| 1 | Supply, Laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 Sqmm 3.5 core with and including cable gland & cable lugs complete all as specified and directed by Engineer-in-Charge. |
| 2 | Ditto all as per Serial Item No 1, but for aluminium conductor of size 120 Sqmm 3.5 core. |
| 3 | Ditto all as per Serial Item No 1, but for aluminium conductor of size 95 Sqmm 3.5 core. |
| 4 | Ditto all as per Serial Item No 1, but for aluminium conductor of size 70 Sqmm 3.5 core. |
| 5 | Excavation for earth work by mechanical means (Hydraulic excavator) in foundation trenches or drains (not exceeding 1.5 metre in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 metre, including getting out the excavated hard rock (blasting prohibited) and disposal of surplus excavated hard rock as directed, within a lead of 50 metre complete all as specified and directed by Engineer-in-Charge. |
| 6 | Material and Labour for sand cushioning to underground cable and punning for cushioning of cable 8cm below the cable and 15cm above cable all as specified and directed by Engineer-In-Charge.Note:- Measurement shall be done after punning down of sand. |
| 7 | Supplying and laying un-reinforced precast concrete cable cover, class LV, type 1, flat size 250 mm x 150 mm x 40 mm and abutting each other with gap between adjacent precast concrete cable cover not exceeding 10 mm over underground cables for protection complete all as specified and directed. |
| 8 | Returning, filling in, including spreading, leveling watering and well ramming in layers not exceeding 25 cm in Soft/disintegrated rock complete all as specified and directed. |
| 9 | Removing of excavated rock not exceeding 50 metre from starting points complete all as directed by Engineer-in-Charge. |
| 10 | Material and Labour for cutting of hard standing / Road for laying of pipe line/cable and making good surfaces after laying of pipe line/ cable up to 30cm in depth complete all as specified and directed by Engineer-in-Charge. |
| 11 | Material and Labour for GI tubing medium grade in repairs including accessories for protection of cables on poles / under road crossing of 80 mm bore size complete all as specified and directed. |
| 12 | Supply and laying HDPE duct pipe of bore 100 mm for protection of electric cables complete all as specified and directed by Engineer-In-Charge. |
| 13 | Supply and installation of fast earth electrode 3.0 metre length size model F84, having two MS pipe one inside the other with proper not deep galvanised outer diameter 88 mm and inner diameter 48 mm and the cavity between the rod pipes is filled with ground resistance improvement powder, sealed with both end the outer pipe of electrode should be zinc coated, the electrode should buried directly in the ground by making boring of diameter 10\" with boring machine highly conductive non-magnetic and non-corrosive is to be connected with Gl strip 25 X 4 mm of 2 to 3 metre length to facilitate further connection to earth dolly and provision of earthing chamber in bricks wall size 45 x 45 x 15 cm an having PCC cover of required size complete all as directed and all as per IS 3034 (1981) complete.Note: Gl strip to be measured and paid separately. |
| 14 | Supply and Fix Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25 x 4mm galvanised iron strip complete all as specified and directed. |
| 15 | Supply and Fix PVC FRLS cable duct of size 100mm X 50mm fixed on wall with un slotted type non slip cover including with all accessories including fixing plug, cable tie attachment, wire retainer mounting clamp angle/corner duct, channel ports etc. complete all as specified and directed by Engineer-In-Charge. |
| 16 | Supply and Fix 4 Pole MCCB 250 Amp, 50 Hz, 415 Volt with rupturing capacity 36 KA complete all as specified and directed by Engineer-In-Charge. |
| 17 | Supply install, testing and commissioning of LT Panel board, outdoor type (CPRI Approved), gable roof, floor mounted, factory made suitable for 415volt, 3 Phase, 4 wire, 50 HZ, AC supply system having bus bars chamber with copper bus bars of rating 300 Amps fully insulated by insulation of RYB colour 100 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 40X40X6 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size including lugs and cable gland to incoming and outgoing cable with hinges to panel doors and locking arrangement as desired complete all as directed by Engineer-In-Charge and comprising of the following:-(A) IN COMING(a) MCCB 4 Pole, 415 Volts, 25 KA, 200 Amp rating thermal magnetic release adjustable type (Icu=Ics=100%) -01 No.(b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No.(c) Panel mounted multifunction energy meter of accuracy CL-1.0 rating - 01 No.(B) OUT GOING(a) MCB TPN 415 Volts 63 Amp rating -03 Nos.(b) MCCB 4 Pole, 415 Volts, 25 KA, 160 Amp rating thermal magnetic release adjustable type (Icu=Ics=100%) -01 No.(c) MCCB 4 Pole, 415 Volts, 25 KA, 125 Amp rating thermal magnetic release adjustable type (Icu=Ics=100%) -01 No. |
| 18 | Supply, Laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 Sqmm 4 core with and including cable gland & cable lugs complete all as specified and directed by Engineer-in-Charge. |
| 19 | Supply & laying of 3 Core 1.5 Sqmm sheath PVC insulated flexible copper conductor cable complete all as specified and directed. |
| 20 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 Sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge. |
| 21 | Excavation in trenches for laying of pipe/cables not exceeding 1.5 metre depth and 1.5 metre wide and getting out in hard/dense soil complete all as specified and directed by Engineer-in-Charge. |
| 22 | Supply and fix rigid non-metallic PVC conduit of 20 mm exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. complete all as specified and directed by Engineer-in-charge. |
| 23 | Supply and fix junction box of 1 to 4 way of 20 mm as required etc. complete all as specified and directed. |
| 24 | Supply and laying DWC (Double wall corrugated) duct pipe outer dia 63 mm and inner dia 50 mm confirming IS 16205 (Part 24) for protection of electric cable complete all as specified and directed. |
| 25 | Supply and fixing of timer switch astronomical time watch digital type along with switch for (auto/manual) on and off including suitable incoming MCB and contactor complete distribution board and wiring as per requirement fitted in a FRP Junction box which shall be environment friendly, recyclable, UV resistant, halogen & silicon free, anti-acid & anti corrosive, Degree of Ingress Protection IP 65, Wall Mounting type, including M32 Cable glands for 10/16 Sqmm X 2/3.5/4.0 Core cable incoming & outgoing- 2 Nos with terminals, MCB, Cable Glands etc, complete all as specified and directed by Engineer-in-charge. |
| 26 | Supply and fix light junction boxes of size 130x130x77 mm, shockproof, rustproof, termite resistant, weather proof, of IP 65 and cable entry from bottom, pole/ bollard light mounting arrangement including along with terminals and insulators and MCB SP 6 Amps rating with provision of MCB, Cable Glands, flexible PVC conduit complete all as directed by Engineer-in-charge. |
| 27 | Material and Labour for 40mm dia GI tubing medium grade (ISI marked) with all fitting/accessories for protection of cable on pole/wall and under road crossing including clamps, nuts bolts etc. complete all as specified and directed. |
| 28 | Material and Labour for hard standing / road cutting and repairing the same with road patch material width up to 60 cm all as specified and directed by Engineer in Charge |
| 29 | Supply and Fix LED Bollard light suitable for landscape lighting, IP 65 protection, inverted pyramid tripod type, soft 360° light distribution, Maximum power consumption shall be 10Watt, 3 stage CCCV driver with minimum 4kV surge protection voltage range of 150 to 270Volt AC, CCT around 3000K or warm white light and connecting accessories complete all as specified and directed at site by Engineer in Charge. Note: Rate quoted included for excavation, foundation & earth work. |
| 30 | Supply and fixing LED street light fitting 35-Watt 230 Volt AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as directed by Engineer-in-charge. |
| 31 | Supply and fixing LED flood light 100-watt 230 Volt, AC outdoor type with thermal management in multiple optics and equipped with IP65/66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and as directed by Engineer in Charge. |
| 32 | Supply and fixing post top lantern LED type 40 watt, 230 volts AC outdoor type with decorative post top for 360-degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete all as specified and as directed by Engineer in Charge. |
| 33 | Supply and fix GI pipe Bracket of 40 mm dia medium grade pipe bend to shape of approximate length 1 metre including 2 Nos, MS Clamp of flat iron of suitable size complete with nut, bolt, washers, and welding including two coats of aluminium paints over a coat of red oxide primer all as specified and as directed by Engineer in Charge. |
| 34 | Material and labour Cement concrete (1:3:6) type C-1 using 20 mm graded stone aggregate for pedestal of poles/copping including necessary frame work, fair finishing to exposed surfaces using extra cement complete all as directed by Engineer in Charge. |
| 35 | Supply and fix double door Triple pole and neutral, 4way DB, 415 Volt complete as specified and as directed by Engineer in Charge. |
| 36 | Supply and fixing MCB SP 5 to 32 Amps rating 240 Volt, 10KA \"B\" curve in the MCB DB complete with connection testing and commissioning all as specified and directed |
| 37 | Supply and fixing MCB TPN, 40 to 100Amps rating 415 Volt, 10KA \"B\" curve in the MCB DB complete with connection testing and commissioning all as specified and directed |
| 38 | Supply and Fixing Surface Modular Box of 6 way along with 6 way Modular plate and 2 Nos of 16 Amps Switches and 6/16Amps multipurpose Sockets with connected internal wiring complete all as specified and directed by Engineer in Charge. Notes: Modular Plate, Switches & Sockets are inclusive of the rate quoted. |
| 39 | Supply, install, testing and commissioning of LT 415 Volt, 4 wire AC 50 Hz, factory made, CPRI approved, wall mounted out door type Panel of suitable size, Centre opening in two half front ,inner door shall be individual hinged type door for individual control switches made out of CRCA sheet and outer door made out of 3 mm thick with locking arrangement , duly powder coated and along with gable roof, ventilation louvers & including control wiring with 10 Sqmm Copper wire including copper bus bar of 200 amps capacity complete to accommodate the following accessories :- (A) INCOMING(a) Solar Net Meter of size 600mm x 600mm x 300 mm.(b) MCCB 160 Amp, 25 KA, 4 pole, 415 Volts Thermal adjustable type– 01 No(c) Solar Check Meter of size 250mm x 150mm x 100 mm(d) MCB TPN 415 Volts 40 Amp rating -01 Nos(e) Multifunction meter along with suitable CT, PT - 01 Set (f) LT danger notice plate made out of 1.6 mm thick MS sheet - 01 No (g) Indicator lamp LED type (set of 3) - 1 set Cond/--- |
| 40 | (B) OUT GOING(a) MCB TPN 415 Volts 63 Amp rating -02 Nos (b) MCB TPN 415 Volts 32 Amp rating -02 Nos (c) MCB SPN 415 Volts 20 Amp rating- 01 Nos T(d) MCCB 4 Pole, 415 Volts, 25 KA, 125 Amp rating thermal magnetic adjustable release type including spreaders, nut, bolts, lugs etc. (Icu=Ics=100%) Notes:1. Rates quoted must be included of panel accessories like cable gland, Aluminium Lugs, control wiring, Bus bar, Digital Ammeter, Voltmeter, danger plate, indicator lamp, push button, single phase preventer -02 Nos, MCCB\"s and disconnecting existing Solar Net and Check Meter along with cables from the wall and re connecting and fixing of the same in LT Panel along with proper dressing of cables etc.2. The contractor should lease with state electricity board (i.e., MSEB) for the necessary connections of Solar Net Meter and Check Meter at his own expenses.3. Rate quoted does not include the item cost of Solar Net and Check Meter.4. The panel design and drawing should get approved by the department before placing order to the manufacturer. |
| 41 | Supply, installation, testing and commissioning LT 415 Volt, 4 wire AC 50 Hz, factory made, CPRI approved, wall mounted out door type Panel of suitable size, Centre opening in two halve front ,inner door shall be individual hinged type door for individual control switches made out of CRCA sheet and outer door made out of 3 mm thick with locking arrangement , duly powder coated and along with gable roof, ventilation louvers & including control wiring with 10 Sqmm Copper wire including copper bus bar of 100 amps capacity complete to accommodate the following accessories :- (A) INCOMING(a) Meter of size 250mm x 150mm x 100 mm(b) MCCB 63 Amp 415 Volts 25KA rating – 01 No(c) Multifunction meter along with suitable CT, PT - 01 Set (d) LT danger notice plate made out of 1.6 mm thick MS sheet - 01 No (e) Indicator lamp LED type (set of 3) - 1 setCond/-- |
| 42 | (B) OUT GOING(a) MCB TPN 415 Volts 40 Amp rating -02 Nos (b) MCB SPN 415 Volts 20 Amp rating- 02 Nos Notes: 1. Rates quoted must be included of panel accessories like cable gland, Aluminium Lugs, control wiring, Bus bar, Digital Ammeter, Voltmeter, danger plate, indicator lamp, push button, single phase preventer -02 Nos, MCCB\"s and disconnecting existing Meter along with cables from the wall and re connecting and fixing of the same in LT Panel along with proper dressing of cables etc,.2. The contractor should lease with state electricity board for the necessary connections of Meter at his own expenses.3. Rate quoted does not include the item cost of Meter.4. The panel design and drawing should get approved by the department before placing order to the manufacturer. |
| 43 | Supply, Laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 Sqmm 3.5 core with and including cable gland & cable lugs complete all as specified and directed by Engineer-in-Charge. |
| 44 | Supply and laying High density polyethylene pipes (HDPE) of pressure rating 6 Kg/cm2 and size 50 mm dia laid in trenches for protection of electric cables complete all as specified and directed. |
| 45 | Supply and fixing of MCCB incoming TPN DB vertical type, suitable for 100/125 Amps MCCB as incomer, made of sheet steel, powder painted with neutral bus bar of suitable rating, neutral link, IP-43-IK09 protection grade, 415 Volts VTPN with 6 way double door complete all as specified and directed by Engineer-in-charge |
| 46 | Supply and fixing MCB SP 40 to 63 Amps rating 240 Volt, 10KA \"C\" curve in the MCB DB complete with connection testing and commissioning all as specified and directed. |
| 47 | Supply and fixing MCB TP 63 Amps rating 415 Volt, 10KA \"C\" curve in the MCB DB complete with connection testing and commissioning all as specified and directed |
| 48 | Supply and fixing MCCB 4 Pole, 125 Amps with breaking capacity 25 KA, 415 Volt, Thermal Adjustable type, complete all as specified and directed by Engineer-in-Charge |
| 49 | Supply and fixing MCCB 4 Pole, 160 Amps with breaking capacity 25 KA, 415 Volt, Thermal Adjustable type, complete all as specified and directed by Engineer-in-Charge |
| 50 | Material and labour for sub main/circuit wiring with 2 runs of 6 Sqmm plus one run 6 Sqmm earth wire of FRLS PVC insulated copper conductor, single core cable in surface/ recessed as required withand including PVC casing capping complete all as specifie |
| 51 | Supply and fix power unit with 25 Amp SP MCB and 16 Amp plug socket complete all as specified and directed. |
| 52 | Material and Labour for disconnecting and reconnecting of LT XLPE cables/MCCBs of various sizes from 10 to 50 Sqmm from existing panel /Changeover/ MCCB panel including removing of cable, preparation of cable for connection, suitable Aluminium lugs, nut, bolts, glands, GI pipe etc. complete all as specified and as directed on site by Engineer in Charge.Notes: (i) The cost of earth work for taking out LT cable loop and refilling and Aluminium Lugs will deem to be included in above quoted rate. (ii)GI pipe to be measured under separate BOQ item mentioned. |