CCT 5665±355K as per ANSI BIN, Luminaire intergal driver with 5KV surge protection, Over Load Protection, No Load Protection and BIS Marking (R no. for Driver), Driver Certiifcation IEC64347-2-13 IS(15885), Driver should be concealed under IP66,Over all electrical efficency more than 90%, Driver electrical efficiency will be > 85% connecting with PVC copper cable of size 3x1 sqmm as per IS 10322 at Least 2 Year on site warranty without any condition complete all as specified and directed. |
| 14 | RCC CULVERT |
| 15 | RCC Culvert complete, incl exc, PCC, BB work in CM 1:4, RCC slab in M-25 concrete of00.90 m clear span all as per Drg No STD-1315 Sh 1/1 |
| 16 | (b)-Do- E119 but of 3.00 M clear span |
| 17 | EXTERNAL ELECTRIC SUPPLY& LIGHTNING WORKS |
| 18 | M&L for erection of intenally and externally hot dipped galvanised 3mm thick steel sheet (grade S355JO) 7mtr long \"smart poles\" of octogonal cross section with intergral camouflaged junction box for incorporating controlgears with flust door with necessary locking arrangements, having base plate 220x220x12mm to be grouted on suitable size shallow foundation with M-15 concrete with 700 mm long 04 Nos 20mm dia, bolts and 3mm anchor plate, mounted with pole top mounting spigot type hot galvanised single arm street light mounting bracket single arm bracket 1000mm in length in all as per instructions and technical specification of Engr-in-Charge. |
| 19 | Supply, installation, commissioning and testing of Main LT cubical panel outdoor type with locking arrangement made out of CRCA sheet of 3.15 mm thick having front openable door, vermin and weather proof having canopy for protection, all surfaces powder coated painted and including 200 Amp rated aluminium bus bars with cubicle painted with Seimens grey colour all as per manufacturer\"s instructions mounted on angle iron frame of size 50x50x6mm having four legs of 60 cm long grouted to PCC foundation and including following fittings, fixtures and accessories:- INCOMING:-(a) MCCB 63 Amps, 4 pole, 16 KA, 415 Volts - 01 No. (Main) OUTGOING:- (a) MCB TPN 40 Amps 415 Volts 10 KA - 02 No. (BLDG/ Spare)(b) SPN 06-32 Amps 230 Volts- 01 No. (Spare)(c) Digital type Volt meter 0-500 Volts square type with selector switch- 01 No. (d) Digital type Ammeter 0-200 Amps square type with selector switch- 01 No. (e) Wiring complete with copper wire of suitable size (f)Indicator lamp LED type, set of three marked red, yellow & blue - 03 Set |
| 20 | Material and labour for precast factory made LT cable route indicator/marker with ingreeve \"LT CABLE\" on block made out of RCC of size 1000x150x150mm (with 400mm under ground and 600mm above the ground) 4 nos of 6mm round bar fixed in ground with two coat of yellow synthatic enamel paint over a coat of red oxide primer and red colour of \"LT Cable\" ingreeve, with 15cm offsets on all 04 sides of the indicator/ marker(including excavation and returning filling) complete all as directed by Engr-in-charge. |
| 21 | Labour for boring underground upto 100 mm bore for road crossing 3 metre to 10 metre not exceeding 1.5 metre in depth for laying of electric cable and GI tubing in soft/loose soil complete all as specified and directed. |
| 22 | Supply and fixing of Static Discharge Handles made out of 20mm dia, 500mm length electrolytic copper solid rod fixed on wall with Dough moulding compound (DMC) insulator, brass spacers and connected to the static discharge conductor/ 20 X 3 mm copper strip with brazing all as speicfied and directed. |
| 23 | S&F Digital thermo hygro meter all as specified and directed |
| 24 | Copper strip 20 X 3 mm, ETP grade material (as per IS 191) with copper fixing hardware\"s Dough moulding compound (DMC) insulator at every 0.6 mtr interval for supports the down conductor to be fixed on wall laid in ground as per specified and directed by Engineer-in-Charge |
| 25 | Earthing complete with and including galvanised steel earth plate electrode 600 mm x 600 mm x 6 mm surrounded by a mixture of charcoal and salt in alternate layers burried directly in ground vertically in a pit of depth not less than 2.25 m deep below ground level with top edge of earth plate at a depth of not less than 1.5 m below ground level, connected with and including galvanised iron or steel earth wire, 4mm diaby means bolts, nuts, check nuts and washers made out of galvanised iron, 15 mm bore (medium grade) GI pipe for protection of earthing lead, 20 mm bore (mediumgrade) GI pipe for watering with funnel, wire mesh and including necessary excavation and earth work, PCC 1:2:4 type B-1 pit and 50 mm thickRCC 1:1.5:3 type A-1 reinforced with XPM (weight not less than 3 kg/sq m) pit cover, C.I frame, charcoal and comman salt filling in alternate layers, complete all as shown and specified in electrical plate No. 3 of SSR Part-I (2009) complete all as specified and directed by Engineer-in-Charge.NOTE : The unit rate includes for protecton pipe 15mm and GI earth wire4mm from top of earth plate upto 7.50 metre above ground level. |
| 26 | NOTES APPLICABLE TO SRL ITEM NO. 25 ABOVE : (i) The cost of earth lead /stripof GI/copper and GI pipe for protection of earth lead/strip upto 7.5m is included in the quoted rate.(ii) The earth chamber shall be constructed 50 cm away from the edge of earth pit and cost of the cost of excavation & earth workis deemed to be included in the quoted rate. (iii) The new earthing so constructed must have resistance value below 2 ohms. If aforesaid resistance value is not achieved, contractor shall make proper addition/alteration to the newly constructed earthing at his own cost. |
| 27 | Material & Labour for earthing complete with galvanized steel earth plate 60 cm X 60 cm X 6 mm thick buried vertically in ground to depth not less than 2.25 metres deep below ground level, with top edge of earth plate not less than 1.5 m below ground level, connected to galvanized iron earth strip of size 25 mmx 4mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel including excavation and earth work in any type of soil ,and removing surplus soil to a distance not exceeding 50 metres ,GI pipe light grade 40mm bore for protection of earth wire upto 7.5 metre from earth plate electrode and connected to continous earth lead on pole/test point, supplying and laying charcoal dust common salt in alternate layers (each layer shall be 15 cm thick) , GIfunnel and wire mesh, 20mm dia GI pipe light grade for watering including necessary excavation and earth work, PCC 1:2:4type -B1 and 40 mm thick RCC M-25 (Design Mix) coverwith handle reinforced with 8 mm dia mild steel reinforcement at 15 cm c/c spacing in both ways with handle of 8 mm dia bar for fitting , pit cover, CI frame,all as shown and specified in electrical plate No 3 of SSR Part I complete all as specified and directed . |
| 28 | NOTES APPLICABLE TO SRL ITEM NO. 26 ABOVE : (i) The cost of earth lead /stripof GI/copper and GI pipe for protection of earth lead/strip upto 7.5m is included in the quoted rate.(ii) The earth chamber shall be constructed 50 cm away from the edge of earth pit and cost of the cost of excavation & earth workis deemed to be included in the quoted rate. (iii) The new earthing so constructed must have resistance value below 2 ohms. If aforesaid resistance value is not achieved, contractor shall make proper addition/alteration to the newly constructed earthing at his own cost. |
| 29 | S&F MCCB,Four pole, 63 AMPS, 415 Volt 16kA, with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, Adjustable short circuit for each phase from 6 - 10 x In complete all as specified and directed. |
| 30 | Supply and fix of weather proof cable with Copper conductor 2.5 sqmm 3 core, PVC round sheated for connection from looping box to street light fitting complete all as specified and directed. |
| 31 | Supply and fixing of Static Discharge Handles made out of 20mm dia, 500mm length electrolytic copper solid rod fixed on wall with Dough moulding compound (DMC) insulator, brass spacers and connected to the static discharge conductor/ 20 X 3 mm copper strip with brazing all as speicfied and directed. |
| 32 | S&F Digital thermo hygro meter all as specified and directed |
| 33 | Copper strip 20 X 3 mm, ETP grade material (as per IS 191) with copper fixing hardware\"s Dough moulding compound (DMC) insulator at every 0.6 mtr interval for supports the down conductor to be fixed on wall laid in ground as per specified and directed by Engineer-in-Charge |
| 34 | Material & Labour for earthing complete with galvanized steel earth plate 60 cm X 60 cm X 6 mm thick buried vertically in ground to depth not less than 2.25 metres deep below ground level, with top edge of earth plate not less than 1.5 m below ground level, connected to galvanized iron earth strip of size 32mmx6mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel including excavation and earth work in any type of soil ,and removing surplus soil to a distance not exceeding 50 metres ,GI pipe light grade 40mm bore for protection of earth wire upto 7.5 metre from earth plate electrode and connected to continous earth lead on pole/test point, supplying and laying charcoal dust common salt in alternate layers (each layer shall be 15 cm thick) , GIfunnel and wire mesh, 20mm dia GI pipe light grade for watering including necessary excavation and earth work, PCC 1:2:4type -B1 and 40 mm thick RCC M-25 (Design Mix) coverwith handle reinforced with 8 mm dia mild steel reinforcement at 15 cm c/c spacing in both ways with handle of 8 mm dia bar for fitting , pit cover, CI frame,all as shown and specified in electrical plate No 3 of SSR Part I complete all as specified and directed. |
| 35 | NOTES APPLICABLE TO SRL ITEM NO. 32.00 ABOVE : (i) The cost of earth lead /stripof GI/copper and GI pipe for protection of earth lead/strip upto 7.5m is included in the quoted rate.(ii) The earth chamber shall be constructed 50 cm away from the edge of earth pit and cost of the cost of excavation & earth workis deemed to be included in the quoted rate. (iii) The new earthing so constructed must have resistance value below 2 ohms. If aforesaid resistance value is not achieved, contractor shall make proper addition/alteration to the newly constructed earthing at his own cost. |
| 36 | Providing and laying 30 mm thick (consolidated thickness) Bituminous Concrete (BC) layer conforming to clause 507 of MoRT&H specifications for road and bridge work (Fifth Revision) including cost of coarse aggregates, fine aggregates, filler, 5.5% binder (paving Bitumen grade VG-30) content by weight of total mix and crushed aggregates of grading 2, Anti Stripping Agent, Warm Mix Additives (quantity, quality and grade as per the approved Job Mix Formula) etc,cleaning and pre-heating of the mineral aggregate, filler & bitumen to the specific temperature, thoroughly mixing with binder of specified bitumen content, Anti Stripping Agent, Warm Mix Additives as per mix design in Hot Mix Plant of 100-120 TPH capacity, carrying the hot mixed materials by means of tipper, trucks, or any other approved and suitable arrangements, laying the hot premixed materials over the prepared surface by means of paver finisher including manual operation as and when required for proper grade, level and camber thorough rolling with power roller 8 to 12 tonnes smooth wheeled, vibratory and tandem roller with necessary hand packing and pinning to give an even surface, including running expense of all plants and machineries, inclusive of proper traffic control during laying to the satisfaction of Engineer-in-Charge, required quality control tests at required interval etc complete in all respects complete all as specified and directed by Engr-in-Charge. |
| 37 | NOTES APPLICABLE TO SRL ITEM NO. 33 ABOVE : (i) The contractor shall quote the rate against Item considering 5.5% VG-30 bitumen content. Job mix formula as per clause No 505.3.3 of MoRT&H specifications for road and bridge work (Fifth Revision) for bituminous concrete shall be got designed from NIT/ CTL/ Govt Engg College and shall be got approved from GE in writing well before commencement of work without any financial effect to the department. Also the bitumen content shall not be less 5.4% by weight of total mix as per clause 507.2.5 of MoRT&H specifications (Fifth Revision).(ii)The cost of materials, transportation, Job mix formula from lab and testing charges for various tests as required are included in the unit rate quoted by the contractor. (iii) Cost of filler i.e rock dust, hydrated lime or cement is deemed to be included in unit rate.(iv) If qty of binder contents is less than the qty as specified in respective items of BOQ, it shall be adjusted at supply only rates of paving bitumen @ Rs 45.00 Per Kg and if qty of binder contents is more than the qty as specified in respective items of BOQ no adjustment shall be made.(v) After spreading of mix as per clause 507.4.7 of MoRT&H specifications entire surface during the operation shall be rolled with road roller 8-10 tonnes (smooth wheeled) followed with vibratory road roller of 8 -10 tonnes static weight, followed by finish rolling with 6 to 8 tonnes smoooth wheeled tandem roller as per clause No 507.4.8 of MoRT&H specifications (Fifth Revision) and the cost of the same shall be deemed to be included in the quoted rate. |