| 1 | GENERAL SUMMARYNOTE: Schedule ‘A’ Part - I to VIII are prepriced by MES under Ser No. 2.00to 5.00. Bidders shall insert their lumpsum amount in the Green coloured field under Col-7 only. |
| 2 | Lumpsum price worked out by the contractor for “BUILDINGS / STRUCTURES ” as listed in Schedule ‘A’ Part - I |
| 3 | Lumpsum price worked out by the tenderer for \"SITE CLEARANCE / SITE DEVELOPMENT/ EARTH WORK/ EXCAVATION\" as listed in Schedule ‘A’ Part-II |
| 4 | Lumpsum price worked out by the tenderer for \"INTERNAL ELECTRIFICATION\" as listed in Schedule ‘A’ Part-III |
| 5 | Lumpsum price worked out by the tenderer for \"INTERNAL WATER SUPPLY\" as listed in Schedule ‘A’ Part-IV |
| 6 | Lumpsum price worked out by the tenderer for \"SEWAGE DISPOSAL\" as listed in Schedule ‘A’ Part-V |
| 7 | Lumpsum price worked out by the tenderer for \"AREA DRAINAGE\" as listed in Schedule ‘A’ Part-VI |
| 8 | Lumpsum price worked out by the tenderer for \"EXTERNAL WATER SUPPLY\" as listed in Schedule ‘A’ Part-VII |
| 9 | Lumpsum price worked out by the tenderer for \"EXTERNAL ELECTRICAL SUPPLY\" as listed in Schedule ‘A’ Part-VIII |
| 10 | SCHEDULE \"A\" PART - IXMISCELLANEOUS ITEMSNOTE:Schedule ‘A’ Part - IX is not prepriced by MES and prepriced rate indicated as 0.00 under Col.5 signifies this fact only. Bidder shall insert their rates in Green colour filled under Col-7. |
| 11 | Ponit wiring with 1.5 sqmm FRLS PVC insulated and unsheathed copper conductor multistranded 1100 volts grade, ISI marking drawn thorugh and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marking, concaled including provn of pre fabricated galvanised module box of 2 mm thick of suitable size as required at site for fixing switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity, connected to earth duly complete all as specified and directed for the following: |
| 12 | (a) One lightpoint controlled by one switch |
| 13 | (b) One fan (Ceiling/Wall/Exhaust fan) point controlled by one switch |
| 14 | (c) One 3 pin socket outlet 5 Amps socket on Independent board |
| 15 | (d) One 3 Pin socket outlet 5 amps socket on same board |
| 16 | All as per Item No. 11 here-in-before but One3 pin socket outlet 15 amps socket on independent board with 2.5 sqmm FRLS PVC wire and one run of 2.5 sqmm copper cable for earth continuty. |
| 17 | M&L Submain wiring for Single phase supply with PVC insulated FRLS copper conductor cable unsheathed for circuit along with earth wire incl PVC rigid conduit of suitable size with acessories complete for 2 runs 4.0 Sqmm and 1 runs 4.0 Sqmm complete and making good the disturbed area all as specified and directed.Note: 3 run of 4 sqmm & one run of PVC conduit shall be measuredas single unit |
| 18 | M & L for Earthing complete with galvanised steel plate electrode, 600 x 600 x 6 mm thick, buried directly in ground (earth pit not less than 2.25 mtrs deep below nominal ground level) with top edge of the plate not less than not less than 1.5 metres below nominal ground level connected to earthing lead of 4 mm dia galvanised iron or steel wire all as shown in plate No. 3 of SSR PART 1 of 2009 to the earthing test point all as specified and as directed.Note :- the cost of excavation and earth work PCC pit and RCC cover funnel & watering pipe, wiremesh, charcoal dust and common salt earth lead protection pipe upto 7.5 Rmt shall be deemed included in the unit rate for earthing all as specified and as directed. |
| 19 | M&L for brick masonary valve chamber of size 900x900x900mm ( internal size) by providing PCC 1:2:8 tyepe D2 foundation 100 mm thickbrick work in CM 1:4 plastering 15mmthickin CM 1:4 internal surfaces completely and external surfaces completelyand external surfaces upto 150mm below GL, 75mm thick PCC 1:2:4 type B as in coping valve chamber cover made up of 40x40x5mm thick angle iron frame and 3.15 mm thick MS sheet cover complete with lockeing arrangement and handle including painting steel surfaces with two coats of enamel paint over a coatof red oxide primer including dismantling the existing damaged valve chamber and removing debris away from the premises etc complete |
| 20 | Supply and lay Double walled Corrugated High density poly ethylene pipes(HDPE) of pressure rating 6 kgf/cm2 of size 40mm laid in trenches complete all as specified and directed. |
| 21 | Supply and fix energy saving ,street light fittings LED 45 watts luminaire with high power LEDs and unique flood optics to ensure uuniform distribution and saving upto 50% w.r.t conventional systemand maintenance free system ,ideal for area lighting , high mast and bill board including fixing arrangement on pole by providingGI pipe medium grade 25 mm dia 1.5 Mtrin length bent to an angle 135 degreeincluding two coats of aluminium paint over a coat of zinc chromate primer along with bolts, nuts etcwith suitable size MS Clamp two Nos made out of 25x3 mm FI, prewired and including connecting up with 3 core flexible copper conductor cable of suitable size from connector to fitting all as specified andas directed by Engr-in-Charge |
| 22 | Supply and fix LED search light 2000 watt 220 volt,50 Hzs irradiation range over 1800 mtr 360 degree turning angle , waight approximate 42 kgsmade stainless steel body and alluminium alloy for fitting base supporting arm and tempered glass and body should be air tight to bear pressure 0.025Mpa and can be equipped with a flexible rubber house to exhaust lever heated air with suitable try pot stand for fixing of lightall as specified and directed |
| 23 | Supply and fix weather proof cable junction boxes suitable for outdoor installaions with knockout for cable entrylooping in box PVCwith side dimension155mmx210mmx92 mm comprising of connector -01nos including mounting arrangementsandlugs etc. complete all as specified and as directed. |
| 24 | Supply and fix PVC insulated two single core 1.5 sqmm FRLS copper conductor and one run of 1.5 sqmm multistranded copper conductor as earth continuity conductor drawn through andincluding suitable dia non metallic rigidPVC conduitand accessoriescomplete all as specified and as directed.Note : (i)Two run 1.5 Sqmm of single core, one run of 1.5 sqmm earth conductor and PVC conduit will be measured as one RM. |
| 25 | Repair/replacement ofswitching ON and OFF the street lights based on astro time controlling switch for automatic controller of street light on 2.0 mm thick sheet metal enclosure consist of 230 Volt astro Time Switch, MCB SPN 40 Amp.contactor 25 to 32 Amp, selector switch for auto and manual and internally pre wired, terminal blocks mounting brackets, cable glands and openable door with lock and key and manual setting features fixed on wall/panel board complete all as specefied and directed. |
| 26 | SIGNATURE OF CONTRACTOR |